Gurugram
08042756762
S – Earthing/Grounding Regulations
Earthing/Grounding Requirements
Conductors and Earth rods
As with lightning protection,  the first choice faced 
by the designer of an earthing system is the type 
of conductor to be used. The correct
choice of conductor is extremely important,  
whether it be a simple below ground electrode or 
a complex computer room signal reference grid.
Conductors
Typical conductor types include flat tape,  solid circular and stranded 
cable. For above ground applications,  copper,  aluminum and steel may 
be used. Below ground,  copper is the most common choice due to its 
high resistance to corrosion.
Examples of typical earthing installation
Types of Earthing Connections
Mechanical or Exothermic type connections are both used in the International 
World for earthing connections.  Specific countries and clients have preferences for 
one method or the other,  but in general,  both are widely used and are accepted 
engineering practice.
Examples of typical earthing installation
Protective equipotential bonding via multiple cables
Typical Earthing Arrangement
Various earthing and bonding conductors and components
Surge Protective Devices
When using surge devices make sure they comply with IEC 
61643 and connect in the appropriate manner
Typical Earthing Cable Sizing
The cross‐sectional area of branch conductors connecting equipment and structures 
to plant earth ring shall be as followed as a rule of thumb as recommended by various 
earthing equipment manufacturers and IEC 62035 &  AS1768/2007
To metallic enclosures of HV electrical equipment 70mm²
To metallic enclosures of LV electrical equipment,  having a supply 
cable cross‐sectional area ≥ 35mm²
70mm²
To metallic enclosures of LV electrical equipment,  having a supply 
cable cross‐sectional area < 35mm²
25mm²
To control panels,  etc. 25mm²
To non‐electrical equipment exposed to lighting,  e.g. tanks,  columns 
and tall structures
70mm²
To other non‐electrical equipment 25mm²
Earthing and Bonding Systems
The principal reasons for earthing and bonding in electrical installations are:
• To eliminate the possibility of electric shock to personnel
• To enable protection devices to operate correctly so that the duration of fault currents are kept 
to a minimum
• To equalize the voltage potential of normally non‐current carrying metalwork
• To prevent electrostatic charge of process plant to fluid movement
In hazardous areas,  the elimination of sources of ignition is very important and effective earthing
and bonding play an important role.  EN60079‐14 clause 4.7 states that “care shall be taken to 
ensure that the earthing and potential equalization bonding provisions in hazardous areas are 
maintained in good condition”
Types of common systems are as followed:
• TN‐S – System has separate neutral and protective conductors throughout
• TT – A system in which one point of the source of energy is directly earthed but which 
electrically independent of the electrodes used to earth the exposed conductive parts of the 
electrical system.
• TN‐C – A system in which a single conductor serves as both the neutral and protective conductor 
in part of a system
• IT – A system in which there is no direct connection between live parts and earth but exposed 
conductive parts of the electrical installation are earthed.
The EN/IEC 60079‐14 installation directive 
requires equipotential bonding within hazardous 
areas of Zones 0 and 1 to prevent the occurrence 
of sparks capable of causing ignition or of a 
temperature rise caused by potential differences. 
Implementation of the equipotential bonding 
must comply with the system configuration to 
DIN VDE 0100 Part 410 and the design ratings to 
DIN VDE 0100 Part 540. 
Full equipotential bonding is achieved by 
connecting not only the housings of the 
electrical equipment into the equipotential
bonding,  but also all other accessible,  conductive 
structural parts such as building construction,  
metal containers,  piping etc. Extraneous 
conductive parts which do not belong to the 
structure or installation of the system (e.g. door 
frames,  window frames) need not be 
incorporated into the equipotential bonding
Equipotential Bonding in 
Hazardous Areas
The IEC started working on coming up with a universal design for plugs and sockets 
worldwide,  trying to ensure that dangerous situations could not arise during the 
periods when the new system and the multitude of existing ones had to exist side by 
side.  The first drafts of a universal system considered by SC 23C proposed all flat pins 
and this was pursued for many years. However,  at the voting stage,  objections grew 
and,  many National Committees expressed themselves more in favor of a round pin 
solution. The other serious problem encountered was in trying to find a unique 
solution for 125V and 250V distribution systems. After long,  and often acrimonious,  
discussion,  the subcommittee came to an acceptable solution which was finally 
formulated in 1986 as publication IEC 906‐1 (now IEC 60906‐1) for 250V installations 
using round pins and in 1992 as IEC 906‐2 (now IEC 60906‐2) for 125V installations 
using the familiar US flat pin design.
More recently,  in the 1990s,  CENELEC,  in Europe,  was put under pressure by the 
European Commission to devise a harmonized plug and socket system for Europe. 
CENELEC took as its starting point the IEC standard of 1986 and spent thousands of 
man‐hours undertaking the almost impossible task of modifying the design with the 
aim of ensuring 100% risk‐free operation of the system when used in conjunction 
with all the existing types in Europe. Naturally,  apart from the technical difficulties,  
there was the clash of the many vested commercial and political interests and it was 
not surprising that,  after much work and many meetings,  CENELEC had to admit 
defeat and abandon its efforts.
Universal Plug and Socket Systems??
Nov 17th, 2017 11:15 AM

Keywords