CALCULATION OF LIGHTNING PROTECTION Application o...

CALCULATION OF LIGHTNING PROTECTION Application of Structure (A)= Houses & Buildings as per Table Multiplying Factor = 0.3 Type of Constructions (B)= Steel framed encased without Metal Roof as per Table Multiplying Factor =0.2 Contests or Consequential Effects (C)= Domestic / Office Buildings as per Table Multiplying Factor =0.3 Degree of Isolation (D)= Structure in a large area having greater height as per Table Multiplying Factor =0.4 Type of Country (E)= Flat country at any level so as per Table Multiplying Factor =0.3 Overall Multiplying Factor (M) =0.3×0.2×0.3×0.4×0.3 Overall Multiplying Factor (M) =0.00216 Overall Risk Factor Calculated (xc)= M x P Overall Risk Factor Calculated (xc)= 0.00216 x0.05098 Overall Risk Factor Calculated (xc)= 000110127 B