EXTERNAL LIGHTNING PROTECTION SYSTEM AS PER INDIAN STANDARDS IS/IEC 62305-NBC 2016
GENERAL
Lightning Protection System shall be in accordance with IS IEC 62305-3 & NBC-2016.
Lightning Protection consists of external Protection for the building with Air termination,
Down Conductors and Earthing and Internal protection for power lines with Surge
Protective devices.
AIR TERMINATION SYSTEM
Material, Configuration and Minimum cross sectional area of air terminal & down
conductors
Air Termination mesh conductor and down conductors: 8 mm Aluminium alloy round
conductor (50 mm2).
Air Termination Rod: 10 mm, 16 mm & 40 mm solid Aluminium rods (combination of
sizes
JOINTS
Aluminium accessories connection between Aluminium materials are necessary. Stainless
steel accessories if connections are between aluminium and copper / copper coated
materials.
Earth Termination Conductor shall be of 10 mm solid copper coated steel conductor
(minimum 100 microns min coating)
Earth Termination Joints in soil shall be done with Exothermic welding.
AIR TERMINAL HOLDER
Conductors shall be securely fixed on the terrace by means of concrete with suitable fixing
materials fixed on the roof by adhesive or cement mortar taking care of varying weather
conditions. Plastic air termination conductor holder is not allowed. The minimum height of
this air terminal holder shall be 50 mm to avoid the contact of conductor with water
EXPANSION PIECE
In order to take care the expansion of metal in summer and contraction in winter,
expansion piece with suitable connectors shall be used at every 20meter distance of
horizontal air termination mesh.
JOINTS AND BENDS
The lightning protective system shall have few joints as far as possible & air terminal &
down conductor have to be straight. Where it is not possible, it should NOT be bent at 90
degree (right angles) & should have a curved path of 45 degree bend.
DOWN CONDUCTOR SYSTEM
In order to reduce the probability of damage to electronic/electrical equipment, the
down conductors shall be arranged in equal distance in such a way that from the
point of strike to earth, several parallel current paths exist& length of the current path
shall be minimum. Down conductors shall be installed at each exposed corner of the
structure as a minimum. Maximum distance between down conductors shall be as per the table above
TEST JOINTS
At the connection to the earth conductor, a test joint should be fitted on each down
conductor at a height of one meter from the ground, except in the case of natural down
conductors combined with foundation earth electrode. The purpose of test joint is measure the earth resistance value. The remaining portion of down conductor (i.e., after
the test joint should be mounted inside a PVC pipe of minimum 3 mm thickness.
QUALITY & CONFIRMATIONS
All materials and accessories shall be tested as per IEC 62561 for its mechanical /
corrosion resistant / electrical conductivity. Vendor shall provide test reports along
with completion certificate. GI (Hot dip galvanized or zinc electroplated) fixing
materials and fasteners are not allowed.
Keywords
Plastic air termination conductor holder
EXTERNAL LIGHTNING PROTECTION SYSTEM
several parallel current paths
Minimum cross sectional area
Expansion Piece with connector to compensate the expansion and contraction of Solid Round Al. Conductor during temperature as per IS/IEC
Stainless Steel cross connector for 8- 10 mm round AL conductor to meet the requirement of IS/IEC - 62305.
earth resistance value
Terrace Aluminium Conductor Holder
8 mm Aluminium alloy
8 MM Aluminium Condudtor
air terminal holder
10 mm solid copper
Earthing Conductor Aluminium Wire 8mm
LIghtning Protection As Per NBC