1G Ω Humidity 0-95% (R.H) Operating temperature -40 to +80 deg C. 3.20.8For more details regarding equipotential protector, Ref Annexure-2 – IEC 62305- 3 Standard. 3.21 Lightning Protection System(LPS) –Earth termination network, types and specifications:- 3.21.1 An earth electrode should be connected to each down conductor of LPS. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 50/124 Version 2.0 3.21.2 Each of these earths should have a resistance not exceeding the product given by 10Ω multiplied by the number of earth electrodes to be provided. For example, for a system with 15 down conductors, the individual earth reading should not be more than 10x15=150Ω. The whole lightning protective system, including any ring earth, should have a combined resistance to earth not exceeding 10Ω without taking account of any bonding. 3.21.3 A reduction of the resistance to earth to a value below 10Ω hasthe advantage of further reducing the potential gradient around the earth electrode when discharging lightning current. It also further reduces the risk of side flashing to metal in or on a structure. Hence every effort shall be made to ensure as much low ground resistance as possible. 3.21.4 The Earthing shall be provided/ made as per specifications given for Earthing System in the manual. ---------------------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 51/124 Version 2.0 Chapter - 4 Earthing Systems 4.1 Earthing:- Lightning, Surges or Unintentional contact between an energized electric conductor and the metal frame or structure that encloses it or an insulation failure in electrical equipment’s etc., can cause dangerously high voltages in the electrical distribution system. Under such circumstances, grounding provides an alternative low impedance path and thereby minimizes damages. A good and an efficient earth ensure that all parts of apparatus other than live parts shall be at earth potential that is zero at all the time. The scope of this section shall cover the following:- a) Earthing electrode/station b) Earthing conductors c) Earthing of equipment and installation The earthing resistance depends on:- a) Resistance of electrode b) Contact resistance between electrode and soil c) Resistance of soil between electrode surface and infinite earth. Resistance of electrode and contact resistance between electrode and soil are very small fraction of an ohm. Approximately 90 % of an earth resistance lies within 2 m between electrode and earth. Moreover, Earth conductivity is essentially electrolytic in nature and is affected by moisture content of soil, its chemical composition and concentration of salt dissolved in the contained water. It is also dependent on grain size and closeness in packing. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 52/124 Version 2.0 4.2 Selection of Earth Pit Site:- Following is the order of preference for selecting an earth pit position. Wet marshy ground Clay/loamy soil with little sand Clay/loamy soil with sand, gravel and stones Damp and wet sand 4.3 Scope: This specification of earthing system describes in detail, the components to be used and the procedure for constructing the earth system. The main purpose of this is to maintain consistent low earth resistance value over the years without contaminating the Ground water. 4.4 Components: The Earthing system shall consist of Earth Rods / plates and conductive and eco-friendly backfill compound, Earth termination clamps and Earth Bus Bar to facilitate connections to the equipment. The type earth electrode shall be any of the following, as specified:- (a) Pipe / rod earth electrode ; (as per IS 3043) (b) Plate earth electrode; (as per IS 3043) 4.5 Methods of Implementations:- The earthing can be implemented in four ways depending on the requirements, site and ground conditions:- 4.5.1 Conventional earthing using copper plates as per IS 3043:- 4.5.1.1 Earth Pit of the Size of 1 meter diameter and 3 meter depth shall be excavated, after depth of 3 meter the size of excavation shall be 900X300X900mm depth. 4.5.1.2 Plate Electrodes shall be in vertical position. 4.5.1.3PVC pipe for Watering shall be used of 40mm Diameter, length of 3m ( contain hole of 12mm Diameter in Zigzag manner starting from 15cm away from bottom to 2 meter height ). 4.5.1.4 At bottom 150mm layer of salt and charcoal power shall be installed, then Plate shall be installed. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 53/124 Version 2.0 4.5.1.5 Min 120 Kg each of charcoal powder and salt shall be used for each earthing pit. 4.5.1.6 The plate/pipe electrode, as far as practicable, shall be buried below permanent moisture level but in no case less than 2.5 meter below finished ground level. 4.5.1.7 600 mm × 600 mm × 3.15 mm copper plate buried at a depth of 8 ft in vertical position with the pit filled with alternate layers of charcoal and salt up to 4 ft from bottom. 4.5.1.8 The copper plates shall be connected to earth strip by riveting and brazing at no less than two points and the joints shall be protected by heavy coat of bitumen. 4.5.1.9 Schematic diagram for copper plate earthing is shown in Figure 4.1. Figure- 4.1 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 54/124 Version 2.0 4.5.2 Earthing rods directly driven into the earth :- 4.5.2.1 The length of the electrode shall be either 1.22meter or 2meter or 3meter based on the application. 4.5.2.2 Electrodes used for neutral earthing and lightning protection earthing shall be at least 3 meter long and for other applications, electrodes of at least 1.22meter or 2meter length may be used. 4.5.2.3 Earthing System is depicted in Fig 4.2(a) and 4.2(b) below:- Figure-4.2(a) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 55/124 Version 2.0 Figure-4.2(b) 4.5.2.4The combined earth rod length of a system should be not less than 9 meter whilst each individual earth rod should be not less than 1.5 meter in length. Figure-4.3 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 56/124 Version 2.0 4.5.3 Chemical earthing:- 4.5.3.1 A copper plate or copper coated rod, conventional earthing system should be used as a rule. In general salt and charcoal is used as backfill material for conventional earthing pits and these are eco-friendly. 4.5.3.2 In extreme conditions of rocky or sandy or dry condition where it is difficult to achieve the desired performance of earthing terminals by conventional system, chemical earthing may be employed. 4.5.3.3 The backfill material used in chemical earthing systems for soil treatment shall be highly conductive and should be certified as non-polluting and safe for use near potable ground water systems. 4.5.3.4 The ground conductivity enhancing backfill Material shall be a compound having a low resistance in the range of 0.12 ohm/Meter as specified in IEEE 80 (5 % of the Resistivity of Bentonite), non-corrosive highly conductive powdered material that improves grounding effectiveness, especially in areas of high soil resistivity such as rocky and sandy areas. 4.5.3.5 This material shall be suitable to be installed in either slurry or dry form. The backfill material shall confirm to the following specifications: Shall be highly electrically conductive and non-soluble. Shall not leach into ground. Shall be electronically conductive (like in metals) and shall not depend on moisture / salt for conduction Shall have a resistivity of less than 0.12 ohm/meter Shall be compatible with all copper grounding systems Shall contain a corrosion inhibitor to mitigate corrosion of copper Shall not contain hazardous chemicals Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 57/124 Version 2.0 Shall be certified to ANSI / NSF standard 60 as safe for use near potable ground water resources Shall not be affected by drought and shall be stable between -10˚ to +50˚C temperature. Shall be suitable for any kind of soil Where, the water table is high or runoff water is foreseen, the backfill compound shall solidify as specified in BS: 7430.The compound shall set like concrete to prevent erosion over a period of time. However under such condition only conventional earthing system should be used. NOTE:-Ref - BS7430 & IEEE80 where use of Carbon backfill compound for obtaining low resistance and maintenance free earthing is clearly recommended under specific conditions. 4.5.4 Horizontal / Lateral Earthing:- Whenever it is not possible to excavate to a depth where the vertical earth electrodes can be installed, the Lateral / Horizontal earthing method shall be adopted as follows:- 4.5.4.1 Three pits of 350 x 150 mm shall be dug to a depth of 3 feet and at a distance of at least 2meter from each other. 4.5.4.2 They can be laid either in a straight line formation or a triangular formation depending on the space availability at site. 4.5.4.3 One copper bonded steel plate of 300 mm× 300 mm× 3 mm shall be placed in each of the earth pits. 4.5.4.4 The earth pits shall be filled with the highly conductive and ecofriendly backfill material up to 6 inches above the top of the plate. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 58/124 Version 2.0 4.5.4.5 These plates shall be interconnected using copper flat / strip of at least 50 sq. mm cross sectional area. Such flat / strip shall be installed in a trench of 100 mm width at a depth of 600 mm (0.6m) from the ground level. 4.5.4.6 The entire trench shall be filled with the highly conductive and eco-friendly backfill material in such a way that there is a minimum of 2 inches of compound on the top and bottom of the interconnecting strip. 4.5 Earth Electrode Specifications:- 4.5.1 The electrodes shall be preferably in one piece of the desired length. 4.5.2 The electrode shall be a solid steel rod made of high tensile low carbon steel and coated with molecularly bonded electrolytic copper on the outside (as per UL 467 or equivalent) . The Earth electrode shall conform to the following specifications : Steel core: 600 MPa The thickness of the copper coating shall be at least 250 microns. Copper jacket should not crack on bending of earth rod Copper: 99.9% pure electrolytic copper Copper Structure: Very fine grain structure and highly ductile Copper Bonding: Fully bonded with steel core Nominal Diameter over Copper: 14.5mm Threads: Rolled into copper M16x2 The electrode diameter shall be 14.2 mmdia . Ends: Chamfer and Pointed (2mm and 6mm x 45deg) The electrode should be able to carry a minimum short time current of 15 kA for one second. Couplers should be made of brass Clamps should be made of brass or stainless steel Driving head or striker head should be of High tensile steel Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 59/124 Version 2.0 Driving tip should be of mild steel The earth electrode shall carry standards marking and manufacturer’s name. Clamps and fixtures should be used in the earthing system to ensure perfect and reliable contact. 4.5.3 Earth rod and accessories are depicted in Figure 4.4 below:- Figure-4.4 NOTE: - Ref – IS-3043 & IEC-60364 where use of such electrodes are permitted & the disadvantage of using plate electrodes are highlighted Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 60/124 Version 2.0 4.6 Soil Treatment:- Approximately 90 % of resistance between electrode and earth lies within a radius of 2m from the electrode. So, for soil treatment, to reduce the earth resistance, a shallow basin, 0.5m around the top of the electrode, half a metre in radius is excavated. This basin is then applied with artificial agents like NaCl, CaCl2, Na2CO3, CuSO4, salt, soft coke, charcoal in suitable proportion. Then the basin is filled several times with water for allowing it to percolate into the ground. 4.7 Earthing System Inspection Chamber:- 4.7.1 A 300X300X300 mm (inside dimension) concrete box with smooth cement plaster finish shall be provided on the top of the pit. A concrete lid, painted black, approx. 50 mm. thick with pulling hooks, shall be provided to cover the earth pit. 4.7.2 Care shall be taken regarding level of the floor surrounding the earth so that the connector is not too deep in the masonry or projecting out of it. 4.7.3 On backside of the cover, date of the testing and average resistance value shall be written with yellow paint on black background. 4.7.4 Alternatively prefabricated earthing inspection chambers may also be used. These have precise dimension and better service life. They are convenient to install and require low maintenance. A Polymer or CI cover shall be provided on the top of the earth system. The prefabricated Earthing inspection chamber should be light weight and suitable for extreme weather conditions. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 61/124 Version 2.0 4.7.5Care shall be taken regarding Care shall be taken regarding level of the floor surrounding the earth so that the connector is not too deep in the masonry or projecting out of it. 4.7.6 Grounding test terminal box shall be installed at an appropriate location suitable for testing the earth resistance. 4.7.7 Typical Inspection Chamber is shown in Figure 4.5 below:- Figure 4.5- Inspection Chamber 4.8 Earthing Conductor: - 4.8.1The earth conductors shall be fixed to the wall/columns etc., at every 500mm with 10mm spacers. The total earthing system shall be mechanically and electrically connected to provide independent path to earth. 4.8.2If the conductor is protected from corrosion, the area of cross section for copper conductor shall be more than 16 mm2 . Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 62/124 Version 2.0 4.8.3If the conductor is not protected from corrosion, the area of cross section for copper conductor shall be more than 25 mm2 . 4.9 Earth Resistance: The earth resistance of combined earth system (to be measured at EEB) shall be less than or equal to 1 ohm, as per the requirement. It shall be measured by an approved earth testing apparatus for individual earth pits. The procedure for measuring earth resistance is given in Chapter- 6. 4.10 Equipotential Earth Bus bar and its connection to equipment’s & Surge protection devices in the Equipment room: - 4.10.1 Equipotential earth bus bars 4.10.1.1There shall be one Equipotential earth bus bar for each of the equipment room. The Equipotential earth bus bars located in individual equipment rooms shall be termed as Sub Equipotential bus bars (SEEB). The Equipotential earth bus bar connected to Class ‘B’ SPDs and the main earth pit shall be termed as Main Equipotential earth bus bar (MEEB). 4.10.1.2The EEBs shall have pre-drilled holes of suitable size for termination of bonding conductors. The EEBs shall be insulated from the building walls. Each EEB shall be installed on the wall with low voltage insulator spacers of height 60mm. The insulators used shall have suitable insulating and fire resistant properties for this application. The EEBs shall be installed at the height of 0.5m from the room floor surface for ease of installation & maintenance. All terminations on the EEBs shall be by using copper lugs with spring washers. 4.10.2 Bonding Connections:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 63/124 Version 2.0 4.10.2.1 To minimize the effect of circulating earth loops and to provide equi-potential bonding, “star type” bonding connection is required. As such, each of the SEEBs installed in the rooms shall be directly connected to MEEB using bonding conductors. Also, equipment/racks in the room shall be directly connected to its SEEB. The bonding conductors shall be bonded to their respective lugs by welding. 4.10.2.2All connections i.e. routing of bonding conductors from equipment’s to SEEB & from SEEBs to MEEB shall be as short and as direct as possible with min. bends and separated from other wiring. However, connection from SPD to MEEB shall be as short as possible and preferably without any bend. 4.10.2.3Materials and dimensions of bonding components for connection of individual equipment’s with Equipotential bus bar and earth electrode shall be as given below:- Component /Bonding Material Size Main Equipotential earth busbar (MEEB) Copper 300X25X6 mm (min.) Sub Equipotential earth busbar (SEEB) Copper 150X25X6 mm (min.) Individual equipment’s to SEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 10 sq.mm SEEB to MEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 16 sq.mm Surge protection devices (SPD) to MEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 16sq.mm Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 64/124 Version 2.0 MEEB to main earth electrode. Multi-strand single core PVC insulated copper cable as per IS:694 (Duplicated) 35sq.mm Main earth pit to other earth pit in case of loop earth Copper tape 25X2 mm 4.11 Markings for Earthing systems:- 4.11.1 Earth bars and terminals at all switch boards shall be marked permanently as “E”. 4.11.2 Main earth terminal shall be marked safety earth – “DO NOT DISCONNECT”. 4.11.3 All earth pits shall be identified properly i.e. by suitable nomenclature identifying earth pit with the facility, Earth pit no etc. 4.12 Earthing System Requirement for CNS facilities:- 4.12.1 The electronic ground conductor shall be PVC insulated standard copper wire of 22 mm² or larger. One such conductor shall run from each equipment area or grouping of related electronic equipment and be terminated at the grounding test terminal box. Electronic ground conductors shall not be interconnected except at the common point. 4.12.2 Each cabinet and isolated item of electronic equipment shall be individually connected to the electronic ground conductor by the shortest possible route. The connecting jumper wire shall be 8 mm² or the size of the power feeder to the electronic equipment cabinet, whichever is larger. In addition, cabinets which are installed sideby-side shall be bonded together by copper wire jumpers, of 8 mm² or larger. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 65/124 Version 2.0 4.12.3 Care shall be taken to assure that ground loops are not created inadvertently. 4.13 COMMUNICATIONS CABLE TRAY SYSTEMS:- 4.13.1 Bond the metallic structures of one cable tray in each tray run following the same path to provide 100 percent electrical continuity throughout this cable tray systems as follows:- 4.13.1.1 Splice plates provided by the cable tray manufacturer can be used for providing a ground bonding connection between cable tray sections when the resistance across a bolted connection is 10 milliohms or less. 4.13.1.2 Install a standard (16 mm²) bonding jumper across each cable tray splice or junction where splice plates cannot be used. 4.13.1.3 When cable tray terminations to cable rack, install standard 16 mm² (bonding jumper between cable tray and cable rank pan. 4.14 Important points regarding Earthing System 4.14.1 Minimum dimensions for earth terminations are as follows:- Component Dia in mm Area mm 2 Copper clad or galvanized steel rods. For Copper clad steel rods, the core should be of low carbon steel of tensile strength700N/mm 2 , (as per Underwriters laboratories UL-467-2007)99.9% electrolytic copper should be molecularly bonded to the steel core and radial width of copper should not be less than 0.25mm. 17.2(with minimum length of 3 meter) 25 32 232 491 804 4.14.2 Earth network/ring: A common earth termination network is recommended for the lightning protective system and all other services. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 66/124 Version 2.0 4.14.3 The resistance to earth should, in this case, be the lowest value required for any of the individual services. In other words, all the earth terminals that of equipment, electrical power, lightning protective system, antenna, etc., are to be connected together to form a common earth network. 4.14.4 One lightning protection system should consist of at least one plate earth terminal and other earth electrodes made by driving copper rods of suitable type into the ground. 4.14.5 No appreciable advantage in resistance reduction is gained by increasing the diameter or surface of the driven electrode. Larger sizes become more difficult to drive and are more expensive in materials. 4.14.6 Where deep driving of earth rods is not possible, a matrix arrangement of rods coupled to one another by conductors can be used. If possible the earth rods must be spaced at a distance at least twice their driven depth. 4.15 Importance of earth ring in reducing potential gradient:- 4.15.1 As the lightning current is discharged through the earth electrode, the surrounding soil is raised for the duration of the discharge to a potential with respect to the body of the earth. The resulting potential gradient is illustrated in Figure 4.6 and it is shown how its voltage gradient can be reduced by adding ring earth electrodes to lower the effective earth resistance. 4.15.2 Such potential difference may be lethal to a person if it exceeds a few thousand volts and to an animal if it exceeds a few hundred volts. 4.15.3 As this potential difference is a function of the product of the lightning current and the resistance of the earth electrode, the importance of keeping the latter as low as possible is evident. For practical purposes, a maximum value of 10Ω is recommended. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 67/124 Version 2.0 4.15.4 The danger to persons within a structure is effectively reduced by the presence of any floor other than that of earth or rock. 4.15.5 To reduce the voltage gradient in case of lightning, a long ground surface near to masts, towers and columns, the earth terminations of each lightning protective system should be interconnected by a ring conductor. 4.15.6 This ring conductor should preferably be buried to a depth of at least 0.5m unless other considerations, such as the need for bonding other objects to it or testing, make it desirable to leave it exposed. 4.15.7 The ring conductor should be connected to the ring conductors of the neighbouring structures. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 68/124 Version 2.0 Figure-4.6 4.16 Anti-corrosive measures (Importance thereof):- Corrosion due to atmospheric, chemical, electrolytic or other causes is likely to impair any part of the lightning protective system; therefore, suitable precautions as mentioned below should be taken to prevent its occurrence:- 4.16.1 Due to the harmful corrosion which is likely to result, coke breeze should not be allowed to come in contact with copper electrodes and salting of the ground in the vicinity of any earth electrode should not be practiced. 4.16.2 In some cases if it is not possible to achieve earth’s resistance less than 1 ohm then all copper to copper joints shall be made by welding or brazing only Bolting of joints shall not be accepted. The minimum distance by which these electrodes should be separated is 3mtrs and maximally it can go up to twice of it i.e. 6mtrs. 4.16.3 Electrolytic corrosion between dissimilar metals: The contacts of dissimilar metals unless the contact surfaces are kept completely dry and protected against the ingress of moisture, are likely to initiate and accelerate corrosion. 4.16.4 The metal of lightning protection system must be compatible to the metals of the structure over which it passes or makes contact with corrosion inhibitors may be used if required. 4.16.5 Aluminium is prone to corrosion when in contact with cement and mortar mixes. 4.16.6 Backfill compound if used for soil treatment shall provide anti corrosion protection to the electrodes. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 69/124 Version 2.0 4.16.7 Fittingsshould be resistant to the corrosive agencies or be otherwise suitably protected. 4.16.8 Joints and bonds may be protected with bitumen or embedded in plastic compound according to the local conditions as shown in figure 4.7 below:- Figure-4.8 ------------------------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 70/124 Version 2.0 Chapter-5 Surge and Transient Protection Systems 5.1 Surge & Transient:- Surge is an overvoltage or overcurrent of a short duration occurring on a power line while transient is an overvoltage or overcurrent pulse occurring on a power, signal, control or data line. The term “surge” is used to describe a transient overvoltage on a power line that has duration of a few microseconds. A transient overvoltage can exceed the insulation rating of electrical equipment causing degradation of insulation and immediate damage to the equipment. Relatively low-amplitude transient overvoltages applied repetitively on the equipment will reduce its mean time before failure. The result will be that equipment will have to be repaired more often, increasing operating costs. 5.2 Why Surge Protection is needed:- 5.2.1Power surges can cause failure, permanent degradation, or temporary malfunction of electronic devices and systems. The development of an effective Surge Protection Device (SPD) is of paramount importance to manufacturers and users of industrial electronic equipment. 5.2.2Almost all manufacturers of industrial-type SPDs use metal–oxide varistors (MOVs) in their design. MOVs are composed of a thin disk wafer of material (metal– oxide) that has a known voltage breakdown characteristic. At low voltages, the MOV conducts very little current (microamperes). As the voltage approaches breakdown, the MOV then begins to conduct current. At voltages slightly above the break down, large currents flow, effectively clamping the output voltage. This clamping feature allows the higher voltage levels to be shunted to ground, preventing overvoltages on equipment. 5.2.3 Figure 5.1 and 5.2below show the voltage waveform before and after an ideal Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 71/124 Version 2.0 SPD:- Figure 5.1 Voltagewaveform before SPD. Figure 5.2 Voltage waveform after an ideal SPD 5.2.4 Causes of Power Line Surges:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 72/124 Version 2.0 The sporadic damped phenomena that occur in electrical systems are generally described as transients and surges or in other words Power surges and transient overvoltages are due to the sudden change in the electrical conditions of a circuit and the release of large amounts of energy stored in the inductance and capacitance elements of the system. Sources of power surges can be external or internal to the facility. 5.2.4.1External sources of transient overvoltages can be the following:- Lightning. Switching (on/off) of capacitor banks, for power coefficient Correction. Power-line disconnection and reconnection. Transformer switching on/off. Electrostatic discharges. Power utility load switching. Poor quality of power transmission and distribution grids. 5.2.4.2 Internal surges are caused by the operation of the following devices:- circuit breakers or fuses; electric motors, i.e., elevators; air conditioners; VSDs generators. 5.3 It is very important to note that the IS 3043 has specifically recommended the use of surge protection systems to protect the sensitive equipment’s against over voltages induced by lightning and switching surges. 5.4 Transient over voltages are generated due to:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 73/124 Version 2.0 a) Whenever a lightning strikes directly / in the near vicinity; b) As a consequence of different faults in the power system; and c) Switching on and off of different loads etc. d) Hence, it is very important to protect the sensitive electrical and electronic equipment’s against these transient voltage surges. 5.5 The transient voltage surges are broadly classified into two types :- Lightning Surges ( Handled by Class B or Type I SPDs); and Switching surges ( Handled by Class C or Type II SPDs) 5.5.1 The lightning surges bring very high amount of destructive energy into the system and hence, are potentially very dangerous. The Class B SPDs are designed to handle the lightning current surges. 5.5.2 The switching surges are relatively frequent than the lightning surges. Although they bring in relatively less energy into the system, however, they still are strong enough to damage the sensitive electronics. The switching surges are handled by the Class C SPDs. 5.5.3 Latest IEEE Guidelines express that lightning activity at a place can induce surges due to Galvanic Coupling for about 1.7 km radius from the point of impact. Hence, it is important to note, both the lightning and the switching surges can come from outside of our power system and hence these surges need to be isolated at the mains input point itself so it is important to put appropriate surge protection devices to all the cables i.e. Power, Data, Remote Control, RF Cables or any other devices which is likely to carry surge and which enters into a equipment room where sensitive CNS/ATM systems are installed. 5.6 Methodology for surge protection:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 74/124 Version 2.0 Surge mitigation technique suggests use of surge suppression devices for power and data lines. The sole function of a good quality surge suppressor is to protect sensitive electronic equipment from transient over voltages. It must limit transient over voltages to a value that do not surpass the AC sine wave peaks by more than 30%. 5.6.1 A surge protector (or surge suppressor) is an appliance designed to protect electrical devices from voltage spikes. A surge protector attempts to limit the voltage supplied to an electric device by either blocking or shorting to ground any unwanted voltages above a safe threshold. 5.6.2 The terms surge protection device (SPD), or the obsolescent term transient voltage surge suppressor (TVSS), are used to describe electrical devices typically installed in power distribution panels, process control systems, communications systems, and other heavy-duty industrial systems, for the purpose of protecting against electrical surges and spikes, including those caused by lightning. 5.7 Main performance parameters of a surge protector are as follows:- 5.7.1 Clamping voltage also known as the let-through voltage. This specifies what spike voltage will cause the protective components inside a surge protector to divert unwanted energy from the protected line. A lower clamping voltage indicates better protection, but can sometimes result in a shorter life expectancy for the overall protective system. 5.7.2 Joules rating: This number defines how much energy the surge protector can theoretically absorb in a single event, without failure. Counter-intuitively, a lower number may indicate longer life expectancy if the device can divert more energy elsewhere and thus will need to absorb less energy. In other words, a protective device offering a lower clamping voltage while diverting the same surge current will cause more of the surge energy to be dissipated elsewhere in the system. Better protectors Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 75/124 Version 2.0 exceed peak ratings of 1000 Joules and 40, 000 Amperes. It is often claimed that a lower Joule rating is undersized protection, since the total energy in harmful spikes can be significantly larger than this. However, if properly installed, for every joule absorbed by a protector, another 4 to 30 joules may be dissipated harmlessly into ground. A MOVbased protector (described below in Para 4.8.1) with a higher let-through voltage can receive a higher joule rating, even though it lets more surge energy through to the device to be protected. 5.7.3 Response time: Surge protectors do not operate instantaneously; a slight delay exists. The longer the response time, the longer the connected equipment will be exposed to the surge. However, surges usually take around a few microseconds to reach their peak voltage, and a surge protector with a nanosecond response time would kick in fast enough to suppress the most damaging portion of the spike. All MOVs have response times measured in nanoseconds, while test waveforms usually used to design and calibrate surge protectors are all based on modelled waveforms of surges measured in microseconds. As a result, MOV-based protectors have no trouble producing impressive response-time specifications. Slower-responding technologies (notably, GDTs) may have difficulty protecting against fast spikes. 5.7.4 Transient surges: These are characterised by different waveforms. The most frequently referenced IEEE waveform used to simulate lightning induced transient activity is the combination wave. This wave is characterised by short duration, high frequency 8/20 µs current and 1.2/50 µs voltage waveform. 5.8 Types of surge protectors:- Systems used to reduce or limit high voltage surges can include one or more of the following types of electronic components. Some surge suppression systems use multiple technologies, since each method has its strong and weak points. Some of these operate primarily by diverting unwanted surge energy away from the protected load, through a protective component connected in a parallel (or shunted) topology. Some others block Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 76/124 Version 2.0 unwanted energy by using a protective component connected in series with the power fed to the protected load, and additionally may shunt the unwanted energy like the earlier systems. 5.8.1 Metal oxide Varistors (MOV) : A metal oxide varistors consists of a bulk semiconductor material (typically sintered granular zinc oxide) that can conduct large currents (effectively short-circuits) when presented with a voltage above its rated voltage. MOVs typically limit voltages to about 3 to 4 times the normal circuit voltage by diverting surge current elsewhere than the protected load. 5.8.1.1 MOVs may be connected in parallel to increase current capability and life expectancy; provided they are matched sets (unmatched MOVs have a tolerance of approximately ±20% on voltage ratings, which is not sufficient). 5.8.1.2 MOVs have finite life expectancy and "degrade" when exposed to a few large transients, or multiple smaller transients. As a MOV degrades, its triggering voltage falls lower and lower. If the MOV is being used to protect a low-power signal line, the ultimate failure mode typically is a partial or complete short circuit of the line, terminating normal circuit operation. 5.8.1.3 If used in a power filtering application, eventually the MOV behaves as a part-time effective short circuit on an AC (or DC) power line, which will cause it to heat up, starting a process called thermal runaway. 5.8.1.4 As the MOV heats up, it may degrade further, causing a catastrophic failure that can result in a small explosion or fire, if the line current is not otherwise limited. 5.8.1.5 When used in power applications, MOVs usually are thermal fused or otherwise protected to avoid persistent short circuits and other fire hazards. In a typical power strip, the visible circuit breaker may be distinct from the internal thermal fuse, which is not normally visible to the end user. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 77/124 Version 2.0 5.8.1.6 If a surge current is so excessively large as to exceed the MOV parameters and blow the thermal fuse, then a light found on some protectors would indicate unacceptable failure. 5.8.1.7 Even adequately-sized MOV protectors will eventually degrade beyond acceptable limits, with or without a failure light indication. 5.8.1.8 Therefore, all MOV-based protectors intended for long-term use should have an indicator that the protective components have failed, and this indication must be checked on a regular basis to insure that protection is still functioning. 5.8.1.9 Because of their good price/performance ratio, MOVs are the most common protector component in low-cost basic AC power protectors. 5.8.2 Transient voltage suppression (TVS) diode: ATVS diode is a type of Zener diode, also called an avalanche diode or silicon avalanche diode (SAD), which can limit voltage spikes. 5.8.2.1 These components provide the fastest limiting action of protective components (theoretically in picoseconds), but have a relatively low energy absorbing capability. 5.8.2.2 Voltages can be clamped to less than twice the normal operation voltage. 5.8.2.3 If current impulses remain within the device ratings, life expectancy is exceptionally long. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 78/124 Version 2.0 5.8.2.4 If component ratings are exceeded, the diode may fail as a permanent short circuit; in such cases, protection may remain but normal circuit operation is terminated in the case of low-power signal lines. 5.8.2.5 Due to their relatively-limited current capacity, TVS diodes are often restricted to circuits with smaller current spikes. 5.8.2.6 TVS diodes are also used where spikes occur significantly more often than once a year, since this component will not degrade when used within its ratings. 5.8.2.7 A unique type of TVS diode (trade names Transzorb or Transil) contains reversed paired series avalanche diodes for bi-polar operation. 5.8.2.8 TVS diodes are often used in high-speed but low power circuits, such as in data communications. These devices can be paired in series with another diode to provide low capacitance as required in communication circuits. 5.8.3 Thyristor Surge Protection device (TSPD), a specialized solid-state electronic device used in crowbar circuits to protect against overvoltage conditions. 5.8.3.1 These Thyristor-family devices can be viewed as having characteristics much like a spark gap or a GDT, but can operate much faster. 5.8.3.2 They are related to TVS diodes, but can "break over" to a low clamping voltage analogous to an ionized and conducting spark gap. After triggering, the low clamping voltage allows large current surges to flow while limiting heat dissipation in the device. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 79/124 Version 2.0 5.8.4 Gas Discharge Tube (GDT): A gas discharge tube (GDT) is a sealed glassenclosed device containing a special gas mixture trapped between two electrodes, which conduct electric current after becoming ionized by a high voltage spike. 5.8.4.1 GDTs can conduct more current for their size than other components. 5.8.4.2 Like MOVs, GDTs have a finite life expectancy, and can handle a few very large transients or a greater number of smaller transients. 5.8.4.3 The typical failure mode occurs when the triggering voltage rises so high that the device becomes ineffective, although lightning surges can occasionally cause a dead short. 5.8.4.4 GDTs take a relatively long time to trigger, permitting a higher voltage spike to pass through before the GDT conducts significant current. It is not uncommon for a GDT to let through pulses of 500 V or more in duration of100 ns. 5.8.4.5 In some cases, additional protective components are necessary to prevent damage to a protected load, caused by high-speed let-through voltage which occurs before the GDT begins to operate. 5.8.4.6 GDTs create an effective short circuit when triggered, so that if any electrical energy (spike, signal, or power) is present, the GDT will short this. 5.8.4.7 Once triggered, a GDT will continue conducting (called follow-on current), until all electric current sufficiently diminishes, and the gas discharge quenches. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 80/124 Version 2.0 5.8.4.8 Unlike other shunt protector devices, a GDT once triggered will continue to conduct at a voltage less than the high voltage that initially ionized the gas; this behaviour is called negative resistance. 5.8.4.9 Additional auxiliary circuitry may be needed in DC (and some AC) applications to suppress follow-on current, to prevent it from destroying the GDT after the initiating spike has dissipated. 5.8.4.10 Some GDTs are designed to deliberately short out to a grounded terminal when overheated, thereby triggering an external fuse or circuit breaker. 5.8.4.11 Many GDTs are light-sensitive, in that exposure to light lowers their triggering voltage. Therefore, GDTs should be shielded from light exposure, or opaque versions that are insensitive to light should be used. 5.8.4.12 Due to their exceptionally low capacitance, GDTs are commonly used on high frequency lines, such as those used in telecommunications equipment. 5.8.4.13 Because of their high current handling capability, GDTs can also be used to protect power lines, but the follow-on current problem must be controlled. 5.8.5 Selenium Voltage Suppressor: An "overvoltage clamping" bulk semiconductor similar to a MOV, though it does not clamp as well. 5.8.5.1 It usually has a longer life than a MOV. It is used mostly in high-energy DC circuits, like the exciter field of an alternator. 5.8.5.2 It can dissipate power continuously, and it retains its clamping characteristics throughout the surge event, if properly sized. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 81/124 Version 2.0 5.8.6 Carbon Block Spark Gap Overvoltage Suppressor: A spark gap is one of the oldest protective electrical technologies still found in telephone circuits, having been developed in the nineteenth century. In this type of suppressor, a carbon rod electrode is held with an insulator at a specific distance from a second electrode. The gap dimension determines the voltage at which a spark will jump between the two parts and short to ground. The typical spacing for telephone applications is 0.076 mm (0.003"). 5.8.6.1 Carbon block suppressors are similar to gas arrestors (GDTs) but with the two electrodes exposed to the air, their behaviour is affected by the surrounding atmosphere, especially the humidity. 5.8.6.2 Since their operation produces an open spark, these devices should never be installed where an explosive atmosphere may develop. 5.8.7 Quarter-wave coaxial surge arrestor :Used in RF signal transmission paths, this technology features a tuned quarter-wavelength short-circuit stub that allows it to pass a bandwidth of frequencies, but presents a short to any other signals, especially down towards DC. The pass bands can be narrowband (about ±5% to ±10% bandwidth) or wideband (above ±25% to ±50% bandwidth). Quarter-wave coax surge arrestors have coaxial terminals, compatible with common coax cable connectors (especially N or 7- 16 types).They provide the most rugged available protection for RF signals above 400 MHz; at these frequencies they can perform much better than the gas discharge cells typically used in the universal / broad band coax surge arrestors. Quarter-wave arrestors are useful for telecommunications applications, such as Wi-Fi at 2.4 or 5 GHz but less useful for TV/CATV frequencies. Since a quarter-wave arrestor shorts out the line for low frequencies, it is not compatible with systems which send DC power for a LNB up the coaxial downlink. A typical Quarter-wave coaxial surge arrestor is shown in figure 5.3 below:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 82/124 Version 2.0 Figure- 5.3 5.8.8 Series Mode (SM) Surge Suppressors: These devices are not rated in Joules because they operate differently from the earlier suppressors, and they do not depend on materials that inherently wear out during repeated surges. 5.8.8.1 SM suppressors are primarily used to control transient voltage spikes on electrical power feeds to protected devices. 5.8.8.2 They are essentially heavy-duty low-pass filters connected so that they allow 50/60 Hz line voltages through the load, while blocking and diverting higher frequencies. 5.8.8.3 This type of suppressor differs from others by using banks of inductors, capacitors and resistors that shunt voltage spikes to the neutral wire, whereas other designs shunt to the ground wire. Where ground is bonded to neutral at the electrical service entrance, the resulting surge ultimately flows into ground at that connection, but by first dumping into neutral, nearby ground contamination is avoided. 5.8.8.4 Since the inductor in series with the circuit path slows the current spike, the peak surge energy is spread out in the time domain and harmlessly diverted into the capacitor bank. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 83/124 Version 2.0 5.8.8.5 Experimental results show that most surge energies occur at under 100 Joules, so exceeding the SM design parameters is unlikely, but it provides no contingency should rare events induce energies that exceed it. 5.8.8.6 SM suppressors do present a theoretical fire risk, should the absorbed energy exceed design limits of the dielectric material of the components. 5.8.8.7 In practice, surge energy is also limited via arc-over to ground during lightning strikes, leaving a surge remnant that often does not exceed a theoretical maximum (such as 6000 V at 3000 A with a modelled shape of 8 x 20 µs waveform specified by IEEE/ANSI C62.41). 5.8.8.8 SM suppression focuses its protective philosophy on a power supply input, but offers nothing to protect against surges appearing between the input of an SM device and data lines, such as antenna, telephone or LAN connections, or multiple such devices cascaded and linked to the primary devices. 5.8.8.9 In this design philosophy, such events are already protected against the SM device before the power supply. 5.8.8.10 SM low-pass filters are generally not suitable for data communications circuits, because they would also block high-speed data signals from getting through. 5.8.8.11 In comparison to devices relying on components that operate only briefly and do not normally conduct electricity (such as MOVs or GDTs), SM devices tend to be bulkier and heavier than those simpler spike shunting components. 5.8.8.12 The initial costs of SM filters are higher, but a long service life can be expected if they are used properly. In-field installation costs can be higher, since SM Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 84/124 Version 2.0 devices are installed in series with the power feed, requiring the feed to be cut and reconnected. 5.9 Important points regarding installation of Surge Protection at mains input level and at power distribution boxes:- 5.9.1 A comprehensive surge protection system comprising of an INTEGRATED CLASS B +CLASS C TYPE SURGE PROTECTION SYSTEM is ideally suited for installation at the mains input and substation switch boards. 5.9.2 The SPD used shall comply with the performance requirements of the IEC 61643 or equivalent. 5.9.3 The Main Surge Protection System is to be installed in the mains input panel on the LT side. An indicative system is shown in Figure -5.4 below:- Figure- 5.4 5.9.4 The system shall offer comprehensive protection against all types of transient Over Voltages and shall use high capacity MOVs only. It shall be of combined class B+C type. i.e. it shall be capable of handling Lightning as well as Switching Surges. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 85/124 Version 2.0 5.9.5 Class B surge protection device (N-G) may consist of encapsulated air gap device (GDT) and may be used as galvanic separation between N-PE conductors with following characteristics:- i) Protection mode : N-PE ii) Single pole surge protection device iii) Impulse current capacity : 100 kA iv) Max current 160 kA v) Status indicator available 5.9.6 The surge protection system shall be configured such that the system offers all mode (Differential) protection. The protection shall be between each phase to neutral, each phase to earth and between neutral to earth. A typical system is indicated below:- Figure-5.5 5.9.7 The surge protection system shall comprise of multiple MOV based surge arrestors housed in an IP 65 enclosure. 5.9.8 Each Surge arrestor shall consist of at least three elements for backup protection. Each element of the surge arrestors shall comply with the performance requirements of the IEC 61643 or equivalent. 5.9.9 The Surge protection system design shall be modular in nature so that the Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 86/124 Version 2.0 individual surge arrestors can be replaced after its elements have reached the end of their life. 5.9.10 The surge arrestors shall be mounted on a DIN RAIL and housed in an IP 65 or equivalent grade enclosure for reliability and ease of replacement / maintenance. 5.9.11 The design shall be such that when a given element fuses, the balance elements in the surge arrestor continue to offer protection to the installation till it is replaced with a new one in a short period of time. 5.9.12 When any element fuses, the respective status indicator flag shall turn red indicating that the element is out of service. 5.9.13 Each individual element in the surge arrestor shall be rated as follows : - Max. Continuous operating voltage (Uc) 440 V Min. Lightning impulse current (Iimp) 15 KA ( 10/350 µs) per phase Nominal discharge current 80 KA(8/20 µs) Maximum discharge current 150 KA(8/20 µs) Peak value current 40 KA(10/350 µs) Specific energy 400 KJ/Ω Charge 20 As Protection level 1.9 KV(8/20µs);1.7 KV(10/350µs) Response time < 25 ns Residual current < 2.5 mA Follow current 0 Thermo coupler Present Fuse Present Short circuit withstand 25 KA for 50 Hz supply Switching surge current (Imax) 100 KA (8/20 µs) per phase Switching surge current (Inom) 30 KA (8/20 µs) per phase Clamping voltage 1800 V between L-E, L-N, N-E Minimum Inom exposures before fusing 20 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 87/124 Version 2.0 5.9.14 The surge arrestor elements shall be designed to withstand the specified Switching Surge Current (Inom) current for a minimum of 20 times without fusing. 5.9.15 The surge protection system shall be connected in parallel with the circuit and shall not draw the line current. The system shall be connected to the circuit with 10 / 16 Sq mm single core PVC insulated flexible copper conductor cables. The terminal connectors of the system shall be so designed to avoid any loose connections. 5.9.16 In addition to the Main surge protection Device, which provides combined Class B & C protection at the main incoming, a series surge filter may be considered to be installed at all the UPS incoming and outgoing supply which will have the following features:- I) It shall offer All Mode Protection; II) It shall offer redundant protection and staged ; III) LED status indication; and IV) Option for remote monitoring may be considered. 5.9.17 The surge filter shall filter the surges and transients occurring up to the branch panels. It shall offer all mode protection for (L-N, L-E and N-E). 5.9.18 It shall conform to ULI 1449 Edition 2 or equivalent for the metallic enclosure. 5.9.19 The MCB shall be included to ensure safety isolation under power frequency overload condition. 5.9.20 It shall be suitable for a line current of 32A or 63A, 3 phase and up to 320 V 50 Hz power supply. 5.9.21 It shall be connected in series. The surge rating shall be 40 kA, 8/20µs. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 88/124 Version 2.0 5.9.22 Each phase surge arrestor employed shall have two redundant and independent fused and thermal over load protection elements to provide back-up protection for continued equipment survival. 5.9.23 The technical features shall be as described below: Normal Voltage 320Vrms(1p), 380V(3p) Operating Voltage 180-280Vrms(1 ph); 300-480Vrms (3 ph) Operating Frequency 50 Hz Connection type Series Max. surge rating per line 50 kA to 140kA (8/20µs) Let through voltage <380V for 3 KA Cat B Protection mode L-N, L-E, N-E Earth leakage current < 1 µA Efficiency 99% Frequency response 3 dB (at 800 Hz) Response time < 5 ns Standards compliance BS6651-1999 cat.A.B.C AS1768-2003 cat.A.B.C IEEE C62.41 cat.A.B.C CP33-1999 cat.A.B.C IEC 1000-4 5 1995 UL 1449 second edition EMC Compliance BS EN 60950 : 1992; BS EN 61000 : 1999 Alarm isolation 4 Kv Status indicator LED Optional remote alarms Siren sound OK and FAIL LED Alarm(volt free contact) N/O, N/C(2A@250Vac) Alarm conductor size 2.5mm² Conductor size 35 mm² Mounting Back panel screw mount Enclosure material Galvanized steel alloy Enclosure IP rating IP 55 Operating temperature - 40 -85ºc Humidity 0-95% (R.H) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 89/124 Version 2.0 5.10 COMPUTER NETWORK PROTECTOR: - The Cat5, Cat 5e, Cat 6 and POE (Power over Ethernet) cables shall be provided with a suitable surge protector. It shall be suitable for RJ 45 connectors 5.10.1 It shall be designed to protect all widely used computer network system using Ethernet twisted pairs technology like 10/100/1000 BaseT, CDDI, ATM155 and also the Power-over-Ethernet. 5.10.2 It shall offer protection against transient over voltages due to lightning induced surges, AC power interference and ground loop energies appearing between any signal pair and / or its ground which can damage the sensitive network equipment. 5.10.3 The series protector shall be designed to protect both common and differential mode in all the 8 pins of the RJ 45 port and its ground lead. 5.10.4 It shall have the latest circuitry using Silicon Avalanche diode to ensure very fast response time and exceptional low let-through voltage which results in maximum system reliability and up-time. 5.10.5 The shunt capacitance shall be 5pf and negligible in-line resistance so that even the most demanding high speed gigabit multimedia signal can be passed without much signal degradation. 5.10.6 It shall be compact, in-line and simple plug-in design to enable it to be easily located near the protected equipment. 5.10.7 The technical features shall be as described below:- Max. working Voltage 5V Max. operating current 300mA Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 90/124 Version 2.0 Protection modes Common and transverse Lines protected All pairs Response time < 5 ns Max. surge rating 100A (8/20µs) Max. Data rate 100Mb/s (C5, PoE models), 1000Mb/s(C6 models) Let through voltage 23V (A1 5 KV 10/700µs) Shunt capacitance 5pF (single port models), 25pF(rack-mount models) In line resistance -0 Ω Standards compliance 100 Base T, 1000Base T, CAT5, CAT5e, CAT6 Connector type RJ 45 Earth connection Flying lead(single port models) Earth stud(rack-mount models) Enclosure material Anodized aluminum (single port) Galvanized steel alloy(multi-port) Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.11 Telecom line protector: All the telecommunication lines shall be protected with a suitable Surge Protector to protect the modems and other sensitive equipment’s. It shall be designed to protect all widely used telecommunication lines like PSTN, ISDN, DDN and DSL using twisted pairs. Different connectors like RJ45, RJ11 and plug/socket models shall be used to obtain optimum protection. Following are the main characteristics of Telecom line protector:- 5.11.1 The hazard of lightning induction in telephone lines can be managed by using transient protection units in parallel with each line. These multi line protection can have multi stage protection i.e. Hybrid GDT for over voltage protection and PTC for over current protection. 5.11.2 It shall offer Protection against Transient over voltages due to lightning induced surges, AC power interference and ground loop energies appearing between Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 91/124 Version 2.0 any signal pair and/or its ground that can damage the sensitive telecommunication equipment. 5.11.3 The protector shall be designed to protect both common and differential mode in all the connected pins of the RJ 45 or RJ 11 port and its ground lead. 5.11.4 They shall be multi-stage design which employ a combination of high energy gas discharge tube, ultra fast diodes and SAD which results in maximum system reliability and up-time. 5.11.5 It shall have 20KA surge handling capability and 20MHz high bandwidth, so that it can provide the safest protection in lightning intense environment to ensures a smooth data traffic. 5.11.6 It shall be compact, in-line and simple plug-in design enabling it to be easily located near to the protected equipment. 5.11.7 The important technical features of Telecom Line Protector are described as below:- Max. working Voltage (Line to line) 190v (PSTN) , 60 V (ISDN) , 68 V (DDN) 50 V (XDSL) Max. operating current 150mA Protection modes Common and transverse Lines protected 2 wires (RJ11-pin3& 4, RJ45-pin4& 5) 4 wires(RJ11-pin 3& 4, 2& 5, RJ 45-pin 4& 5, 3& 6) Response time < 5 ns Max. surge rating 20A (8/20µs) Max. Data rate 20Mb/s Let through voltage (at 5KV 10/700µs) 220V (PSTN) , 80 V (ISDN) 78V (DDN) , 60V (xDSL) Shunt capacitance < 150pF Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 92/124 Version 2.0 In line resistance 3.9 Ω Standards compliance BS6651-1999, AS1768-2003 IEC61643-21 , ITU(CCITT)1X K17 Connector type RJ 45 or RJ 11 Earth connection Flying lead (single port models) Earth stud (rack-mount models) Enclosure material Anodized aluminum(single port) Galvanized steel alloy (multi-port) Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.12 DATA PORT PROTECTOR:- The SPD for Data Line shall be based on transistor and diode circuitry which ensures a lower let through voltage to protect from the surge and transient overvoltage. Following are the main characteristics of Data Port Protector:- 5.12.1 In case of the Surge current above the Rated capacity it shall fuse and isolate the sensitive equipment. 5.12.2 It shall offer common mode & Transverse mode protection against the Transients appearing between any signal pairs. 5.12.3 The DPP RS232 port protectors shall be compact and in-line design which can be easily connected to the data of the equipments. 5.12.4 The V.35 and the RJ21X data port protectors shall be easily secured onto a standard 35mm Top Hat DIN rail. 5.12.5 It shall have fast response circuit not only to protect the equipments from repeated surges but also to allow the DPP protectors to transparently transmit the data at a speed of up to 20 Mbps. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 93/124 Version 2.0 5.12.6 DPP protector shall offer nearly zero in line resistance and a 40pF capacitance which allows the data to transmit smoothly on the lines. 5.12.7 The important technical features of Data Port Protector are described as below:- Max. operating current 300mA Protection modes Common and transverse Response time 1 ns Max. surge rating 200A (8/20µs) Max. Data rate 20Mb/s Insertion loss <1dB at 20 MHz Capacitance 40pf Standards compliance BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C IEC61643-21, ITU(CCITT)1X K17 CP33-1996 Cat A.B.C, UL497B Connector type DB9 female to male (DPP9) DB25 female to male(DPP25) M/34 female to male(DPP35) RJ21X female to male (DPP50) Earth connection DIN clip (DPP35, DPP50) Flying lead(DPP9), shell(DPP25) Enclosure material Anodized aluminum (DPP35, DPP50) Plastic (DPP9, DPP25) Operating temperature - 40 ºc to 85 ºc Humidity 0 to 95% (R.H) Altitude 0-3650m 5.13 RF COAXIAL PROTECTOR:- RF Coaxial protectors are intended to pass through a desired RF signal with minimum loss or disturbance. To minimize the impact of inserting lightning protectors within the RF circuit, seek out products with the lowest Insertion Loss and lowest VSWR at the frequencies that is intended to operate. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 94/124 Version 2.0 5.13.1Other important main characteristics of RF Coaxial Protector (Fig 5.6) are:- i) Reliable RF performance capability from DC – 3GHz ii) Multi – strike capability iii) Easily replaceable gas discharge tube iv) Bi-directional protection v) AC/DC pass vi) High quality construction vii) Full range of connector type Figure-5.6 5.13.2The coaxial RF protectors shall be a high performance gas discharge tube suppressor capable of wide-band operation from DC up to 3 GHz (N, SMA and D type connector). 5.13.3 The let-through voltage shall be as low as possible and it is capable of handling multi-strike in any lightning intensive environment. 5.13.4 CGR protectors feature easily replaceable gas tube arrester elements, which makes it simple, fast and cost effective in case replacement of the gas tube is required. 5.13.5 Both connector ports of this protector shall be equally protected. This provides protection no matter which way it is installed. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 95/124 Version 2.0 5.13.6 The important technical features of RF Coaxial Protector are described as below:- Frequency range 0-3GHz VSWR < 1.1:1 Return loss > 26dB Insertion loss < 0.2dB Impedance 50 Ω for all models Response time <5ns Peak surge rating 20 kA (8/20µs) DC sparkover voltage 90V+/- 20% (230, 350, 600, 1000V) Max. power 0 – 2000 W Standards compliance ITU(CCITT)1x K17 BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C CP33-1996 Cat A.B.C IEC61643-21/UL497B Body material Brass(Nickel plated) Contact pin Brass(silver/gold plated) Contact socket Beryllium or tin brass(silver/gold plated) Elastic contact Beryllium or tin brass(silver/gold plated) Insulator PTFE O-ring material Silastic Earth connection Via suitable screw ground lug Mounting L shape bracket Operating temperature -4-85ºc Humidity 0-95% (R.H) Altitude 0-3650m IP rating IP 65 Moisture resistance MIL-STD-202 Method 106D Salt fog MIL-STD-202 101D/B Temperature shock MIL-STD-202 107D/A-1 Vibration MIL-STD-202 Method204D/B Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 96/124 Version 2.0 5.14 Telephone Line Protector (Krone Type) The main characteristics of Telephone Line Protector which provides surge protection for telecom and other signalling equipment’s terminated on KRONE connectors are:- 5.14.1 The protector shall be available in various assorted configuration like 1 pair, 10 pair, 50 pair etc in a compact module having multi stage protection. 5.14.2 Full range of voltage to suit any particular applications and the let-through voltage shall be as low as possible. 5.14.3 The series protectors shall be easily pluggable type into the KRONE LSAPLUS disconnection blocks and shall be earthed suitably. 5.14.4 It shall offer both line to line (transverse mode) and line to earth (common mode) protection. 5.14.5 It shall have 20 KA high surge rating and 20 MHz wide bandwidth to provide the best protection and to ensure a smooth data flow in high speed data and signal lines. 5.14.6 It shall be designed in such a way that the surge exceeding the capacity of the primary gas arrester, service should be interrupted by blowing the track fuse and thereby giving a fault condition. 5.14.7 The important technical features of Telephone Line Protector are described as below:- Max. working voltage 7-280V Max. operating current 250Ma Protection modes Common and transverse Protection stages 3 stages Earth leakage current < 5 µA Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 97/124 Version 2.0 Response time <5ns Max. surge rating 20 kA (8/20µs)- KDP 10 5 KA (8/20µs) – KDP 1 Max. data rate 20 Mb/s Insertion loss < 1dB at 20 MHz Let through voltage: (At 5KV 10/700 µs) 10-320 V Capacitance 50 pf In line resistance 3.9Ω Standards compliance ITU(CCITT)1x K17 BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C CP33-1996 Cat A.B.C IEC61643-21 UL497B Earth connection Via earth clips on two ends – KDP 10 Via earth bar – KDP 1 Enclosure material ABS plastic Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.15 Installation notes and Important points in context of installation of Lightning, Surge Protection and Earthing Systems:- 5.15.1 A Connection made up by materials which do not comply with the chemical chain of materials choice like Copper and steel irrespective of their grade is not allowed to be connected with unless separated by appropriate means as stipulated within IEC62305-3. 5.15.2 IEC stipulates that the spark gaps used for single or multiple load be 100 kA at 8/20 µs single rated. Anything above 60 V is deadly for human life. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 98/124 Version 2.0 5.15.3 IEC 62305 regulatory norm permits only one common grounding network. This common grounding network must interconnect or cross mesh all the sub components of the LLZ system like its building, LLZ antenna array, and NF Monitor. Even the grounds of lightning protection system needs to be connected to the common grounding network. All external metal structures must be connected to the ground network. If there is any other equipment installed at the LLZ site, the same must necessarily be given relevant lightning protection not only for the sake of the equipment itself but for the sake of the whole LLZ installation. As an example wiring diagram of a standard electrical shelter installation (typical) of THALES ILS LLZ is shown below: Fig. Wiring Diagram of Electrical Installation (Typical) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 99/124 Version 2.0 5.15.4 Implement lightning protection system compliant to IEC 62305 of Cat I. This does not permit the use of such ionizing devices like the prevectron which promise prevention of lightning and wider coverage. 5.15.5 Lightning protection by systems like “Early Streamer emission”, “Dissipation Array Systems” or “Charge Transfer Systems” are not allowed under standards of US National Fire Protection Association (NFPA), IEC, IEEE, Underwriters Laboratories (UL), US Military etc. 5.15.6 The power cable shielding must be connected to a common ground point. 5.15.7 The mains in-leading and out-leading armoured power cable must have its shield grounded with its PEN conductor to one common ground bus bar. The grounding must be done within 20 cm of the cable entry/exit point to/from the building. 5.15.8 The mechanical shield of each RF cable entering or leaving the building must be bonded to the ground at the point where it enters/leaves the building, but not more than 20 cm inside the building. Preferably it should be done outside the building. 5.15.9 The COM cable used for data communication should have its mechanical armouring and inner static shield connected to ground only at one end, say the TWR side and not at both ends. Connecting to ground at both ends is likely to induce strong equalizing ground current between different potentials of such far away buildings, which may reach values above 100 A under worst condition. The other end, both the armour as well as the shield should be grounded through a spark gap to the nearest common ground. The spark gap should be IEC 62305 compliant with low spark over voltage level (< 70 V AC) and high current rating values of 75 kA at 8/320 µs or more. 5.15.10 The IEC 62305 stipulates that there is only one common ground connecting all potentials to one, as well as the PEN, the power cable shield, the COM cable shield, any internal PE and grounds of SPDs, any RF cable shields and others like external Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 100/124 Version 2.0 groundings and lightning protection inclusive of the subsystems e.g. LLZ antenna, NFM etc. 5.15.11 RF cables entering the shelter must have in line surge arrestors. 5.15.12 The PE wire/conductor of a power cable is not a ground connection. The ground connection for static issues must use a connecting wire of cross sectional area 16 mm2 or more and use the shortest path to the near most ground. 5.15.13 All multi strand wire must use cable end sleeves and cable end lugs to enable proper installation and also to reduce chemical chain involved in corrosion. Any flat tape or round wire / cable connections must utilise termination clamps or brackets. 5.15.14 The cable routing of various voltage circuit must be separated, for e.g. the RF, the AC, the DC and the GND and static shields of all the cables must be grounded at point of entry into the building. 5.15.15 All shielded cable like RF, COM, armoured PWR line etc. should be connected to common potential ground at every 20 m along its external path. Same is to be done at every 2.5 m when internally laid. 5.15.16 Common ground network for a DVOR must be connected, DVOR building, Counterpoise steel structure, Counterpoise mesh, power cable shielding, power cable PEN wire, COM cable shield via spark gap, ground connection to SPD related to PWR, COM or RF cabling, Lightning protector rods, DVOR monitor mast/antenna, and other metallic objects of the system. 5.15.17 Copper can be bonded to galvanized steel via special bimetal media or stainless steel media of V4A grade. 5.15.18 PE: Protective earth; PEN: Combined protective earth and neutral; N: Neutral must all be connected to a common bus bar. Electrical conductors entering a Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 101/124 Version 2.0 structure should be metal cased. This metal casing should be electrically continuous within the structure; it should be earthed at the point of entry inside the structure on the user’s side of the service and bonded directly to the lightning protective system. 5.15.19 Where the electrical conductors are connected to an overhead electricity supply line, a 15m length of buried armoured cable should be inserted between the overhead line and the point of entry to the structure. 5.15.20 The overhead supply lines are liable to have large surges induced in them from lightning discharges. Hence is, therefore, needed where they join the buried cable. This will allow a large part of the lightning current to be discharged to earth at a safe distance, which is determined by the rolling sphere’s radius, from the structure. 5.15.21 Surge suppressors should be installed with minimum lead lengths to their respective panels. Under fast rise time conditions, cable inductance becomes important and high transient voltages can be developed across long leads. 5.15.22 In all instances, use high quality, high speed self diagnosing protective components. 5.15.23 Proper ground must be ensured. Earth resistance to be strived to achieved to be as low as possible preferably less than 5 Ω. 5.15.24 Do not install suppressor, if neutral to ground bond is not present. 5.15.25 If neutral to ground voltage is greater than 2 V AC, the electrical system is faulty and needs to be rectified. 5.16 Surge protection for typical DSCN System 5.16.1 A surge protector (or surge suppressor) device is used to protect linkway modem and RF components of DSCN system from lightning spikes and surges. A surge protector removes the lightning spikes induced in the RF cable through earth conduction. Moreover, Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 102/124 Version 2.0 power supply strips installed at DSCN system and RF component ends shall have built in surge protectors. A surge protection device shall also be mounted on a circuit breaker panel of UPS output. Figure below shows power strip with built in surge protector. 5.16.2 RF Connector Type of Surge Protector to be installed in DSCN System: 1. The surge protector of impedance 75Ω shall have F type female and F type male ends for connecting F type male to linkway2100 modem’s RX port and F type female to RF cable. 2. The surge protector of impedance 50Ω shall have N type female and N type male ends for connecting N type male to Linkway 2100 modem’s TX port and N type female to RF cable. 3. The surge protector shall have F type female and F type male ends for connecting F type male to linkway S2 modem’s TX and RX ports and F type female to RF cable. The impedance of surge protector shall be 75Ω for RX path and 50 Ω for TX path. 4. The surge protector of impedance 50Ω shall have N type female and N type male ends for connecting N type male to BUC’s TX port and N type female to RF cable. 5. The surge protector of impedance 75Ω shall have N type female and N type male ends for connecting N type male to LNB RX’s port and N type female to RF cable. Note: Most of LNB consist of N type port but a few LNBs are of F type. Stations may check before procurement. 5.16.3 Connection Diagram of Surge Protector (SPD) for DSCN System: Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 103/124 Version 2.0 5.16.4 Specification of typical Coaxial Cable Surge Protector used in DSCN system Proposed model is 90V DC. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 104/124 Version 2.0 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 105/124 Version 2.0 NOTE: * Surge protector shall have rating of ‘DC Breakdown voltage’ of 90 Volt. # If 75 Ohm Surge protector is not available than 50 Ohm may be used with same voltage rating as above and LMR 400- 50 Ohm coaxial cable should be used instead of LMR 400-75 Ohm for Rx path. 5.16.5 Connection of Surge Protector Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 106/124 Version 2.0 5.17 Coaxial Connector Seal 5.17.1 Sealing Concepts for Coaxial Connectors: The electrical connecting points in coaxial connectors must be protected against ambient influences. Dust, water and moisture are a constant hazard especially in outdoor applications. Moisture particularly, which penetrates a coaxial system, changes the RF transmission enormously and leads to impedances or poor return loss values. Seals must be fitted at all connecting points to protect the sensitive and expensive electronics. Fig: Sealing Tape 5.17.2 Coax Seal Moisture Proof Sealing Tape 1/2" x 60". Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 107/124 Version 2.0 Coax-Seal is a special material that will quickly and effectively seal all types of coaxial fittings of any shape from moisture, water and corrosion. Coax-Seal stays flexible for years thus insuring moisture proof connections. It ensures good SWR and long coax life. CoaxSeal also allows you to disconnect and reconnect fittings with the same material by simply re-forming the plastic. Coax-Seal is the only material that will adhere to vinyl and poly vinyl connector’s outer covers. Coax-Seal is non-toxic, non-corrosive, non-conducting and stays flexible at any temperature. 5.17.3 Specifications of Self-Fusing Silicon tape/Silicon Rubber Tape: 1. Self-Bonding Silicone 2. Color: Black/oxide-red/Gray 3. Thickness: 30 mil 4. Width: 1.5 inches 5. Length: 15 feet 6. Operating Temperature Range: -30C to +70C 7. Tensile Strength: 700 PSI Minimum 8. Ultimate Elongation: 300% Minimum 9. Tear Resistance: 85 psi 10. Configuration: Rectangular shape Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 108/124 Version 2.0 Fig: Self-fusing Silicone tape ---------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 109/124 Version 2.0 Chapter - 6 Measurement of Earth Resistance 6.1 Measurement of Earth Resistivity:- 6.1.1 Need for the measurement of Resistivity:- The resistivity of the soil varies within extremely wide limits, between 1 and 10, 000 Ω-meters. The resistivity of the soil is found to be non-uniform at many station sites. To design the most economical and technically sound grounding system for large installations, it is necessary to obtain accurate data on soil resistivity and on its variation. Resistivity measurements at the site help in designing a good earthing system. The resistivity of the earth varies over a wide range depending on its moisture content. It is therefore, advisable to conduct earth resistivity tests during the dry season in order to get conservative results. 6.1.2 Test Locations:- In the evaluation of the earth resistivity of, at least eight test directions should be chosen from the centre to cover the whole site. This number shall be increased for very large station sites and for sites where, the test results obtained at various locations show a significant difference, indicating variations in soil formation. In case of transmission lines, the measurements shall be taken along the direction of the line throughout the length approximately once in every 4 kilometers. 6.2 Principle of Tests:- 6.2.1 Wenner’s four electrode method is recommended for these types of field investigations. In this method, four electrodes are driven into the earth along a straight line at equal intervals. A current I is passed through the two outer electrodes and the earth as shown in figure below and the voltage difference V observed between the two inner electrodes. The current I flowing into the earth produces an electric field proportional to its density and to the resistivity of the soil. The voltage V measured Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 110/124 Version 2.0 between the inner electrodes is, therefore, proportional to the field. Consequently, the resistivity will be proportional to the ratio of the voltage to current. If the depth of burial of the electrodes in the ground is negligible compared to the spacing between the electrodes, then:- ρ = 2π SV / I Earth testers normally used for these tests comprise the current source and meter in a single instrument and directly read the resistance. The most frequently used earth tester is the four –terminal Megger shown in Fig 1. When using such a Megger, the resistivity may be evaluated from the modified equation as given below. ρ = 2π x SR Where ρ = resistivity in ohm – meters S = distance between successive electrode in meters R = Megger reading in ohms. C1, C2 Current Electrodes P1, P2 Potential Electrodes Fig. 6.1 Measurement of Earth Resistivity ---------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 111/124 Version 2.0 Chapter -7 Supply, Installation, Testing and Commissioning [SITC] of Lightning, Surge Protection and Earthing System of CNS Facilities as part of Turnkey Project. 7.1When Lightning, Surge Protection and Earthing System of CNS Facilities are being procured under SITC as a part of turnkey project, General Technical specifications of the Tender Document in such cases should clearly specify following:- The vendor/supplier/system integrator shall be responsible for complete Supply, Installation, Testing and Commissioning of the Lightning, Surge Protection and Earthing System of the facility. The vendor/supplier/system integrator shall design and provide a comprehensive Lightning, Surge Protection and Earthing System which shall meet the following National and International Standards:- IS-2309 Code of protection for Lightning Protection IS -3043 Code of practice for earthing IS -5216 Safety procedures & practice in electrical work IEC -62305 Protection against Lightning IEC -61643 Low Voltage Surge Protective Devices IEC -60364 Low Voltage electric Installation: ANSI/UL 467 Grounding & Bonding Equipment 7.2 The lightning & Surge Protection System provided shall be a comprehensive system i.e. it should include:- 7.2.1Power Supply Surge Protection System at the input of Equipment room where the facility is proposed to be installed and each distribution board which will supply power to the equipment and its accessories. 7.2.2Surge Protection system should be provided to all incoming and outgoing cables connected to system such as Data lines [Telephone, OFC, RC cables etc] and RF Cables etc. Standard bonding of cable shields/trays to ground at building entry/exit points must be ensured. 7.2.3Air Terminals/Lightning Rods should be positioned to give full coverage of structure [Building, Antenna, Mast etc.] against the lightning. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 112/124 Version 2.0 7.2.4 Earthing system shall meet the following requirements: 7.2.4.1 Provide safety to equipment from power line faults, lightning and surges. 7.2.4.2 Provide a common reference ground plane for electronic equipment which will minimize electronic system noise and electromagnetic interference (EMI). 7.2.4.3 The grounding system design shall be based on single grounding network with multiple earths. 7.2.5 Appropriate references should be made to the guidelines provided in the manual in this regard. 7.2.6 If only a part of Lightning, Surge Protection and Earthing System e.g. only surge protection system is to be supplied by vendor then also appropriate references should be made to standards in this regard in the tender document. 7.3 Any other specific requirement for Lightning, Surge protection and earthing system specific to the equipment being procured should also be clearly specified in the Tender Document. 7.4 Lightning, Surge Protection and Earthing System of CNS facility shall form a part of Factory Acceptance Test (FAT) and Site Acceptance Test (SAT). 7.5 The complete layout of the Lightning, Surge Protection and Earthing System of CNS facility shall be submitted by the vendor/supplier/system integrator before commissioning. ---------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 113/124 Version 2.0 Chapter -8 Maintenance Procedures of Lightning, Surge Protection and Earthing Systems 8.1Responsibility of Maintenance Maintenance of Earthing, Lightning and Surge Protection System for the CNS installations installed in Terminal Building and/or Technical Block and located inside operational area and around airport (Radar, LLZ, GP, DVOR, OM/MM and NDB etc. ) shall be looked after by the CNS personnel. 8.2 Testing:- 8.2.1 On the completion of the installation, or any modification to it, the following measurements should be made and the results recorded in a lightning protective system logbook: i) The resistance to earth of the whole installation and of each earth termination. ii)The electrical continuity of all conductors, bonds and joints. 8.2.2 If the resistance to earth of a lightning protective system exceeds 5Ω, the value should be reduced. If the resistance is less than 5Ω, but significantly higher than the previous reading, the cause should be investigated and any necessary remedial action should be taken. 8.2.3 Tests should be repeated at fixed intervals, preferably not exceeding 06 months. 8.2.4 It is emphasized that before isolating a lighting protection earth, it should be tested to ensure that it is not “live”, using a sensitive voltage device. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 114/124 Version 2.0 8.3 System Inspection:- 8.3.1 All lightning protective systems should be visually inspected by a competent person during installation, after completion and after alteration or extension, in order to verify that they are in accordance with the recommendations in this code. 8.3.2 Visual inspections should be repeated at fixed intervals, preferably not exceeding 03 months. 8.3.3 In addition, the mechanical condition of all conductors, bonds, joints, and earth electrodes (including reference electrodes) should be checked and the observations noted. 8.3.4 If, for any reason, such as other site works, it is temporarily not possible to inspect certain parts of the installation, this also should be noted. 8.4 Total System Maintenance 8.4.1 Of particular importance is the regular detailed examination of the complete LPS for any evidence of corrosion. If this check is not carried out then vital components within the LPS, which may have suffered from corrosion and which could exhibit a high resistance could be missed. This will have a detrimental effect on the whole system making it an unattractive high impedance path for the lightning current to follow. 8.4.2 The earth resistance for all the electrodes must be measured periodically to ensure their usability. 8.4.3 The resistance of the air terminals to the earth electrode should also be measured periodically. 8.4.4 Maintenance Checks For Lightning Protection System Following checks should be carried out at regular interval – once every 06 months: Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 115/124 Version 2.0 8.4.4.1 Inspection of Air Terminal Physical inspection of air terminal and functionality checks with air terminal test meter. 8.4.4.2 Inspection of Down-conductors Check for corrosion Continuity testing by continuity tester, across all types of conductors in lightning protection and grounding system. The resistance should be strived to be as less as possible preferably less than 5.0 ohm. The down conductors are routed, located and electrically bonded as required. 8.4.5 Periodic Check for Earthing System: Earth resistance will be checked at the interval of 6 months with the standard process of measurement (Three point method) and recorded. If the measured value is beyond specified standards, corrective action must be taken. Earth termination systems are interconnected. Where a conductor is totally hidden, its electrical continuity should be tested. In case specified standards of earth resistance are not met, ground conductivity may be improved by Refilling of earth pit with electrolytic compound for electrolytic grounding system where provided. Recharging of earth pits in case conventional grounding system is installed. Physical inspection of connection between ground rod and down conductor near grounding system for corrosion, bad contacts followed by corrective action. 8.4.6 Inspection of Surge Protection devices: All surge protection devices should be checked at an interval of 3 months for their functionality. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 116/124 Version 2.0 Indications provided with surge protection system should be monitored and recorded on daily basis. Faulty devices should be replaced. 8.4.7 Earthing System Inspection Chambers Inspection Chambers of each earthing system should be maintained properly. Grass and other wild growth should be regularly cleared around inspection chamber. Whenever grading or other civil works takes around these chambers, they should be protected properly and should not be allowed to be lost during such works. 8.5 Special Total System Inspection: In the event of occurrence of major lightning strike around the Terminal building and other CNS facility as observed or monitored on the strike record counter, all the aforesaid inspection should be carried out and if need be, the corrective measures to be taken immediately so that LPS is maintained in its optimal effectiveness. 8.6 Inspection Regarding Modifications / Repairs of the Protected Structures While carrying out the periodic maintenance particular attention should be paid, besides earthing and corrosion, to alteration or extensions to the structure that may affect the LPS. Examples of such alterations or extensions are:- a) Change in the use of building; b) Installation of fuel oil storage tank near to building; c) Erection of radio aerials; and d) Installation or alteration to electrical, telecommunications or computing Facilities within or closely connected to the building. 8.7 Records The following records should be kept on site, or by the person responsible for the upkeep of the installation:- a) Scale drawings showing the nature, dimensions and position of all components and Parts of the LPS. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 117/124 Version 2.0 b) The nature of the soil and any special earthing arrangements. c) Date and particulars of salting, if used. d) Test conditions, date and results. e) Alterations, additions or repairs to the system. f) The name and contact details of the person/s responsible for the installation or its upkeep. 8.8 Maintenance Schedules A coordinated programs of inspection and maintenance of the lightning and surge protection systems have been designed in the form of preventive maintenance schedules as given below to ensure its serviceability. 1. Weekly Preventive Maintenance 2. Monthly Preventive Maintenance 3. Inspection after Lightning 4. Pre Monsoon/Pre Winter Maintenance. 8.8.1 Weekly Preventive Maintenance Schedule Visual Inspection (Corrosion, loose connection, dry solder) Surge Protective Devices Status Remarks Air Terminal Down Conductors Connectors of Earth Pit Air terminal & Down conductor Down conductor & Earth Electrode Self diagnostic type of Surge protectors. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 118/124 Version 2.0 8.8.2 Monthly Preventive Maintenance Schedule Surge Protective Devices Status (Resistance of GDT element should be very high) Earth Resistance Value observed Earth Resistance Value of site at the time of Installation Tightness of Connectors of Visual Inspection as given in table at 8.8.1 Air Remarks terminal & Down Conductor Down Conductor & Earth Electrode 8.8.3 Inspection after Lightning Status of surge protector(Resistance of GDT element) Visual Inspection as as given in table 8.8.1 Earth Air Resistance Remarks Terminal & its Connection Down Conductor & its Connection Earth Pit Rx path Tx path Power strip Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 119/124 Version 2.0 8.8.4 Pre Monsoon/Pre Winter Maintenance Earth Resistance Loop Resistance of Air terminal & Down conductor Tightness of Connectors of Greasing of Connectors of Visual inspection As given in table 8.8.1 Equipotential Bonding status Value at Installation Value observed Value at Installation Value observed Air terminal & Down conductor Down conductor & Earth electrode Air terminal & Down conductor Down conductor & Earth electrode Air terminals Down conductor ------------------------------------------------ Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 120/124 Version 2.0 Chapter -9 DEFINITIONS and ACRONYMS 9.1 DEFINITIONS In this Manual, the following definitions shall apply.- 9.1.1 Lightning Flash: Electrical discharge of atmospheric origin between cloud and earth comprising one or more impulse of many kilo amps 9.1.2 Lightning Strokes: The single distinguishable current impulse of a flash. 9.1.3 Lightning Protective System: The whole system of conductors used to protect a structure from the effects of lightning. 9.1.4 Air Termination (Air Termination Network):That part of a lightning protective system which is intended to intercept lightning discharges. 9.1.5 Down Conductor: Conductor that connects an air termination with an earth termination. 9.1.6 Bond: A conductor intended to provide electrical connection between the lightning protective system and other metalwork and between various portions of the latter. 9.1.7 Joint: A mechanical and/or electrical junction between two or more portions of a lightning protective system. 9.1.8 Testing Joint: Joints designed and situated so as to enable resistance or continuity measurements to be made. 9.1.9 Earth Termination (Earth Termination Network) :That part of a lightning protective system which is intended to discharge lightning currents into the general mass of the earth. All points below the lowest testing point in a down conductor are included in this term. 9.1.10 Earth Electrode: That part of the earth termination making direct electrical contact with earth. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 121/124 Version 2.0 9.1.11 Ring Conductor: Earth termination or electrode fixed to a structure above or below the earth or within or under foundations. A ring conductor may be used alone as an earth termination network or in conjunction with metal rods as an interconnection conductor. 9.1.12 Indicating Plate: A plate detailing the number and position of earth electrodes. 9.1.13 Reference Earth Electrode:An earth electrode capable of being completely isolated from an earth termination network for use in periodic testing. 9.1.14 Log Book:A record of tests and inspections of a lightning conductor installation. 9.2 Acronyms A : Ampere ASR : Airport Surveillance Radar ARSR : Air route Surveillance Radar ANSI : American National Standard Institute ATM system : Air Traffic Management System BS : British standards BIS : Bureau of Indian Standards cm : centimeter CNS : Communication Navigation Surveillance CNS-OM : CNS –Operation & Maintenance Deg. : Degree dia : Diameter DME : Distance Measuring Equipment ES : Earthing System EES : Earth Electrode System IS : Indian Standards (Bureau of India Standards) IEC : International Electro technical Commission IEEE : Institute of Electrical and Electronics Engineers LA : Lightning Arrestor Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 122/124 Version 2.0 LLZ : Localizer LPS : Lightning Protection System Ft : Feet GP : Glide Path kA : Kilo Ampere kmph : Kilometer per hour kV : Kilo volt M(m) : Meter mm : millimeter ms : mill second MIL –STD : Military Standard EEB :Equi-potential Earth Bus bar MEEB :Main Equi-potential Earth Bus bar NDB : Non Direction Beacon NF : Near Field NFPA : National Fire Protection Association MV : Mega Volt RF : Radio Frequency SMR : Surface Movement Radar UL : Underwriters Lab. V : Volt VLSI : Very Large Scale Integrated Circuit ---------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 123/124 Version 2.0 ******End of CNS Vol. V Ver. 2.0 *****"> 1G Ω Humidity 0-95% (R.H) Operating temperature -40 to +80 deg C. 3.20.8For more details regarding equipotential protector, Ref Annexure-2 – IEC 62305- 3 Standard. 3.21 Lightning Protection System(LPS) –Earth termination network, types and specifications:- 3.21.1 An earth electrode should be connected to each down conductor of LPS. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 50/124 Version 2.0 3.21.2 Each of these earths should have a resistance not exceeding the product given by 10Ω multiplied by the number of earth electrodes to be provided. For example, for a system with 15 down conductors, the individual earth reading should not be more than 10x15=150Ω. The whole lightning protective system, including any ring earth, should have a combined resistance to earth not exceeding 10Ω without taking account of any bonding. 3.21.3 A reduction of the resistance to earth to a value below 10Ω hasthe advantage of further reducing the potential gradient around the earth electrode when discharging lightning current. It also further reduces the risk of side flashing to metal in or on a structure. Hence every effort shall be made to ensure as much low ground resistance as possible. 3.21.4 The Earthing shall be provided/ made as per specifications given for Earthing System in the manual. ---------------------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 51/124 Version 2.0 Chapter - 4 Earthing Systems 4.1 Earthing:- Lightning, Surges or Unintentional contact between an energized electric conductor and the metal frame or structure that encloses it or an insulation failure in electrical equipment’s etc., can cause dangerously high voltages in the electrical distribution system. Under such circumstances, grounding provides an alternative low impedance path and thereby minimizes damages. A good and an efficient earth ensure that all parts of apparatus other than live parts shall be at earth potential that is zero at all the time. The scope of this section shall cover the following:- a) Earthing electrode/station b) Earthing conductors c) Earthing of equipment and installation The earthing resistance depends on:- a) Resistance of electrode b) Contact resistance between electrode and soil c) Resistance of soil between electrode surface and infinite earth. Resistance of electrode and contact resistance between electrode and soil are very small fraction of an ohm. Approximately 90 % of an earth resistance lies within 2 m between electrode and earth. Moreover, Earth conductivity is essentially electrolytic in nature and is affected by moisture content of soil, its chemical composition and concentration of salt dissolved in the contained water. It is also dependent on grain size and closeness in packing. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 52/124 Version 2.0 4.2 Selection of Earth Pit Site:- Following is the order of preference for selecting an earth pit position. Wet marshy ground Clay/loamy soil with little sand Clay/loamy soil with sand, gravel and stones Damp and wet sand 4.3 Scope: This specification of earthing system describes in detail, the components to be used and the procedure for constructing the earth system. The main purpose of this is to maintain consistent low earth resistance value over the years without contaminating the Ground water. 4.4 Components: The Earthing system shall consist of Earth Rods / plates and conductive and eco-friendly backfill compound, Earth termination clamps and Earth Bus Bar to facilitate connections to the equipment. The type earth electrode shall be any of the following, as specified:- (a) Pipe / rod earth electrode ; (as per IS 3043) (b) Plate earth electrode; (as per IS 3043) 4.5 Methods of Implementations:- The earthing can be implemented in four ways depending on the requirements, site and ground conditions:- 4.5.1 Conventional earthing using copper plates as per IS 3043:- 4.5.1.1 Earth Pit of the Size of 1 meter diameter and 3 meter depth shall be excavated, after depth of 3 meter the size of excavation shall be 900X300X900mm depth. 4.5.1.2 Plate Electrodes shall be in vertical position. 4.5.1.3PVC pipe for Watering shall be used of 40mm Diameter, length of 3m ( contain hole of 12mm Diameter in Zigzag manner starting from 15cm away from bottom to 2 meter height ). 4.5.1.4 At bottom 150mm layer of salt and charcoal power shall be installed, then Plate shall be installed. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 53/124 Version 2.0 4.5.1.5 Min 120 Kg each of charcoal powder and salt shall be used for each earthing pit. 4.5.1.6 The plate/pipe electrode, as far as practicable, shall be buried below permanent moisture level but in no case less than 2.5 meter below finished ground level. 4.5.1.7 600 mm × 600 mm × 3.15 mm copper plate buried at a depth of 8 ft in vertical position with the pit filled with alternate layers of charcoal and salt up to 4 ft from bottom. 4.5.1.8 The copper plates shall be connected to earth strip by riveting and brazing at no less than two points and the joints shall be protected by heavy coat of bitumen. 4.5.1.9 Schematic diagram for copper plate earthing is shown in Figure 4.1. Figure- 4.1 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 54/124 Version 2.0 4.5.2 Earthing rods directly driven into the earth :- 4.5.2.1 The length of the electrode shall be either 1.22meter or 2meter or 3meter based on the application. 4.5.2.2 Electrodes used for neutral earthing and lightning protection earthing shall be at least 3 meter long and for other applications, electrodes of at least 1.22meter or 2meter length may be used. 4.5.2.3 Earthing System is depicted in Fig 4.2(a) and 4.2(b) below:- Figure-4.2(a) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 55/124 Version 2.0 Figure-4.2(b) 4.5.2.4The combined earth rod length of a system should be not less than 9 meter whilst each individual earth rod should be not less than 1.5 meter in length. Figure-4.3 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 56/124 Version 2.0 4.5.3 Chemical earthing:- 4.5.3.1 A copper plate or copper coated rod, conventional earthing system should be used as a rule. In general salt and charcoal is used as backfill material for conventional earthing pits and these are eco-friendly. 4.5.3.2 In extreme conditions of rocky or sandy or dry condition where it is difficult to achieve the desired performance of earthing terminals by conventional system, chemical earthing may be employed. 4.5.3.3 The backfill material used in chemical earthing systems for soil treatment shall be highly conductive and should be certified as non-polluting and safe for use near potable ground water systems. 4.5.3.4 The ground conductivity enhancing backfill Material shall be a compound having a low resistance in the range of 0.12 ohm/Meter as specified in IEEE 80 (5 % of the Resistivity of Bentonite), non-corrosive highly conductive powdered material that improves grounding effectiveness, especially in areas of high soil resistivity such as rocky and sandy areas. 4.5.3.5 This material shall be suitable to be installed in either slurry or dry form. The backfill material shall confirm to the following specifications: Shall be highly electrically conductive and non-soluble. Shall not leach into ground. Shall be electronically conductive (like in metals) and shall not depend on moisture / salt for conduction Shall have a resistivity of less than 0.12 ohm/meter Shall be compatible with all copper grounding systems Shall contain a corrosion inhibitor to mitigate corrosion of copper Shall not contain hazardous chemicals Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 57/124 Version 2.0 Shall be certified to ANSI / NSF standard 60 as safe for use near potable ground water resources Shall not be affected by drought and shall be stable between -10˚ to +50˚C temperature. Shall be suitable for any kind of soil Where, the water table is high or runoff water is foreseen, the backfill compound shall solidify as specified in BS: 7430.The compound shall set like concrete to prevent erosion over a period of time. However under such condition only conventional earthing system should be used. NOTE:-Ref - BS7430 & IEEE80 where use of Carbon backfill compound for obtaining low resistance and maintenance free earthing is clearly recommended under specific conditions. 4.5.4 Horizontal / Lateral Earthing:- Whenever it is not possible to excavate to a depth where the vertical earth electrodes can be installed, the Lateral / Horizontal earthing method shall be adopted as follows:- 4.5.4.1 Three pits of 350 x 150 mm shall be dug to a depth of 3 feet and at a distance of at least 2meter from each other. 4.5.4.2 They can be laid either in a straight line formation or a triangular formation depending on the space availability at site. 4.5.4.3 One copper bonded steel plate of 300 mm× 300 mm× 3 mm shall be placed in each of the earth pits. 4.5.4.4 The earth pits shall be filled with the highly conductive and ecofriendly backfill material up to 6 inches above the top of the plate. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 58/124 Version 2.0 4.5.4.5 These plates shall be interconnected using copper flat / strip of at least 50 sq. mm cross sectional area. Such flat / strip shall be installed in a trench of 100 mm width at a depth of 600 mm (0.6m) from the ground level. 4.5.4.6 The entire trench shall be filled with the highly conductive and eco-friendly backfill material in such a way that there is a minimum of 2 inches of compound on the top and bottom of the interconnecting strip. 4.5 Earth Electrode Specifications:- 4.5.1 The electrodes shall be preferably in one piece of the desired length. 4.5.2 The electrode shall be a solid steel rod made of high tensile low carbon steel and coated with molecularly bonded electrolytic copper on the outside (as per UL 467 or equivalent) . The Earth electrode shall conform to the following specifications : Steel core: 600 MPa The thickness of the copper coating shall be at least 250 microns. Copper jacket should not crack on bending of earth rod Copper: 99.9% pure electrolytic copper Copper Structure: Very fine grain structure and highly ductile Copper Bonding: Fully bonded with steel core Nominal Diameter over Copper: 14.5mm Threads: Rolled into copper M16x2 The electrode diameter shall be 14.2 mmdia . Ends: Chamfer and Pointed (2mm and 6mm x 45deg) The electrode should be able to carry a minimum short time current of 15 kA for one second. Couplers should be made of brass Clamps should be made of brass or stainless steel Driving head or striker head should be of High tensile steel Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 59/124 Version 2.0 Driving tip should be of mild steel The earth electrode shall carry standards marking and manufacturer’s name. Clamps and fixtures should be used in the earthing system to ensure perfect and reliable contact. 4.5.3 Earth rod and accessories are depicted in Figure 4.4 below:- Figure-4.4 NOTE: - Ref – IS-3043 & IEC-60364 where use of such electrodes are permitted & the disadvantage of using plate electrodes are highlighted Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 60/124 Version 2.0 4.6 Soil Treatment:- Approximately 90 % of resistance between electrode and earth lies within a radius of 2m from the electrode. So, for soil treatment, to reduce the earth resistance, a shallow basin, 0.5m around the top of the electrode, half a metre in radius is excavated. This basin is then applied with artificial agents like NaCl, CaCl2, Na2CO3, CuSO4, salt, soft coke, charcoal in suitable proportion. Then the basin is filled several times with water for allowing it to percolate into the ground. 4.7 Earthing System Inspection Chamber:- 4.7.1 A 300X300X300 mm (inside dimension) concrete box with smooth cement plaster finish shall be provided on the top of the pit. A concrete lid, painted black, approx. 50 mm. thick with pulling hooks, shall be provided to cover the earth pit. 4.7.2 Care shall be taken regarding level of the floor surrounding the earth so that the connector is not too deep in the masonry or projecting out of it. 4.7.3 On backside of the cover, date of the testing and average resistance value shall be written with yellow paint on black background. 4.7.4 Alternatively prefabricated earthing inspection chambers may also be used. These have precise dimension and better service life. They are convenient to install and require low maintenance. A Polymer or CI cover shall be provided on the top of the earth system. The prefabricated Earthing inspection chamber should be light weight and suitable for extreme weather conditions. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 61/124 Version 2.0 4.7.5Care shall be taken regarding Care shall be taken regarding level of the floor surrounding the earth so that the connector is not too deep in the masonry or projecting out of it. 4.7.6 Grounding test terminal box shall be installed at an appropriate location suitable for testing the earth resistance. 4.7.7 Typical Inspection Chamber is shown in Figure 4.5 below:- Figure 4.5- Inspection Chamber 4.8 Earthing Conductor: - 4.8.1The earth conductors shall be fixed to the wall/columns etc., at every 500mm with 10mm spacers. The total earthing system shall be mechanically and electrically connected to provide independent path to earth. 4.8.2If the conductor is protected from corrosion, the area of cross section for copper conductor shall be more than 16 mm2 . Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 62/124 Version 2.0 4.8.3If the conductor is not protected from corrosion, the area of cross section for copper conductor shall be more than 25 mm2 . 4.9 Earth Resistance: The earth resistance of combined earth system (to be measured at EEB) shall be less than or equal to 1 ohm, as per the requirement. It shall be measured by an approved earth testing apparatus for individual earth pits. The procedure for measuring earth resistance is given in Chapter- 6. 4.10 Equipotential Earth Bus bar and its connection to equipment’s & Surge protection devices in the Equipment room: - 4.10.1 Equipotential earth bus bars 4.10.1.1There shall be one Equipotential earth bus bar for each of the equipment room. The Equipotential earth bus bars located in individual equipment rooms shall be termed as Sub Equipotential bus bars (SEEB). The Equipotential earth bus bar connected to Class ‘B’ SPDs and the main earth pit shall be termed as Main Equipotential earth bus bar (MEEB). 4.10.1.2The EEBs shall have pre-drilled holes of suitable size for termination of bonding conductors. The EEBs shall be insulated from the building walls. Each EEB shall be installed on the wall with low voltage insulator spacers of height 60mm. The insulators used shall have suitable insulating and fire resistant properties for this application. The EEBs shall be installed at the height of 0.5m from the room floor surface for ease of installation & maintenance. All terminations on the EEBs shall be by using copper lugs with spring washers. 4.10.2 Bonding Connections:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 63/124 Version 2.0 4.10.2.1 To minimize the effect of circulating earth loops and to provide equi-potential bonding, “star type” bonding connection is required. As such, each of the SEEBs installed in the rooms shall be directly connected to MEEB using bonding conductors. Also, equipment/racks in the room shall be directly connected to its SEEB. The bonding conductors shall be bonded to their respective lugs by welding. 4.10.2.2All connections i.e. routing of bonding conductors from equipment’s to SEEB & from SEEBs to MEEB shall be as short and as direct as possible with min. bends and separated from other wiring. However, connection from SPD to MEEB shall be as short as possible and preferably without any bend. 4.10.2.3Materials and dimensions of bonding components for connection of individual equipment’s with Equipotential bus bar and earth electrode shall be as given below:- Component /Bonding Material Size Main Equipotential earth busbar (MEEB) Copper 300X25X6 mm (min.) Sub Equipotential earth busbar (SEEB) Copper 150X25X6 mm (min.) Individual equipment’s to SEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 10 sq.mm SEEB to MEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 16 sq.mm Surge protection devices (SPD) to MEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 16sq.mm Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 64/124 Version 2.0 MEEB to main earth electrode. Multi-strand single core PVC insulated copper cable as per IS:694 (Duplicated) 35sq.mm Main earth pit to other earth pit in case of loop earth Copper tape 25X2 mm 4.11 Markings for Earthing systems:- 4.11.1 Earth bars and terminals at all switch boards shall be marked permanently as “E”. 4.11.2 Main earth terminal shall be marked safety earth – “DO NOT DISCONNECT”. 4.11.3 All earth pits shall be identified properly i.e. by suitable nomenclature identifying earth pit with the facility, Earth pit no etc. 4.12 Earthing System Requirement for CNS facilities:- 4.12.1 The electronic ground conductor shall be PVC insulated standard copper wire of 22 mm² or larger. One such conductor shall run from each equipment area or grouping of related electronic equipment and be terminated at the grounding test terminal box. Electronic ground conductors shall not be interconnected except at the common point. 4.12.2 Each cabinet and isolated item of electronic equipment shall be individually connected to the electronic ground conductor by the shortest possible route. The connecting jumper wire shall be 8 mm² or the size of the power feeder to the electronic equipment cabinet, whichever is larger. In addition, cabinets which are installed sideby-side shall be bonded together by copper wire jumpers, of 8 mm² or larger. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 65/124 Version 2.0 4.12.3 Care shall be taken to assure that ground loops are not created inadvertently. 4.13 COMMUNICATIONS CABLE TRAY SYSTEMS:- 4.13.1 Bond the metallic structures of one cable tray in each tray run following the same path to provide 100 percent electrical continuity throughout this cable tray systems as follows:- 4.13.1.1 Splice plates provided by the cable tray manufacturer can be used for providing a ground bonding connection between cable tray sections when the resistance across a bolted connection is 10 milliohms or less. 4.13.1.2 Install a standard (16 mm²) bonding jumper across each cable tray splice or junction where splice plates cannot be used. 4.13.1.3 When cable tray terminations to cable rack, install standard 16 mm² (bonding jumper between cable tray and cable rank pan. 4.14 Important points regarding Earthing System 4.14.1 Minimum dimensions for earth terminations are as follows:- Component Dia in mm Area mm 2 Copper clad or galvanized steel rods. For Copper clad steel rods, the core should be of low carbon steel of tensile strength700N/mm 2 , (as per Underwriters laboratories UL-467-2007)99.9% electrolytic copper should be molecularly bonded to the steel core and radial width of copper should not be less than 0.25mm. 17.2(with minimum length of 3 meter) 25 32 232 491 804 4.14.2 Earth network/ring: A common earth termination network is recommended for the lightning protective system and all other services. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 66/124 Version 2.0 4.14.3 The resistance to earth should, in this case, be the lowest value required for any of the individual services. In other words, all the earth terminals that of equipment, electrical power, lightning protective system, antenna, etc., are to be connected together to form a common earth network. 4.14.4 One lightning protection system should consist of at least one plate earth terminal and other earth electrodes made by driving copper rods of suitable type into the ground. 4.14.5 No appreciable advantage in resistance reduction is gained by increasing the diameter or surface of the driven electrode. Larger sizes become more difficult to drive and are more expensive in materials. 4.14.6 Where deep driving of earth rods is not possible, a matrix arrangement of rods coupled to one another by conductors can be used. If possible the earth rods must be spaced at a distance at least twice their driven depth. 4.15 Importance of earth ring in reducing potential gradient:- 4.15.1 As the lightning current is discharged through the earth electrode, the surrounding soil is raised for the duration of the discharge to a potential with respect to the body of the earth. The resulting potential gradient is illustrated in Figure 4.6 and it is shown how its voltage gradient can be reduced by adding ring earth electrodes to lower the effective earth resistance. 4.15.2 Such potential difference may be lethal to a person if it exceeds a few thousand volts and to an animal if it exceeds a few hundred volts. 4.15.3 As this potential difference is a function of the product of the lightning current and the resistance of the earth electrode, the importance of keeping the latter as low as possible is evident. For practical purposes, a maximum value of 10Ω is recommended. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 67/124 Version 2.0 4.15.4 The danger to persons within a structure is effectively reduced by the presence of any floor other than that of earth or rock. 4.15.5 To reduce the voltage gradient in case of lightning, a long ground surface near to masts, towers and columns, the earth terminations of each lightning protective system should be interconnected by a ring conductor. 4.15.6 This ring conductor should preferably be buried to a depth of at least 0.5m unless other considerations, such as the need for bonding other objects to it or testing, make it desirable to leave it exposed. 4.15.7 The ring conductor should be connected to the ring conductors of the neighbouring structures. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 68/124 Version 2.0 Figure-4.6 4.16 Anti-corrosive measures (Importance thereof):- Corrosion due to atmospheric, chemical, electrolytic or other causes is likely to impair any part of the lightning protective system; therefore, suitable precautions as mentioned below should be taken to prevent its occurrence:- 4.16.1 Due to the harmful corrosion which is likely to result, coke breeze should not be allowed to come in contact with copper electrodes and salting of the ground in the vicinity of any earth electrode should not be practiced. 4.16.2 In some cases if it is not possible to achieve earth’s resistance less than 1 ohm then all copper to copper joints shall be made by welding or brazing only Bolting of joints shall not be accepted. The minimum distance by which these electrodes should be separated is 3mtrs and maximally it can go up to twice of it i.e. 6mtrs. 4.16.3 Electrolytic corrosion between dissimilar metals: The contacts of dissimilar metals unless the contact surfaces are kept completely dry and protected against the ingress of moisture, are likely to initiate and accelerate corrosion. 4.16.4 The metal of lightning protection system must be compatible to the metals of the structure over which it passes or makes contact with corrosion inhibitors may be used if required. 4.16.5 Aluminium is prone to corrosion when in contact with cement and mortar mixes. 4.16.6 Backfill compound if used for soil treatment shall provide anti corrosion protection to the electrodes. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 69/124 Version 2.0 4.16.7 Fittingsshould be resistant to the corrosive agencies or be otherwise suitably protected. 4.16.8 Joints and bonds may be protected with bitumen or embedded in plastic compound according to the local conditions as shown in figure 4.7 below:- Figure-4.8 ------------------------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 70/124 Version 2.0 Chapter-5 Surge and Transient Protection Systems 5.1 Surge & Transient:- Surge is an overvoltage or overcurrent of a short duration occurring on a power line while transient is an overvoltage or overcurrent pulse occurring on a power, signal, control or data line. The term “surge” is used to describe a transient overvoltage on a power line that has duration of a few microseconds. A transient overvoltage can exceed the insulation rating of electrical equipment causing degradation of insulation and immediate damage to the equipment. Relatively low-amplitude transient overvoltages applied repetitively on the equipment will reduce its mean time before failure. The result will be that equipment will have to be repaired more often, increasing operating costs. 5.2 Why Surge Protection is needed:- 5.2.1Power surges can cause failure, permanent degradation, or temporary malfunction of electronic devices and systems. The development of an effective Surge Protection Device (SPD) is of paramount importance to manufacturers and users of industrial electronic equipment. 5.2.2Almost all manufacturers of industrial-type SPDs use metal–oxide varistors (MOVs) in their design. MOVs are composed of a thin disk wafer of material (metal– oxide) that has a known voltage breakdown characteristic. At low voltages, the MOV conducts very little current (microamperes). As the voltage approaches breakdown, the MOV then begins to conduct current. At voltages slightly above the break down, large currents flow, effectively clamping the output voltage. This clamping feature allows the higher voltage levels to be shunted to ground, preventing overvoltages on equipment. 5.2.3 Figure 5.1 and 5.2below show the voltage waveform before and after an ideal Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 71/124 Version 2.0 SPD:- Figure 5.1 Voltagewaveform before SPD. Figure 5.2 Voltage waveform after an ideal SPD 5.2.4 Causes of Power Line Surges:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 72/124 Version 2.0 The sporadic damped phenomena that occur in electrical systems are generally described as transients and surges or in other words Power surges and transient overvoltages are due to the sudden change in the electrical conditions of a circuit and the release of large amounts of energy stored in the inductance and capacitance elements of the system. Sources of power surges can be external or internal to the facility. 5.2.4.1External sources of transient overvoltages can be the following:- Lightning. Switching (on/off) of capacitor banks, for power coefficient Correction. Power-line disconnection and reconnection. Transformer switching on/off. Electrostatic discharges. Power utility load switching. Poor quality of power transmission and distribution grids. 5.2.4.2 Internal surges are caused by the operation of the following devices:- circuit breakers or fuses; electric motors, i.e., elevators; air conditioners; VSDs generators. 5.3 It is very important to note that the IS 3043 has specifically recommended the use of surge protection systems to protect the sensitive equipment’s against over voltages induced by lightning and switching surges. 5.4 Transient over voltages are generated due to:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 73/124 Version 2.0 a) Whenever a lightning strikes directly / in the near vicinity; b) As a consequence of different faults in the power system; and c) Switching on and off of different loads etc. d) Hence, it is very important to protect the sensitive electrical and electronic equipment’s against these transient voltage surges. 5.5 The transient voltage surges are broadly classified into two types :- Lightning Surges ( Handled by Class B or Type I SPDs); and Switching surges ( Handled by Class C or Type II SPDs) 5.5.1 The lightning surges bring very high amount of destructive energy into the system and hence, are potentially very dangerous. The Class B SPDs are designed to handle the lightning current surges. 5.5.2 The switching surges are relatively frequent than the lightning surges. Although they bring in relatively less energy into the system, however, they still are strong enough to damage the sensitive electronics. The switching surges are handled by the Class C SPDs. 5.5.3 Latest IEEE Guidelines express that lightning activity at a place can induce surges due to Galvanic Coupling for about 1.7 km radius from the point of impact. Hence, it is important to note, both the lightning and the switching surges can come from outside of our power system and hence these surges need to be isolated at the mains input point itself so it is important to put appropriate surge protection devices to all the cables i.e. Power, Data, Remote Control, RF Cables or any other devices which is likely to carry surge and which enters into a equipment room where sensitive CNS/ATM systems are installed. 5.6 Methodology for surge protection:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 74/124 Version 2.0 Surge mitigation technique suggests use of surge suppression devices for power and data lines. The sole function of a good quality surge suppressor is to protect sensitive electronic equipment from transient over voltages. It must limit transient over voltages to a value that do not surpass the AC sine wave peaks by more than 30%. 5.6.1 A surge protector (or surge suppressor) is an appliance designed to protect electrical devices from voltage spikes. A surge protector attempts to limit the voltage supplied to an electric device by either blocking or shorting to ground any unwanted voltages above a safe threshold. 5.6.2 The terms surge protection device (SPD), or the obsolescent term transient voltage surge suppressor (TVSS), are used to describe electrical devices typically installed in power distribution panels, process control systems, communications systems, and other heavy-duty industrial systems, for the purpose of protecting against electrical surges and spikes, including those caused by lightning. 5.7 Main performance parameters of a surge protector are as follows:- 5.7.1 Clamping voltage also known as the let-through voltage. This specifies what spike voltage will cause the protective components inside a surge protector to divert unwanted energy from the protected line. A lower clamping voltage indicates better protection, but can sometimes result in a shorter life expectancy for the overall protective system. 5.7.2 Joules rating: This number defines how much energy the surge protector can theoretically absorb in a single event, without failure. Counter-intuitively, a lower number may indicate longer life expectancy if the device can divert more energy elsewhere and thus will need to absorb less energy. In other words, a protective device offering a lower clamping voltage while diverting the same surge current will cause more of the surge energy to be dissipated elsewhere in the system. Better protectors Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 75/124 Version 2.0 exceed peak ratings of 1000 Joules and 40, 000 Amperes. It is often claimed that a lower Joule rating is undersized protection, since the total energy in harmful spikes can be significantly larger than this. However, if properly installed, for every joule absorbed by a protector, another 4 to 30 joules may be dissipated harmlessly into ground. A MOVbased protector (described below in Para 4.8.1) with a higher let-through voltage can receive a higher joule rating, even though it lets more surge energy through to the device to be protected. 5.7.3 Response time: Surge protectors do not operate instantaneously; a slight delay exists. The longer the response time, the longer the connected equipment will be exposed to the surge. However, surges usually take around a few microseconds to reach their peak voltage, and a surge protector with a nanosecond response time would kick in fast enough to suppress the most damaging portion of the spike. All MOVs have response times measured in nanoseconds, while test waveforms usually used to design and calibrate surge protectors are all based on modelled waveforms of surges measured in microseconds. As a result, MOV-based protectors have no trouble producing impressive response-time specifications. Slower-responding technologies (notably, GDTs) may have difficulty protecting against fast spikes. 5.7.4 Transient surges: These are characterised by different waveforms. The most frequently referenced IEEE waveform used to simulate lightning induced transient activity is the combination wave. This wave is characterised by short duration, high frequency 8/20 µs current and 1.2/50 µs voltage waveform. 5.8 Types of surge protectors:- Systems used to reduce or limit high voltage surges can include one or more of the following types of electronic components. Some surge suppression systems use multiple technologies, since each method has its strong and weak points. Some of these operate primarily by diverting unwanted surge energy away from the protected load, through a protective component connected in a parallel (or shunted) topology. Some others block Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 76/124 Version 2.0 unwanted energy by using a protective component connected in series with the power fed to the protected load, and additionally may shunt the unwanted energy like the earlier systems. 5.8.1 Metal oxide Varistors (MOV) : A metal oxide varistors consists of a bulk semiconductor material (typically sintered granular zinc oxide) that can conduct large currents (effectively short-circuits) when presented with a voltage above its rated voltage. MOVs typically limit voltages to about 3 to 4 times the normal circuit voltage by diverting surge current elsewhere than the protected load. 5.8.1.1 MOVs may be connected in parallel to increase current capability and life expectancy; provided they are matched sets (unmatched MOVs have a tolerance of approximately ±20% on voltage ratings, which is not sufficient). 5.8.1.2 MOVs have finite life expectancy and "degrade" when exposed to a few large transients, or multiple smaller transients. As a MOV degrades, its triggering voltage falls lower and lower. If the MOV is being used to protect a low-power signal line, the ultimate failure mode typically is a partial or complete short circuit of the line, terminating normal circuit operation. 5.8.1.3 If used in a power filtering application, eventually the MOV behaves as a part-time effective short circuit on an AC (or DC) power line, which will cause it to heat up, starting a process called thermal runaway. 5.8.1.4 As the MOV heats up, it may degrade further, causing a catastrophic failure that can result in a small explosion or fire, if the line current is not otherwise limited. 5.8.1.5 When used in power applications, MOVs usually are thermal fused or otherwise protected to avoid persistent short circuits and other fire hazards. In a typical power strip, the visible circuit breaker may be distinct from the internal thermal fuse, which is not normally visible to the end user. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 77/124 Version 2.0 5.8.1.6 If a surge current is so excessively large as to exceed the MOV parameters and blow the thermal fuse, then a light found on some protectors would indicate unacceptable failure. 5.8.1.7 Even adequately-sized MOV protectors will eventually degrade beyond acceptable limits, with or without a failure light indication. 5.8.1.8 Therefore, all MOV-based protectors intended for long-term use should have an indicator that the protective components have failed, and this indication must be checked on a regular basis to insure that protection is still functioning. 5.8.1.9 Because of their good price/performance ratio, MOVs are the most common protector component in low-cost basic AC power protectors. 5.8.2 Transient voltage suppression (TVS) diode: ATVS diode is a type of Zener diode, also called an avalanche diode or silicon avalanche diode (SAD), which can limit voltage spikes. 5.8.2.1 These components provide the fastest limiting action of protective components (theoretically in picoseconds), but have a relatively low energy absorbing capability. 5.8.2.2 Voltages can be clamped to less than twice the normal operation voltage. 5.8.2.3 If current impulses remain within the device ratings, life expectancy is exceptionally long. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 78/124 Version 2.0 5.8.2.4 If component ratings are exceeded, the diode may fail as a permanent short circuit; in such cases, protection may remain but normal circuit operation is terminated in the case of low-power signal lines. 5.8.2.5 Due to their relatively-limited current capacity, TVS diodes are often restricted to circuits with smaller current spikes. 5.8.2.6 TVS diodes are also used where spikes occur significantly more often than once a year, since this component will not degrade when used within its ratings. 5.8.2.7 A unique type of TVS diode (trade names Transzorb or Transil) contains reversed paired series avalanche diodes for bi-polar operation. 5.8.2.8 TVS diodes are often used in high-speed but low power circuits, such as in data communications. These devices can be paired in series with another diode to provide low capacitance as required in communication circuits. 5.8.3 Thyristor Surge Protection device (TSPD), a specialized solid-state electronic device used in crowbar circuits to protect against overvoltage conditions. 5.8.3.1 These Thyristor-family devices can be viewed as having characteristics much like a spark gap or a GDT, but can operate much faster. 5.8.3.2 They are related to TVS diodes, but can "break over" to a low clamping voltage analogous to an ionized and conducting spark gap. After triggering, the low clamping voltage allows large current surges to flow while limiting heat dissipation in the device. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 79/124 Version 2.0 5.8.4 Gas Discharge Tube (GDT): A gas discharge tube (GDT) is a sealed glassenclosed device containing a special gas mixture trapped between two electrodes, which conduct electric current after becoming ionized by a high voltage spike. 5.8.4.1 GDTs can conduct more current for their size than other components. 5.8.4.2 Like MOVs, GDTs have a finite life expectancy, and can handle a few very large transients or a greater number of smaller transients. 5.8.4.3 The typical failure mode occurs when the triggering voltage rises so high that the device becomes ineffective, although lightning surges can occasionally cause a dead short. 5.8.4.4 GDTs take a relatively long time to trigger, permitting a higher voltage spike to pass through before the GDT conducts significant current. It is not uncommon for a GDT to let through pulses of 500 V or more in duration of100 ns. 5.8.4.5 In some cases, additional protective components are necessary to prevent damage to a protected load, caused by high-speed let-through voltage which occurs before the GDT begins to operate. 5.8.4.6 GDTs create an effective short circuit when triggered, so that if any electrical energy (spike, signal, or power) is present, the GDT will short this. 5.8.4.7 Once triggered, a GDT will continue conducting (called follow-on current), until all electric current sufficiently diminishes, and the gas discharge quenches. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 80/124 Version 2.0 5.8.4.8 Unlike other shunt protector devices, a GDT once triggered will continue to conduct at a voltage less than the high voltage that initially ionized the gas; this behaviour is called negative resistance. 5.8.4.9 Additional auxiliary circuitry may be needed in DC (and some AC) applications to suppress follow-on current, to prevent it from destroying the GDT after the initiating spike has dissipated. 5.8.4.10 Some GDTs are designed to deliberately short out to a grounded terminal when overheated, thereby triggering an external fuse or circuit breaker. 5.8.4.11 Many GDTs are light-sensitive, in that exposure to light lowers their triggering voltage. Therefore, GDTs should be shielded from light exposure, or opaque versions that are insensitive to light should be used. 5.8.4.12 Due to their exceptionally low capacitance, GDTs are commonly used on high frequency lines, such as those used in telecommunications equipment. 5.8.4.13 Because of their high current handling capability, GDTs can also be used to protect power lines, but the follow-on current problem must be controlled. 5.8.5 Selenium Voltage Suppressor: An "overvoltage clamping" bulk semiconductor similar to a MOV, though it does not clamp as well. 5.8.5.1 It usually has a longer life than a MOV. It is used mostly in high-energy DC circuits, like the exciter field of an alternator. 5.8.5.2 It can dissipate power continuously, and it retains its clamping characteristics throughout the surge event, if properly sized. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 81/124 Version 2.0 5.8.6 Carbon Block Spark Gap Overvoltage Suppressor: A spark gap is one of the oldest protective electrical technologies still found in telephone circuits, having been developed in the nineteenth century. In this type of suppressor, a carbon rod electrode is held with an insulator at a specific distance from a second electrode. The gap dimension determines the voltage at which a spark will jump between the two parts and short to ground. The typical spacing for telephone applications is 0.076 mm (0.003"). 5.8.6.1 Carbon block suppressors are similar to gas arrestors (GDTs) but with the two electrodes exposed to the air, their behaviour is affected by the surrounding atmosphere, especially the humidity. 5.8.6.2 Since their operation produces an open spark, these devices should never be installed where an explosive atmosphere may develop. 5.8.7 Quarter-wave coaxial surge arrestor :Used in RF signal transmission paths, this technology features a tuned quarter-wavelength short-circuit stub that allows it to pass a bandwidth of frequencies, but presents a short to any other signals, especially down towards DC. The pass bands can be narrowband (about ±5% to ±10% bandwidth) or wideband (above ±25% to ±50% bandwidth). Quarter-wave coax surge arrestors have coaxial terminals, compatible with common coax cable connectors (especially N or 7- 16 types).They provide the most rugged available protection for RF signals above 400 MHz; at these frequencies they can perform much better than the gas discharge cells typically used in the universal / broad band coax surge arrestors. Quarter-wave arrestors are useful for telecommunications applications, such as Wi-Fi at 2.4 or 5 GHz but less useful for TV/CATV frequencies. Since a quarter-wave arrestor shorts out the line for low frequencies, it is not compatible with systems which send DC power for a LNB up the coaxial downlink. A typical Quarter-wave coaxial surge arrestor is shown in figure 5.3 below:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 82/124 Version 2.0 Figure- 5.3 5.8.8 Series Mode (SM) Surge Suppressors: These devices are not rated in Joules because they operate differently from the earlier suppressors, and they do not depend on materials that inherently wear out during repeated surges. 5.8.8.1 SM suppressors are primarily used to control transient voltage spikes on electrical power feeds to protected devices. 5.8.8.2 They are essentially heavy-duty low-pass filters connected so that they allow 50/60 Hz line voltages through the load, while blocking and diverting higher frequencies. 5.8.8.3 This type of suppressor differs from others by using banks of inductors, capacitors and resistors that shunt voltage spikes to the neutral wire, whereas other designs shunt to the ground wire. Where ground is bonded to neutral at the electrical service entrance, the resulting surge ultimately flows into ground at that connection, but by first dumping into neutral, nearby ground contamination is avoided. 5.8.8.4 Since the inductor in series with the circuit path slows the current spike, the peak surge energy is spread out in the time domain and harmlessly diverted into the capacitor bank. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 83/124 Version 2.0 5.8.8.5 Experimental results show that most surge energies occur at under 100 Joules, so exceeding the SM design parameters is unlikely, but it provides no contingency should rare events induce energies that exceed it. 5.8.8.6 SM suppressors do present a theoretical fire risk, should the absorbed energy exceed design limits of the dielectric material of the components. 5.8.8.7 In practice, surge energy is also limited via arc-over to ground during lightning strikes, leaving a surge remnant that often does not exceed a theoretical maximum (such as 6000 V at 3000 A with a modelled shape of 8 x 20 µs waveform specified by IEEE/ANSI C62.41). 5.8.8.8 SM suppression focuses its protective philosophy on a power supply input, but offers nothing to protect against surges appearing between the input of an SM device and data lines, such as antenna, telephone or LAN connections, or multiple such devices cascaded and linked to the primary devices. 5.8.8.9 In this design philosophy, such events are already protected against the SM device before the power supply. 5.8.8.10 SM low-pass filters are generally not suitable for data communications circuits, because they would also block high-speed data signals from getting through. 5.8.8.11 In comparison to devices relying on components that operate only briefly and do not normally conduct electricity (such as MOVs or GDTs), SM devices tend to be bulkier and heavier than those simpler spike shunting components. 5.8.8.12 The initial costs of SM filters are higher, but a long service life can be expected if they are used properly. In-field installation costs can be higher, since SM Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 84/124 Version 2.0 devices are installed in series with the power feed, requiring the feed to be cut and reconnected. 5.9 Important points regarding installation of Surge Protection at mains input level and at power distribution boxes:- 5.9.1 A comprehensive surge protection system comprising of an INTEGRATED CLASS B +CLASS C TYPE SURGE PROTECTION SYSTEM is ideally suited for installation at the mains input and substation switch boards. 5.9.2 The SPD used shall comply with the performance requirements of the IEC 61643 or equivalent. 5.9.3 The Main Surge Protection System is to be installed in the mains input panel on the LT side. An indicative system is shown in Figure -5.4 below:- Figure- 5.4 5.9.4 The system shall offer comprehensive protection against all types of transient Over Voltages and shall use high capacity MOVs only. It shall be of combined class B+C type. i.e. it shall be capable of handling Lightning as well as Switching Surges. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 85/124 Version 2.0 5.9.5 Class B surge protection device (N-G) may consist of encapsulated air gap device (GDT) and may be used as galvanic separation between N-PE conductors with following characteristics:- i) Protection mode : N-PE ii) Single pole surge protection device iii) Impulse current capacity : 100 kA iv) Max current 160 kA v) Status indicator available 5.9.6 The surge protection system shall be configured such that the system offers all mode (Differential) protection. The protection shall be between each phase to neutral, each phase to earth and between neutral to earth. A typical system is indicated below:- Figure-5.5 5.9.7 The surge protection system shall comprise of multiple MOV based surge arrestors housed in an IP 65 enclosure. 5.9.8 Each Surge arrestor shall consist of at least three elements for backup protection. Each element of the surge arrestors shall comply with the performance requirements of the IEC 61643 or equivalent. 5.9.9 The Surge protection system design shall be modular in nature so that the Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 86/124 Version 2.0 individual surge arrestors can be replaced after its elements have reached the end of their life. 5.9.10 The surge arrestors shall be mounted on a DIN RAIL and housed in an IP 65 or equivalent grade enclosure for reliability and ease of replacement / maintenance. 5.9.11 The design shall be such that when a given element fuses, the balance elements in the surge arrestor continue to offer protection to the installation till it is replaced with a new one in a short period of time. 5.9.12 When any element fuses, the respective status indicator flag shall turn red indicating that the element is out of service. 5.9.13 Each individual element in the surge arrestor shall be rated as follows : - Max. Continuous operating voltage (Uc) 440 V Min. Lightning impulse current (Iimp) 15 KA ( 10/350 µs) per phase Nominal discharge current 80 KA(8/20 µs) Maximum discharge current 150 KA(8/20 µs) Peak value current 40 KA(10/350 µs) Specific energy 400 KJ/Ω Charge 20 As Protection level 1.9 KV(8/20µs);1.7 KV(10/350µs) Response time < 25 ns Residual current < 2.5 mA Follow current 0 Thermo coupler Present Fuse Present Short circuit withstand 25 KA for 50 Hz supply Switching surge current (Imax) 100 KA (8/20 µs) per phase Switching surge current (Inom) 30 KA (8/20 µs) per phase Clamping voltage 1800 V between L-E, L-N, N-E Minimum Inom exposures before fusing 20 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 87/124 Version 2.0 5.9.14 The surge arrestor elements shall be designed to withstand the specified Switching Surge Current (Inom) current for a minimum of 20 times without fusing. 5.9.15 The surge protection system shall be connected in parallel with the circuit and shall not draw the line current. The system shall be connected to the circuit with 10 / 16 Sq mm single core PVC insulated flexible copper conductor cables. The terminal connectors of the system shall be so designed to avoid any loose connections. 5.9.16 In addition to the Main surge protection Device, which provides combined Class B & C protection at the main incoming, a series surge filter may be considered to be installed at all the UPS incoming and outgoing supply which will have the following features:- I) It shall offer All Mode Protection; II) It shall offer redundant protection and staged ; III) LED status indication; and IV) Option for remote monitoring may be considered. 5.9.17 The surge filter shall filter the surges and transients occurring up to the branch panels. It shall offer all mode protection for (L-N, L-E and N-E). 5.9.18 It shall conform to ULI 1449 Edition 2 or equivalent for the metallic enclosure. 5.9.19 The MCB shall be included to ensure safety isolation under power frequency overload condition. 5.9.20 It shall be suitable for a line current of 32A or 63A, 3 phase and up to 320 V 50 Hz power supply. 5.9.21 It shall be connected in series. The surge rating shall be 40 kA, 8/20µs. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 88/124 Version 2.0 5.9.22 Each phase surge arrestor employed shall have two redundant and independent fused and thermal over load protection elements to provide back-up protection for continued equipment survival. 5.9.23 The technical features shall be as described below: Normal Voltage 320Vrms(1p), 380V(3p) Operating Voltage 180-280Vrms(1 ph); 300-480Vrms (3 ph) Operating Frequency 50 Hz Connection type Series Max. surge rating per line 50 kA to 140kA (8/20µs) Let through voltage <380V for 3 KA Cat B Protection mode L-N, L-E, N-E Earth leakage current < 1 µA Efficiency 99% Frequency response 3 dB (at 800 Hz) Response time < 5 ns Standards compliance BS6651-1999 cat.A.B.C AS1768-2003 cat.A.B.C IEEE C62.41 cat.A.B.C CP33-1999 cat.A.B.C IEC 1000-4 5 1995 UL 1449 second edition EMC Compliance BS EN 60950 : 1992; BS EN 61000 : 1999 Alarm isolation 4 Kv Status indicator LED Optional remote alarms Siren sound OK and FAIL LED Alarm(volt free contact) N/O, N/C(2A@250Vac) Alarm conductor size 2.5mm² Conductor size 35 mm² Mounting Back panel screw mount Enclosure material Galvanized steel alloy Enclosure IP rating IP 55 Operating temperature - 40 -85ºc Humidity 0-95% (R.H) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 89/124 Version 2.0 5.10 COMPUTER NETWORK PROTECTOR: - The Cat5, Cat 5e, Cat 6 and POE (Power over Ethernet) cables shall be provided with a suitable surge protector. It shall be suitable for RJ 45 connectors 5.10.1 It shall be designed to protect all widely used computer network system using Ethernet twisted pairs technology like 10/100/1000 BaseT, CDDI, ATM155 and also the Power-over-Ethernet. 5.10.2 It shall offer protection against transient over voltages due to lightning induced surges, AC power interference and ground loop energies appearing between any signal pair and / or its ground which can damage the sensitive network equipment. 5.10.3 The series protector shall be designed to protect both common and differential mode in all the 8 pins of the RJ 45 port and its ground lead. 5.10.4 It shall have the latest circuitry using Silicon Avalanche diode to ensure very fast response time and exceptional low let-through voltage which results in maximum system reliability and up-time. 5.10.5 The shunt capacitance shall be 5pf and negligible in-line resistance so that even the most demanding high speed gigabit multimedia signal can be passed without much signal degradation. 5.10.6 It shall be compact, in-line and simple plug-in design to enable it to be easily located near the protected equipment. 5.10.7 The technical features shall be as described below:- Max. working Voltage 5V Max. operating current 300mA Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 90/124 Version 2.0 Protection modes Common and transverse Lines protected All pairs Response time < 5 ns Max. surge rating 100A (8/20µs) Max. Data rate 100Mb/s (C5, PoE models), 1000Mb/s(C6 models) Let through voltage 23V (A1 5 KV 10/700µs) Shunt capacitance 5pF (single port models), 25pF(rack-mount models) In line resistance -0 Ω Standards compliance 100 Base T, 1000Base T, CAT5, CAT5e, CAT6 Connector type RJ 45 Earth connection Flying lead(single port models) Earth stud(rack-mount models) Enclosure material Anodized aluminum (single port) Galvanized steel alloy(multi-port) Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.11 Telecom line protector: All the telecommunication lines shall be protected with a suitable Surge Protector to protect the modems and other sensitive equipment’s. It shall be designed to protect all widely used telecommunication lines like PSTN, ISDN, DDN and DSL using twisted pairs. Different connectors like RJ45, RJ11 and plug/socket models shall be used to obtain optimum protection. Following are the main characteristics of Telecom line protector:- 5.11.1 The hazard of lightning induction in telephone lines can be managed by using transient protection units in parallel with each line. These multi line protection can have multi stage protection i.e. Hybrid GDT for over voltage protection and PTC for over current protection. 5.11.2 It shall offer Protection against Transient over voltages due to lightning induced surges, AC power interference and ground loop energies appearing between Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 91/124 Version 2.0 any signal pair and/or its ground that can damage the sensitive telecommunication equipment. 5.11.3 The protector shall be designed to protect both common and differential mode in all the connected pins of the RJ 45 or RJ 11 port and its ground lead. 5.11.4 They shall be multi-stage design which employ a combination of high energy gas discharge tube, ultra fast diodes and SAD which results in maximum system reliability and up-time. 5.11.5 It shall have 20KA surge handling capability and 20MHz high bandwidth, so that it can provide the safest protection in lightning intense environment to ensures a smooth data traffic. 5.11.6 It shall be compact, in-line and simple plug-in design enabling it to be easily located near to the protected equipment. 5.11.7 The important technical features of Telecom Line Protector are described as below:- Max. working Voltage (Line to line) 190v (PSTN) , 60 V (ISDN) , 68 V (DDN) 50 V (XDSL) Max. operating current 150mA Protection modes Common and transverse Lines protected 2 wires (RJ11-pin3& 4, RJ45-pin4& 5) 4 wires(RJ11-pin 3& 4, 2& 5, RJ 45-pin 4& 5, 3& 6) Response time < 5 ns Max. surge rating 20A (8/20µs) Max. Data rate 20Mb/s Let through voltage (at 5KV 10/700µs) 220V (PSTN) , 80 V (ISDN) 78V (DDN) , 60V (xDSL) Shunt capacitance < 150pF Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 92/124 Version 2.0 In line resistance 3.9 Ω Standards compliance BS6651-1999, AS1768-2003 IEC61643-21 , ITU(CCITT)1X K17 Connector type RJ 45 or RJ 11 Earth connection Flying lead (single port models) Earth stud (rack-mount models) Enclosure material Anodized aluminum(single port) Galvanized steel alloy (multi-port) Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.12 DATA PORT PROTECTOR:- The SPD for Data Line shall be based on transistor and diode circuitry which ensures a lower let through voltage to protect from the surge and transient overvoltage. Following are the main characteristics of Data Port Protector:- 5.12.1 In case of the Surge current above the Rated capacity it shall fuse and isolate the sensitive equipment. 5.12.2 It shall offer common mode & Transverse mode protection against the Transients appearing between any signal pairs. 5.12.3 The DPP RS232 port protectors shall be compact and in-line design which can be easily connected to the data of the equipments. 5.12.4 The V.35 and the RJ21X data port protectors shall be easily secured onto a standard 35mm Top Hat DIN rail. 5.12.5 It shall have fast response circuit not only to protect the equipments from repeated surges but also to allow the DPP protectors to transparently transmit the data at a speed of up to 20 Mbps. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 93/124 Version 2.0 5.12.6 DPP protector shall offer nearly zero in line resistance and a 40pF capacitance which allows the data to transmit smoothly on the lines. 5.12.7 The important technical features of Data Port Protector are described as below:- Max. operating current 300mA Protection modes Common and transverse Response time 1 ns Max. surge rating 200A (8/20µs) Max. Data rate 20Mb/s Insertion loss <1dB at 20 MHz Capacitance 40pf Standards compliance BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C IEC61643-21, ITU(CCITT)1X K17 CP33-1996 Cat A.B.C, UL497B Connector type DB9 female to male (DPP9) DB25 female to male(DPP25) M/34 female to male(DPP35) RJ21X female to male (DPP50) Earth connection DIN clip (DPP35, DPP50) Flying lead(DPP9), shell(DPP25) Enclosure material Anodized aluminum (DPP35, DPP50) Plastic (DPP9, DPP25) Operating temperature - 40 ºc to 85 ºc Humidity 0 to 95% (R.H) Altitude 0-3650m 5.13 RF COAXIAL PROTECTOR:- RF Coaxial protectors are intended to pass through a desired RF signal with minimum loss or disturbance. To minimize the impact of inserting lightning protectors within the RF circuit, seek out products with the lowest Insertion Loss and lowest VSWR at the frequencies that is intended to operate. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 94/124 Version 2.0 5.13.1Other important main characteristics of RF Coaxial Protector (Fig 5.6) are:- i) Reliable RF performance capability from DC – 3GHz ii) Multi – strike capability iii) Easily replaceable gas discharge tube iv) Bi-directional protection v) AC/DC pass vi) High quality construction vii) Full range of connector type Figure-5.6 5.13.2The coaxial RF protectors shall be a high performance gas discharge tube suppressor capable of wide-band operation from DC up to 3 GHz (N, SMA and D type connector). 5.13.3 The let-through voltage shall be as low as possible and it is capable of handling multi-strike in any lightning intensive environment. 5.13.4 CGR protectors feature easily replaceable gas tube arrester elements, which makes it simple, fast and cost effective in case replacement of the gas tube is required. 5.13.5 Both connector ports of this protector shall be equally protected. This provides protection no matter which way it is installed. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 95/124 Version 2.0 5.13.6 The important technical features of RF Coaxial Protector are described as below:- Frequency range 0-3GHz VSWR < 1.1:1 Return loss > 26dB Insertion loss < 0.2dB Impedance 50 Ω for all models Response time <5ns Peak surge rating 20 kA (8/20µs) DC sparkover voltage 90V+/- 20% (230, 350, 600, 1000V) Max. power 0 – 2000 W Standards compliance ITU(CCITT)1x K17 BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C CP33-1996 Cat A.B.C IEC61643-21/UL497B Body material Brass(Nickel plated) Contact pin Brass(silver/gold plated) Contact socket Beryllium or tin brass(silver/gold plated) Elastic contact Beryllium or tin brass(silver/gold plated) Insulator PTFE O-ring material Silastic Earth connection Via suitable screw ground lug Mounting L shape bracket Operating temperature -4-85ºc Humidity 0-95% (R.H) Altitude 0-3650m IP rating IP 65 Moisture resistance MIL-STD-202 Method 106D Salt fog MIL-STD-202 101D/B Temperature shock MIL-STD-202 107D/A-1 Vibration MIL-STD-202 Method204D/B Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 96/124 Version 2.0 5.14 Telephone Line Protector (Krone Type) The main characteristics of Telephone Line Protector which provides surge protection for telecom and other signalling equipment’s terminated on KRONE connectors are:- 5.14.1 The protector shall be available in various assorted configuration like 1 pair, 10 pair, 50 pair etc in a compact module having multi stage protection. 5.14.2 Full range of voltage to suit any particular applications and the let-through voltage shall be as low as possible. 5.14.3 The series protectors shall be easily pluggable type into the KRONE LSAPLUS disconnection blocks and shall be earthed suitably. 5.14.4 It shall offer both line to line (transverse mode) and line to earth (common mode) protection. 5.14.5 It shall have 20 KA high surge rating and 20 MHz wide bandwidth to provide the best protection and to ensure a smooth data flow in high speed data and signal lines. 5.14.6 It shall be designed in such a way that the surge exceeding the capacity of the primary gas arrester, service should be interrupted by blowing the track fuse and thereby giving a fault condition. 5.14.7 The important technical features of Telephone Line Protector are described as below:- Max. working voltage 7-280V Max. operating current 250Ma Protection modes Common and transverse Protection stages 3 stages Earth leakage current < 5 µA Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 97/124 Version 2.0 Response time <5ns Max. surge rating 20 kA (8/20µs)- KDP 10 5 KA (8/20µs) – KDP 1 Max. data rate 20 Mb/s Insertion loss < 1dB at 20 MHz Let through voltage: (At 5KV 10/700 µs) 10-320 V Capacitance 50 pf In line resistance 3.9Ω Standards compliance ITU(CCITT)1x K17 BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C CP33-1996 Cat A.B.C IEC61643-21 UL497B Earth connection Via earth clips on two ends – KDP 10 Via earth bar – KDP 1 Enclosure material ABS plastic Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.15 Installation notes and Important points in context of installation of Lightning, Surge Protection and Earthing Systems:- 5.15.1 A Connection made up by materials which do not comply with the chemical chain of materials choice like Copper and steel irrespective of their grade is not allowed to be connected with unless separated by appropriate means as stipulated within IEC62305-3. 5.15.2 IEC stipulates that the spark gaps used for single or multiple load be 100 kA at 8/20 µs single rated. Anything above 60 V is deadly for human life. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 98/124 Version 2.0 5.15.3 IEC 62305 regulatory norm permits only one common grounding network. This common grounding network must interconnect or cross mesh all the sub components of the LLZ system like its building, LLZ antenna array, and NF Monitor. Even the grounds of lightning protection system needs to be connected to the common grounding network. All external metal structures must be connected to the ground network. If there is any other equipment installed at the LLZ site, the same must necessarily be given relevant lightning protection not only for the sake of the equipment itself but for the sake of the whole LLZ installation. As an example wiring diagram of a standard electrical shelter installation (typical) of THALES ILS LLZ is shown below: Fig. Wiring Diagram of Electrical Installation (Typical) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 99/124 Version 2.0 5.15.4 Implement lightning protection system compliant to IEC 62305 of Cat I. This does not permit the use of such ionizing devices like the prevectron which promise prevention of lightning and wider coverage. 5.15.5 Lightning protection by systems like “Early Streamer emission”, “Dissipation Array Systems” or “Charge Transfer Systems” are not allowed under standards of US National Fire Protection Association (NFPA), IEC, IEEE, Underwriters Laboratories (UL), US Military etc. 5.15.6 The power cable shielding must be connected to a common ground point. 5.15.7 The mains in-leading and out-leading armoured power cable must have its shield grounded with its PEN conductor to one common ground bus bar. The grounding must be done within 20 cm of the cable entry/exit point to/from the building. 5.15.8 The mechanical shield of each RF cable entering or leaving the building must be bonded to the ground at the point where it enters/leaves the building, but not more than 20 cm inside the building. Preferably it should be done outside the building. 5.15.9 The COM cable used for data communication should have its mechanical armouring and inner static shield connected to ground only at one end, say the TWR side and not at both ends. Connecting to ground at both ends is likely to induce strong equalizing ground current between different potentials of such far away buildings, which may reach values above 100 A under worst condition. The other end, both the armour as well as the shield should be grounded through a spark gap to the nearest common ground. The spark gap should be IEC 62305 compliant with low spark over voltage level (< 70 V AC) and high current rating values of 75 kA at 8/320 µs or more. 5.15.10 The IEC 62305 stipulates that there is only one common ground connecting all potentials to one, as well as the PEN, the power cable shield, the COM cable shield, any internal PE and grounds of SPDs, any RF cable shields and others like external Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 100/124 Version 2.0 groundings and lightning protection inclusive of the subsystems e.g. LLZ antenna, NFM etc. 5.15.11 RF cables entering the shelter must have in line surge arrestors. 5.15.12 The PE wire/conductor of a power cable is not a ground connection. The ground connection for static issues must use a connecting wire of cross sectional area 16 mm2 or more and use the shortest path to the near most ground. 5.15.13 All multi strand wire must use cable end sleeves and cable end lugs to enable proper installation and also to reduce chemical chain involved in corrosion. Any flat tape or round wire / cable connections must utilise termination clamps or brackets. 5.15.14 The cable routing of various voltage circuit must be separated, for e.g. the RF, the AC, the DC and the GND and static shields of all the cables must be grounded at point of entry into the building. 5.15.15 All shielded cable like RF, COM, armoured PWR line etc. should be connected to common potential ground at every 20 m along its external path. Same is to be done at every 2.5 m when internally laid. 5.15.16 Common ground network for a DVOR must be connected, DVOR building, Counterpoise steel structure, Counterpoise mesh, power cable shielding, power cable PEN wire, COM cable shield via spark gap, ground connection to SPD related to PWR, COM or RF cabling, Lightning protector rods, DVOR monitor mast/antenna, and other metallic objects of the system. 5.15.17 Copper can be bonded to galvanized steel via special bimetal media or stainless steel media of V4A grade. 5.15.18 PE: Protective earth; PEN: Combined protective earth and neutral; N: Neutral must all be connected to a common bus bar. Electrical conductors entering a Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 101/124 Version 2.0 structure should be metal cased. This metal casing should be electrically continuous within the structure; it should be earthed at the point of entry inside the structure on the user’s side of the service and bonded directly to the lightning protective system. 5.15.19 Where the electrical conductors are connected to an overhead electricity supply line, a 15m length of buried armoured cable should be inserted between the overhead line and the point of entry to the structure. 5.15.20 The overhead supply lines are liable to have large surges induced in them from lightning discharges. Hence is, therefore, needed where they join the buried cable. This will allow a large part of the lightning current to be discharged to earth at a safe distance, which is determined by the rolling sphere’s radius, from the structure. 5.15.21 Surge suppressors should be installed with minimum lead lengths to their respective panels. Under fast rise time conditions, cable inductance becomes important and high transient voltages can be developed across long leads. 5.15.22 In all instances, use high quality, high speed self diagnosing protective components. 5.15.23 Proper ground must be ensured. Earth resistance to be strived to achieved to be as low as possible preferably less than 5 Ω. 5.15.24 Do not install suppressor, if neutral to ground bond is not present. 5.15.25 If neutral to ground voltage is greater than 2 V AC, the electrical system is faulty and needs to be rectified. 5.16 Surge protection for typical DSCN System 5.16.1 A surge protector (or surge suppressor) device is used to protect linkway modem and RF components of DSCN system from lightning spikes and surges. A surge protector removes the lightning spikes induced in the RF cable through earth conduction. Moreover, Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 102/124 Version 2.0 power supply strips installed at DSCN system and RF component ends shall have built in surge protectors. A surge protection device shall also be mounted on a circuit breaker panel of UPS output. Figure below shows power strip with built in surge protector. 5.16.2 RF Connector Type of Surge Protector to be installed in DSCN System: 1. The surge protector of impedance 75Ω shall have F type female and F type male ends for connecting F type male to linkway2100 modem’s RX port and F type female to RF cable. 2. The surge protector of impedance 50Ω shall have N type female and N type male ends for connecting N type male to Linkway 2100 modem’s TX port and N type female to RF cable. 3. The surge protector shall have F type female and F type male ends for connecting F type male to linkway S2 modem’s TX and RX ports and F type female to RF cable. The impedance of surge protector shall be 75Ω for RX path and 50 Ω for TX path. 4. The surge protector of impedance 50Ω shall have N type female and N type male ends for connecting N type male to BUC’s TX port and N type female to RF cable. 5. The surge protector of impedance 75Ω shall have N type female and N type male ends for connecting N type male to LNB RX’s port and N type female to RF cable. Note: Most of LNB consist of N type port but a few LNBs are of F type. Stations may check before procurement. 5.16.3 Connection Diagram of Surge Protector (SPD) for DSCN System: Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 103/124 Version 2.0 5.16.4 Specification of typical Coaxial Cable Surge Protector used in DSCN system Proposed model is 90V DC. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 104/124 Version 2.0 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 105/124 Version 2.0 NOTE: * Surge protector shall have rating of ‘DC Breakdown voltage’ of 90 Volt. # If 75 Ohm Surge protector is not available than 50 Ohm may be used with same voltage rating as above and LMR 400- 50 Ohm coaxial cable should be used instead of LMR 400-75 Ohm for Rx path. 5.16.5 Connection of Surge Protector Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 106/124 Version 2.0 5.17 Coaxial Connector Seal 5.17.1 Sealing Concepts for Coaxial Connectors: The electrical connecting points in coaxial connectors must be protected against ambient influences. Dust, water and moisture are a constant hazard especially in outdoor applications. Moisture particularly, which penetrates a coaxial system, changes the RF transmission enormously and leads to impedances or poor return loss values. Seals must be fitted at all connecting points to protect the sensitive and expensive electronics. Fig: Sealing Tape 5.17.2 Coax Seal Moisture Proof Sealing Tape 1/2" x 60". Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 107/124 Version 2.0 Coax-Seal is a special material that will quickly and effectively seal all types of coaxial fittings of any shape from moisture, water and corrosion. Coax-Seal stays flexible for years thus insuring moisture proof connections. It ensures good SWR and long coax life. CoaxSeal also allows you to disconnect and reconnect fittings with the same material by simply re-forming the plastic. Coax-Seal is the only material that will adhere to vinyl and poly vinyl connector’s outer covers. Coax-Seal is non-toxic, non-corrosive, non-conducting and stays flexible at any temperature. 5.17.3 Specifications of Self-Fusing Silicon tape/Silicon Rubber Tape: 1. Self-Bonding Silicone 2. Color: Black/oxide-red/Gray 3. Thickness: 30 mil 4. Width: 1.5 inches 5. Length: 15 feet 6. Operating Temperature Range: -30C to +70C 7. Tensile Strength: 700 PSI Minimum 8. Ultimate Elongation: 300% Minimum 9. Tear Resistance: 85 psi 10. Configuration: Rectangular shape Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 108/124 Version 2.0 Fig: Self-fusing Silicone tape ---------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 109/124 Version 2.0 Chapter - 6 Measurement of Earth Resistance 6.1 Measurement of Earth Resistivity:- 6.1.1 Need for the measurement of Resistivity:- The resistivity of the soil varies within extremely wide limits, between 1 and 10, 000 Ω-meters. The resistivity of the soil is found to be non-uniform at many station sites. To design the most economical and technically sound grounding system for large installations, it is necessary to obtain accurate data on soil resistivity and on its variation. Resistivity measurements at the site help in designing a good earthing system. The resistivity of the earth varies over a wide range depending on its moisture content. It is therefore, advisable to conduct earth resistivity tests during the dry season in order to get conservative results. 6.1.2 Test Locations:- In the evaluation of the earth resistivity of, at least eight test directions should be chosen from the centre to cover the whole site. This number shall be increased for very large station sites and for sites where, the test results obtained at various locations show a significant difference, indicating variations in soil formation. In case of transmission lines, the measurements shall be taken along the direction of the line throughout the length approximately once in every 4 kilometers. 6.2 Principle of Tests:- 6.2.1 Wenner’s four electrode method is recommended for these types of field investigations. In this method, four electrodes are driven into the earth along a straight line at equal intervals. A current I is passed through the two outer electrodes and the earth as shown in figure below and the voltage difference V observed between the two inner electrodes. The current I flowing into the earth produces an electric field proportional to its density and to the resistivity of the soil. The voltage V measured Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 110/124 Version 2.0 between the inner electrodes is, therefore, proportional to the field. Consequently, the resistivity will be proportional to the ratio of the voltage to current. If the depth of burial of the electrodes in the ground is negligible compared to the spacing between the electrodes, then:- ρ = 2π SV / I Earth testers normally used for these tests comprise the current source and meter in a single instrument and directly read the resistance. The most frequently used earth tester is the four –terminal Megger shown in Fig 1. When using such a Megger, the resistivity may be evaluated from the modified equation as given below. ρ = 2π x SR Where ρ = resistivity in ohm – meters S = distance between successive electrode in meters R = Megger reading in ohms. C1, C2 Current Electrodes P1, P2 Potential Electrodes Fig. 6.1 Measurement of Earth Resistivity ---------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 111/124 Version 2.0 Chapter -7 Supply, Installation, Testing and Commissioning [SITC] of Lightning, Surge Protection and Earthing System of CNS Facilities as part of Turnkey Project. 7.1When Lightning, Surge Protection and Earthing System of CNS Facilities are being procured under SITC as a part of turnkey project, General Technical specifications of the Tender Document in such cases should clearly specify following:- The vendor/supplier/system integrator shall be responsible for complete Supply, Installation, Testing and Commissioning of the Lightning, Surge Protection and Earthing System of the facility. The vendor/supplier/system integrator shall design and provide a comprehensive Lightning, Surge Protection and Earthing System which shall meet the following National and International Standards:- IS-2309 Code of protection for Lightning Protection IS -3043 Code of practice for earthing IS -5216 Safety procedures & practice in electrical work IEC -62305 Protection against Lightning IEC -61643 Low Voltage Surge Protective Devices IEC -60364 Low Voltage electric Installation: ANSI/UL 467 Grounding & Bonding Equipment 7.2 The lightning & Surge Protection System provided shall be a comprehensive system i.e. it should include:- 7.2.1Power Supply Surge Protection System at the input of Equipment room where the facility is proposed to be installed and each distribution board which will supply power to the equipment and its accessories. 7.2.2Surge Protection system should be provided to all incoming and outgoing cables connected to system such as Data lines [Telephone, OFC, RC cables etc] and RF Cables etc. Standard bonding of cable shields/trays to ground at building entry/exit points must be ensured. 7.2.3Air Terminals/Lightning Rods should be positioned to give full coverage of structure [Building, Antenna, Mast etc.] against the lightning. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 112/124 Version 2.0 7.2.4 Earthing system shall meet the following requirements: 7.2.4.1 Provide safety to equipment from power line faults, lightning and surges. 7.2.4.2 Provide a common reference ground plane for electronic equipment which will minimize electronic system noise and electromagnetic interference (EMI). 7.2.4.3 The grounding system design shall be based on single grounding network with multiple earths. 7.2.5 Appropriate references should be made to the guidelines provided in the manual in this regard. 7.2.6 If only a part of Lightning, Surge Protection and Earthing System e.g. only surge protection system is to be supplied by vendor then also appropriate references should be made to standards in this regard in the tender document. 7.3 Any other specific requirement for Lightning, Surge protection and earthing system specific to the equipment being procured should also be clearly specified in the Tender Document. 7.4 Lightning, Surge Protection and Earthing System of CNS facility shall form a part of Factory Acceptance Test (FAT) and Site Acceptance Test (SAT). 7.5 The complete layout of the Lightning, Surge Protection and Earthing System of CNS facility shall be submitted by the vendor/supplier/system integrator before commissioning. ---------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 113/124 Version 2.0 Chapter -8 Maintenance Procedures of Lightning, Surge Protection and Earthing Systems 8.1Responsibility of Maintenance Maintenance of Earthing, Lightning and Surge Protection System for the CNS installations installed in Terminal Building and/or Technical Block and located inside operational area and around airport (Radar, LLZ, GP, DVOR, OM/MM and NDB etc. ) shall be looked after by the CNS personnel. 8.2 Testing:- 8.2.1 On the completion of the installation, or any modification to it, the following measurements should be made and the results recorded in a lightning protective system logbook: i) The resistance to earth of the whole installation and of each earth termination. ii)The electrical continuity of all conductors, bonds and joints. 8.2.2 If the resistance to earth of a lightning protective system exceeds 5Ω, the value should be reduced. If the resistance is less than 5Ω, but significantly higher than the previous reading, the cause should be investigated and any necessary remedial action should be taken. 8.2.3 Tests should be repeated at fixed intervals, preferably not exceeding 06 months. 8.2.4 It is emphasized that before isolating a lighting protection earth, it should be tested to ensure that it is not “live”, using a sensitive voltage device. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 114/124 Version 2.0 8.3 System Inspection:- 8.3.1 All lightning protective systems should be visually inspected by a competent person during installation, after completion and after alteration or extension, in order to verify that they are in accordance with the recommendations in this code. 8.3.2 Visual inspections should be repeated at fixed intervals, preferably not exceeding 03 months. 8.3.3 In addition, the mechanical condition of all conductors, bonds, joints, and earth electrodes (including reference electrodes) should be checked and the observations noted. 8.3.4 If, for any reason, such as other site works, it is temporarily not possible to inspect certain parts of the installation, this also should be noted. 8.4 Total System Maintenance 8.4.1 Of particular importance is the regular detailed examination of the complete LPS for any evidence of corrosion. If this check is not carried out then vital components within the LPS, which may have suffered from corrosion and which could exhibit a high resistance could be missed. This will have a detrimental effect on the whole system making it an unattractive high impedance path for the lightning current to follow. 8.4.2 The earth resistance for all the electrodes must be measured periodically to ensure their usability. 8.4.3 The resistance of the air terminals to the earth electrode should also be measured periodically. 8.4.4 Maintenance Checks For Lightning Protection System Following checks should be carried out at regular interval – once every 06 months: Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 115/124 Version 2.0 8.4.4.1 Inspection of Air Terminal Physical inspection of air terminal and functionality checks with air terminal test meter. 8.4.4.2 Inspection of Down-conductors Check for corrosion Continuity testing by continuity tester, across all types of conductors in lightning protection and grounding system. The resistance should be strived to be as less as possible preferably less than 5.0 ohm. The down conductors are routed, located and electrically bonded as required. 8.4.5 Periodic Check for Earthing System: Earth resistance will be checked at the interval of 6 months with the standard process of measurement (Three point method) and recorded. If the measured value is beyond specified standards, corrective action must be taken. Earth termination systems are interconnected. Where a conductor is totally hidden, its electrical continuity should be tested. In case specified standards of earth resistance are not met, ground conductivity may be improved by Refilling of earth pit with electrolytic compound for electrolytic grounding system where provided. Recharging of earth pits in case conventional grounding system is installed. Physical inspection of connection between ground rod and down conductor near grounding system for corrosion, bad contacts followed by corrective action. 8.4.6 Inspection of Surge Protection devices: All surge protection devices should be checked at an interval of 3 months for their functionality. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 116/124 Version 2.0 Indications provided with surge protection system should be monitored and recorded on daily basis. Faulty devices should be replaced. 8.4.7 Earthing System Inspection Chambers Inspection Chambers of each earthing system should be maintained properly. Grass and other wild growth should be regularly cleared around inspection chamber. Whenever grading or other civil works takes around these chambers, they should be protected properly and should not be allowed to be lost during such works. 8.5 Special Total System Inspection: In the event of occurrence of major lightning strike around the Terminal building and other CNS facility as observed or monitored on the strike record counter, all the aforesaid inspection should be carried out and if need be, the corrective measures to be taken immediately so that LPS is maintained in its optimal effectiveness. 8.6 Inspection Regarding Modifications / Repairs of the Protected Structures While carrying out the periodic maintenance particular attention should be paid, besides earthing and corrosion, to alteration or extensions to the structure that may affect the LPS. Examples of such alterations or extensions are:- a) Change in the use of building; b) Installation of fuel oil storage tank near to building; c) Erection of radio aerials; and d) Installation or alteration to electrical, telecommunications or computing Facilities within or closely connected to the building. 8.7 Records The following records should be kept on site, or by the person responsible for the upkeep of the installation:- a) Scale drawings showing the nature, dimensions and position of all components and Parts of the LPS. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 117/124 Version 2.0 b) The nature of the soil and any special earthing arrangements. c) Date and particulars of salting, if used. d) Test conditions, date and results. e) Alterations, additions or repairs to the system. f) The name and contact details of the person/s responsible for the installation or its upkeep. 8.8 Maintenance Schedules A coordinated programs of inspection and maintenance of the lightning and surge protection systems have been designed in the form of preventive maintenance schedules as given below to ensure its serviceability. 1. Weekly Preventive Maintenance 2. Monthly Preventive Maintenance 3. Inspection after Lightning 4. Pre Monsoon/Pre Winter Maintenance. 8.8.1 Weekly Preventive Maintenance Schedule Visual Inspection (Corrosion, loose connection, dry solder) Surge Protective Devices Status Remarks Air Terminal Down Conductors Connectors of Earth Pit Air terminal & Down conductor Down conductor & Earth Electrode Self diagnostic type of Surge protectors. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 118/124 Version 2.0 8.8.2 Monthly Preventive Maintenance Schedule Surge Protective Devices Status (Resistance of GDT element should be very high) Earth Resistance Value observed Earth Resistance Value of site at the time of Installation Tightness of Connectors of Visual Inspection as given in table at 8.8.1 Air Remarks terminal & Down Conductor Down Conductor & Earth Electrode 8.8.3 Inspection after Lightning Status of surge protector(Resistance of GDT element) Visual Inspection as as given in table 8.8.1 Earth Air Resistance Remarks Terminal & its Connection Down Conductor & its Connection Earth Pit Rx path Tx path Power strip Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 119/124 Version 2.0 8.8.4 Pre Monsoon/Pre Winter Maintenance Earth Resistance Loop Resistance of Air terminal & Down conductor Tightness of Connectors of Greasing of Connectors of Visual inspection As given in table 8.8.1 Equipotential Bonding status Value at Installation Value observed Value at Installation Value observed Air terminal & Down conductor Down conductor & Earth electrode Air terminal & Down conductor Down conductor & Earth electrode Air terminals Down conductor ------------------------------------------------ Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 120/124 Version 2.0 Chapter -9 DEFINITIONS and ACRONYMS 9.1 DEFINITIONS In this Manual, the following definitions shall apply.- 9.1.1 Lightning Flash: Electrical discharge of atmospheric origin between cloud and earth comprising one or more impulse of many kilo amps 9.1.2 Lightning Strokes: The single distinguishable current impulse of a flash. 9.1.3 Lightning Protective System: The whole system of conductors used to protect a structure from the effects of lightning. 9.1.4 Air Termination (Air Termination Network):That part of a lightning protective system which is intended to intercept lightning discharges. 9.1.5 Down Conductor: Conductor that connects an air termination with an earth termination. 9.1.6 Bond: A conductor intended to provide electrical connection between the lightning protective system and other metalwork and between various portions of the latter. 9.1.7 Joint: A mechanical and/or electrical junction between two or more portions of a lightning protective system. 9.1.8 Testing Joint: Joints designed and situated so as to enable resistance or continuity measurements to be made. 9.1.9 Earth Termination (Earth Termination Network) :That part of a lightning protective system which is intended to discharge lightning currents into the general mass of the earth. All points below the lowest testing point in a down conductor are included in this term. 9.1.10 Earth Electrode: That part of the earth termination making direct electrical contact with earth. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 121/124 Version 2.0 9.1.11 Ring Conductor: Earth termination or electrode fixed to a structure above or below the earth or within or under foundations. A ring conductor may be used alone as an earth termination network or in conjunction with metal rods as an interconnection conductor. 9.1.12 Indicating Plate: A plate detailing the number and position of earth electrodes. 9.1.13 Reference Earth Electrode:An earth electrode capable of being completely isolated from an earth termination network for use in periodic testing. 9.1.14 Log Book:A record of tests and inspections of a lightning conductor installation. 9.2 Acronyms A : Ampere ASR : Airport Surveillance Radar ARSR : Air route Surveillance Radar ANSI : American National Standard Institute ATM system : Air Traffic Management System BS : British standards BIS : Bureau of Indian Standards cm : centimeter CNS : Communication Navigation Surveillance CNS-OM : CNS –Operation & Maintenance Deg. : Degree dia : Diameter DME : Distance Measuring Equipment ES : Earthing System EES : Earth Electrode System IS : Indian Standards (Bureau of India Standards) IEC : International Electro technical Commission IEEE : Institute of Electrical and Electronics Engineers LA : Lightning Arrestor Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 122/124 Version 2.0 LLZ : Localizer LPS : Lightning Protection System Ft : Feet GP : Glide Path kA : Kilo Ampere kmph : Kilometer per hour kV : Kilo volt M(m) : Meter mm : millimeter ms : mill second MIL –STD : Military Standard EEB :Equi-potential Earth Bus bar MEEB :Main Equi-potential Earth Bus bar NDB : Non Direction Beacon NF : Near Field NFPA : National Fire Protection Association MV : Mega Volt RF : Radio Frequency SMR : Surface Movement Radar UL : Underwriters Lab. V : Volt VLSI : Very Large Scale Integrated Circuit ---------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 123/124 Version 2.0 ******End of CNS Vol. V Ver. 2.0 *****"> 1G Ω Humidity 0-95% (R.H) Operating temperature -40 to +80 deg C. 3.20.8For more details regarding equipotential protector, Ref Annexure-2 – IEC 62305- 3 Standard. 3.21 Lightning Protection System(LPS) –Earth termination network, types and specifications:- 3.21.1 An earth electrode should be connected to each down conductor of LPS. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 50/124 Version 2.0 3.21.2 Each of these earths should have a resistance not exceeding the product given by 10Ω multiplied by the number of earth electrodes to be provided. For example, for a system with 15 down conductors, the individual earth reading should not be more than 10x15=150Ω. The whole lightning protective system, including any ring earth, should have a combined resistance to earth not exceeding 10Ω without taking account of any bonding. 3.21.3 A reduction of the resistance to earth to a value below 10Ω hasthe advantage of further reducing the potential gradient around the earth electrode when discharging lightning current. It also further reduces the risk of side flashing to metal in or on a structure. Hence every effort shall be made to ensure as much low ground resistance as possible. 3.21.4 The Earthing shall be provided/ made as per specifications given for Earthing System in the manual. ---------------------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 51/124 Version 2.0 Chapter - 4 Earthing Systems 4.1 Earthing:- Lightning, Surges or Unintentional contact between an energized electric conductor and the metal frame or structure that encloses it or an insulation failure in electrical equipment’s etc., can cause dangerously high voltages in the electrical distribution system. Under such circumstances, grounding provides an alternative low impedance path and thereby minimizes damages. A good and an efficient earth ensure that all parts of apparatus other than live parts shall be at earth potential that is zero at all the time. The scope of this section shall cover the following:- a) Earthing electrode/station b) Earthing conductors c) Earthing of equipment and installation The earthing resistance depends on:- a) Resistance of electrode b) Contact resistance between electrode and soil c) Resistance of soil between electrode surface and infinite earth. Resistance of electrode and contact resistance between electrode and soil are very small fraction of an ohm. Approximately 90 % of an earth resistance lies within 2 m between electrode and earth. Moreover, Earth conductivity is essentially electrolytic in nature and is affected by moisture content of soil, its chemical composition and concentration of salt dissolved in the contained water. It is also dependent on grain size and closeness in packing. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 52/124 Version 2.0 4.2 Selection of Earth Pit Site:- Following is the order of preference for selecting an earth pit position. Wet marshy ground Clay/loamy soil with little sand Clay/loamy soil with sand, gravel and stones Damp and wet sand 4.3 Scope: This specification of earthing system describes in detail, the components to be used and the procedure for constructing the earth system. The main purpose of this is to maintain consistent low earth resistance value over the years without contaminating the Ground water. 4.4 Components: The Earthing system shall consist of Earth Rods / plates and conductive and eco-friendly backfill compound, Earth termination clamps and Earth Bus Bar to facilitate connections to the equipment. The type earth electrode shall be any of the following, as specified:- (a) Pipe / rod earth electrode ; (as per IS 3043) (b) Plate earth electrode; (as per IS 3043) 4.5 Methods of Implementations:- The earthing can be implemented in four ways depending on the requirements, site and ground conditions:- 4.5.1 Conventional earthing using copper plates as per IS 3043:- 4.5.1.1 Earth Pit of the Size of 1 meter diameter and 3 meter depth shall be excavated, after depth of 3 meter the size of excavation shall be 900X300X900mm depth. 4.5.1.2 Plate Electrodes shall be in vertical position. 4.5.1.3PVC pipe for Watering shall be used of 40mm Diameter, length of 3m ( contain hole of 12mm Diameter in Zigzag manner starting from 15cm away from bottom to 2 meter height ). 4.5.1.4 At bottom 150mm layer of salt and charcoal power shall be installed, then Plate shall be installed. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 53/124 Version 2.0 4.5.1.5 Min 120 Kg each of charcoal powder and salt shall be used for each earthing pit. 4.5.1.6 The plate/pipe electrode, as far as practicable, shall be buried below permanent moisture level but in no case less than 2.5 meter below finished ground level. 4.5.1.7 600 mm × 600 mm × 3.15 mm copper plate buried at a depth of 8 ft in vertical position with the pit filled with alternate layers of charcoal and salt up to 4 ft from bottom. 4.5.1.8 The copper plates shall be connected to earth strip by riveting and brazing at no less than two points and the joints shall be protected by heavy coat of bitumen. 4.5.1.9 Schematic diagram for copper plate earthing is shown in Figure 4.1. Figure- 4.1 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 54/124 Version 2.0 4.5.2 Earthing rods directly driven into the earth :- 4.5.2.1 The length of the electrode shall be either 1.22meter or 2meter or 3meter based on the application. 4.5.2.2 Electrodes used for neutral earthing and lightning protection earthing shall be at least 3 meter long and for other applications, electrodes of at least 1.22meter or 2meter length may be used. 4.5.2.3 Earthing System is depicted in Fig 4.2(a) and 4.2(b) below:- Figure-4.2(a) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 55/124 Version 2.0 Figure-4.2(b) 4.5.2.4The combined earth rod length of a system should be not less than 9 meter whilst each individual earth rod should be not less than 1.5 meter in length. Figure-4.3 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 56/124 Version 2.0 4.5.3 Chemical earthing:- 4.5.3.1 A copper plate or copper coated rod, conventional earthing system should be used as a rule. In general salt and charcoal is used as backfill material for conventional earthing pits and these are eco-friendly. 4.5.3.2 In extreme conditions of rocky or sandy or dry condition where it is difficult to achieve the desired performance of earthing terminals by conventional system, chemical earthing may be employed. 4.5.3.3 The backfill material used in chemical earthing systems for soil treatment shall be highly conductive and should be certified as non-polluting and safe for use near potable ground water systems. 4.5.3.4 The ground conductivity enhancing backfill Material shall be a compound having a low resistance in the range of 0.12 ohm/Meter as specified in IEEE 80 (5 % of the Resistivity of Bentonite), non-corrosive highly conductive powdered material that improves grounding effectiveness, especially in areas of high soil resistivity such as rocky and sandy areas. 4.5.3.5 This material shall be suitable to be installed in either slurry or dry form. The backfill material shall confirm to the following specifications: Shall be highly electrically conductive and non-soluble. Shall not leach into ground. Shall be electronically conductive (like in metals) and shall not depend on moisture / salt for conduction Shall have a resistivity of less than 0.12 ohm/meter Shall be compatible with all copper grounding systems Shall contain a corrosion inhibitor to mitigate corrosion of copper Shall not contain hazardous chemicals Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 57/124 Version 2.0 Shall be certified to ANSI / NSF standard 60 as safe for use near potable ground water resources Shall not be affected by drought and shall be stable between -10˚ to +50˚C temperature. Shall be suitable for any kind of soil Where, the water table is high or runoff water is foreseen, the backfill compound shall solidify as specified in BS: 7430.The compound shall set like concrete to prevent erosion over a period of time. However under such condition only conventional earthing system should be used. NOTE:-Ref - BS7430 & IEEE80 where use of Carbon backfill compound for obtaining low resistance and maintenance free earthing is clearly recommended under specific conditions. 4.5.4 Horizontal / Lateral Earthing:- Whenever it is not possible to excavate to a depth where the vertical earth electrodes can be installed, the Lateral / Horizontal earthing method shall be adopted as follows:- 4.5.4.1 Three pits of 350 x 150 mm shall be dug to a depth of 3 feet and at a distance of at least 2meter from each other. 4.5.4.2 They can be laid either in a straight line formation or a triangular formation depending on the space availability at site. 4.5.4.3 One copper bonded steel plate of 300 mm× 300 mm× 3 mm shall be placed in each of the earth pits. 4.5.4.4 The earth pits shall be filled with the highly conductive and ecofriendly backfill material up to 6 inches above the top of the plate. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 58/124 Version 2.0 4.5.4.5 These plates shall be interconnected using copper flat / strip of at least 50 sq. mm cross sectional area. Such flat / strip shall be installed in a trench of 100 mm width at a depth of 600 mm (0.6m) from the ground level. 4.5.4.6 The entire trench shall be filled with the highly conductive and eco-friendly backfill material in such a way that there is a minimum of 2 inches of compound on the top and bottom of the interconnecting strip. 4.5 Earth Electrode Specifications:- 4.5.1 The electrodes shall be preferably in one piece of the desired length. 4.5.2 The electrode shall be a solid steel rod made of high tensile low carbon steel and coated with molecularly bonded electrolytic copper on the outside (as per UL 467 or equivalent) . The Earth electrode shall conform to the following specifications : Steel core: 600 MPa The thickness of the copper coating shall be at least 250 microns. Copper jacket should not crack on bending of earth rod Copper: 99.9% pure electrolytic copper Copper Structure: Very fine grain structure and highly ductile Copper Bonding: Fully bonded with steel core Nominal Diameter over Copper: 14.5mm Threads: Rolled into copper M16x2 The electrode diameter shall be 14.2 mmdia . Ends: Chamfer and Pointed (2mm and 6mm x 45deg) The electrode should be able to carry a minimum short time current of 15 kA for one second. Couplers should be made of brass Clamps should be made of brass or stainless steel Driving head or striker head should be of High tensile steel Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 59/124 Version 2.0 Driving tip should be of mild steel The earth electrode shall carry standards marking and manufacturer’s name. Clamps and fixtures should be used in the earthing system to ensure perfect and reliable contact. 4.5.3 Earth rod and accessories are depicted in Figure 4.4 below:- Figure-4.4 NOTE: - Ref – IS-3043 & IEC-60364 where use of such electrodes are permitted & the disadvantage of using plate electrodes are highlighted Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 60/124 Version 2.0 4.6 Soil Treatment:- Approximately 90 % of resistance between electrode and earth lies within a radius of 2m from the electrode. So, for soil treatment, to reduce the earth resistance, a shallow basin, 0.5m around the top of the electrode, half a metre in radius is excavated. This basin is then applied with artificial agents like NaCl, CaCl2, Na2CO3, CuSO4, salt, soft coke, charcoal in suitable proportion. Then the basin is filled several times with water for allowing it to percolate into the ground. 4.7 Earthing System Inspection Chamber:- 4.7.1 A 300X300X300 mm (inside dimension) concrete box with smooth cement plaster finish shall be provided on the top of the pit. A concrete lid, painted black, approx. 50 mm. thick with pulling hooks, shall be provided to cover the earth pit. 4.7.2 Care shall be taken regarding level of the floor surrounding the earth so that the connector is not too deep in the masonry or projecting out of it. 4.7.3 On backside of the cover, date of the testing and average resistance value shall be written with yellow paint on black background. 4.7.4 Alternatively prefabricated earthing inspection chambers may also be used. These have precise dimension and better service life. They are convenient to install and require low maintenance. A Polymer or CI cover shall be provided on the top of the earth system. The prefabricated Earthing inspection chamber should be light weight and suitable for extreme weather conditions. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 61/124 Version 2.0 4.7.5Care shall be taken regarding Care shall be taken regarding level of the floor surrounding the earth so that the connector is not too deep in the masonry or projecting out of it. 4.7.6 Grounding test terminal box shall be installed at an appropriate location suitable for testing the earth resistance. 4.7.7 Typical Inspection Chamber is shown in Figure 4.5 below:- Figure 4.5- Inspection Chamber 4.8 Earthing Conductor: - 4.8.1The earth conductors shall be fixed to the wall/columns etc., at every 500mm with 10mm spacers. The total earthing system shall be mechanically and electrically connected to provide independent path to earth. 4.8.2If the conductor is protected from corrosion, the area of cross section for copper conductor shall be more than 16 mm2 . Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 62/124 Version 2.0 4.8.3If the conductor is not protected from corrosion, the area of cross section for copper conductor shall be more than 25 mm2 . 4.9 Earth Resistance: The earth resistance of combined earth system (to be measured at EEB) shall be less than or equal to 1 ohm, as per the requirement. It shall be measured by an approved earth testing apparatus for individual earth pits. The procedure for measuring earth resistance is given in Chapter- 6. 4.10 Equipotential Earth Bus bar and its connection to equipment’s & Surge protection devices in the Equipment room: - 4.10.1 Equipotential earth bus bars 4.10.1.1There shall be one Equipotential earth bus bar for each of the equipment room. The Equipotential earth bus bars located in individual equipment rooms shall be termed as Sub Equipotential bus bars (SEEB). The Equipotential earth bus bar connected to Class ‘B’ SPDs and the main earth pit shall be termed as Main Equipotential earth bus bar (MEEB). 4.10.1.2The EEBs shall have pre-drilled holes of suitable size for termination of bonding conductors. The EEBs shall be insulated from the building walls. Each EEB shall be installed on the wall with low voltage insulator spacers of height 60mm. The insulators used shall have suitable insulating and fire resistant properties for this application. The EEBs shall be installed at the height of 0.5m from the room floor surface for ease of installation & maintenance. All terminations on the EEBs shall be by using copper lugs with spring washers. 4.10.2 Bonding Connections:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 63/124 Version 2.0 4.10.2.1 To minimize the effect of circulating earth loops and to provide equi-potential bonding, “star type” bonding connection is required. As such, each of the SEEBs installed in the rooms shall be directly connected to MEEB using bonding conductors. Also, equipment/racks in the room shall be directly connected to its SEEB. The bonding conductors shall be bonded to their respective lugs by welding. 4.10.2.2All connections i.e. routing of bonding conductors from equipment’s to SEEB & from SEEBs to MEEB shall be as short and as direct as possible with min. bends and separated from other wiring. However, connection from SPD to MEEB shall be as short as possible and preferably without any bend. 4.10.2.3Materials and dimensions of bonding components for connection of individual equipment’s with Equipotential bus bar and earth electrode shall be as given below:- Component /Bonding Material Size Main Equipotential earth busbar (MEEB) Copper 300X25X6 mm (min.) Sub Equipotential earth busbar (SEEB) Copper 150X25X6 mm (min.) Individual equipment’s to SEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 10 sq.mm SEEB to MEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 16 sq.mm Surge protection devices (SPD) to MEEB using copper lugs with stainless steel nut and bolts. Multi-strand single core PVC insulated copper cable as per IS:694 16sq.mm Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 64/124 Version 2.0 MEEB to main earth electrode. Multi-strand single core PVC insulated copper cable as per IS:694 (Duplicated) 35sq.mm Main earth pit to other earth pit in case of loop earth Copper tape 25X2 mm 4.11 Markings for Earthing systems:- 4.11.1 Earth bars and terminals at all switch boards shall be marked permanently as “E”. 4.11.2 Main earth terminal shall be marked safety earth – “DO NOT DISCONNECT”. 4.11.3 All earth pits shall be identified properly i.e. by suitable nomenclature identifying earth pit with the facility, Earth pit no etc. 4.12 Earthing System Requirement for CNS facilities:- 4.12.1 The electronic ground conductor shall be PVC insulated standard copper wire of 22 mm² or larger. One such conductor shall run from each equipment area or grouping of related electronic equipment and be terminated at the grounding test terminal box. Electronic ground conductors shall not be interconnected except at the common point. 4.12.2 Each cabinet and isolated item of electronic equipment shall be individually connected to the electronic ground conductor by the shortest possible route. The connecting jumper wire shall be 8 mm² or the size of the power feeder to the electronic equipment cabinet, whichever is larger. In addition, cabinets which are installed sideby-side shall be bonded together by copper wire jumpers, of 8 mm² or larger. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 65/124 Version 2.0 4.12.3 Care shall be taken to assure that ground loops are not created inadvertently. 4.13 COMMUNICATIONS CABLE TRAY SYSTEMS:- 4.13.1 Bond the metallic structures of one cable tray in each tray run following the same path to provide 100 percent electrical continuity throughout this cable tray systems as follows:- 4.13.1.1 Splice plates provided by the cable tray manufacturer can be used for providing a ground bonding connection between cable tray sections when the resistance across a bolted connection is 10 milliohms or less. 4.13.1.2 Install a standard (16 mm²) bonding jumper across each cable tray splice or junction where splice plates cannot be used. 4.13.1.3 When cable tray terminations to cable rack, install standard 16 mm² (bonding jumper between cable tray and cable rank pan. 4.14 Important points regarding Earthing System 4.14.1 Minimum dimensions for earth terminations are as follows:- Component Dia in mm Area mm 2 Copper clad or galvanized steel rods. For Copper clad steel rods, the core should be of low carbon steel of tensile strength700N/mm 2 , (as per Underwriters laboratories UL-467-2007)99.9% electrolytic copper should be molecularly bonded to the steel core and radial width of copper should not be less than 0.25mm. 17.2(with minimum length of 3 meter) 25 32 232 491 804 4.14.2 Earth network/ring: A common earth termination network is recommended for the lightning protective system and all other services. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 66/124 Version 2.0 4.14.3 The resistance to earth should, in this case, be the lowest value required for any of the individual services. In other words, all the earth terminals that of equipment, electrical power, lightning protective system, antenna, etc., are to be connected together to form a common earth network. 4.14.4 One lightning protection system should consist of at least one plate earth terminal and other earth electrodes made by driving copper rods of suitable type into the ground. 4.14.5 No appreciable advantage in resistance reduction is gained by increasing the diameter or surface of the driven electrode. Larger sizes become more difficult to drive and are more expensive in materials. 4.14.6 Where deep driving of earth rods is not possible, a matrix arrangement of rods coupled to one another by conductors can be used. If possible the earth rods must be spaced at a distance at least twice their driven depth. 4.15 Importance of earth ring in reducing potential gradient:- 4.15.1 As the lightning current is discharged through the earth electrode, the surrounding soil is raised for the duration of the discharge to a potential with respect to the body of the earth. The resulting potential gradient is illustrated in Figure 4.6 and it is shown how its voltage gradient can be reduced by adding ring earth electrodes to lower the effective earth resistance. 4.15.2 Such potential difference may be lethal to a person if it exceeds a few thousand volts and to an animal if it exceeds a few hundred volts. 4.15.3 As this potential difference is a function of the product of the lightning current and the resistance of the earth electrode, the importance of keeping the latter as low as possible is evident. For practical purposes, a maximum value of 10Ω is recommended. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 67/124 Version 2.0 4.15.4 The danger to persons within a structure is effectively reduced by the presence of any floor other than that of earth or rock. 4.15.5 To reduce the voltage gradient in case of lightning, a long ground surface near to masts, towers and columns, the earth terminations of each lightning protective system should be interconnected by a ring conductor. 4.15.6 This ring conductor should preferably be buried to a depth of at least 0.5m unless other considerations, such as the need for bonding other objects to it or testing, make it desirable to leave it exposed. 4.15.7 The ring conductor should be connected to the ring conductors of the neighbouring structures. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 68/124 Version 2.0 Figure-4.6 4.16 Anti-corrosive measures (Importance thereof):- Corrosion due to atmospheric, chemical, electrolytic or other causes is likely to impair any part of the lightning protective system; therefore, suitable precautions as mentioned below should be taken to prevent its occurrence:- 4.16.1 Due to the harmful corrosion which is likely to result, coke breeze should not be allowed to come in contact with copper electrodes and salting of the ground in the vicinity of any earth electrode should not be practiced. 4.16.2 In some cases if it is not possible to achieve earth’s resistance less than 1 ohm then all copper to copper joints shall be made by welding or brazing only Bolting of joints shall not be accepted. The minimum distance by which these electrodes should be separated is 3mtrs and maximally it can go up to twice of it i.e. 6mtrs. 4.16.3 Electrolytic corrosion between dissimilar metals: The contacts of dissimilar metals unless the contact surfaces are kept completely dry and protected against the ingress of moisture, are likely to initiate and accelerate corrosion. 4.16.4 The metal of lightning protection system must be compatible to the metals of the structure over which it passes or makes contact with corrosion inhibitors may be used if required. 4.16.5 Aluminium is prone to corrosion when in contact with cement and mortar mixes. 4.16.6 Backfill compound if used for soil treatment shall provide anti corrosion protection to the electrodes. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 69/124 Version 2.0 4.16.7 Fittingsshould be resistant to the corrosive agencies or be otherwise suitably protected. 4.16.8 Joints and bonds may be protected with bitumen or embedded in plastic compound according to the local conditions as shown in figure 4.7 below:- Figure-4.8 ------------------------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 70/124 Version 2.0 Chapter-5 Surge and Transient Protection Systems 5.1 Surge & Transient:- Surge is an overvoltage or overcurrent of a short duration occurring on a power line while transient is an overvoltage or overcurrent pulse occurring on a power, signal, control or data line. The term “surge” is used to describe a transient overvoltage on a power line that has duration of a few microseconds. A transient overvoltage can exceed the insulation rating of electrical equipment causing degradation of insulation and immediate damage to the equipment. Relatively low-amplitude transient overvoltages applied repetitively on the equipment will reduce its mean time before failure. The result will be that equipment will have to be repaired more often, increasing operating costs. 5.2 Why Surge Protection is needed:- 5.2.1Power surges can cause failure, permanent degradation, or temporary malfunction of electronic devices and systems. The development of an effective Surge Protection Device (SPD) is of paramount importance to manufacturers and users of industrial electronic equipment. 5.2.2Almost all manufacturers of industrial-type SPDs use metal–oxide varistors (MOVs) in their design. MOVs are composed of a thin disk wafer of material (metal– oxide) that has a known voltage breakdown characteristic. At low voltages, the MOV conducts very little current (microamperes). As the voltage approaches breakdown, the MOV then begins to conduct current. At voltages slightly above the break down, large currents flow, effectively clamping the output voltage. This clamping feature allows the higher voltage levels to be shunted to ground, preventing overvoltages on equipment. 5.2.3 Figure 5.1 and 5.2below show the voltage waveform before and after an ideal Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 71/124 Version 2.0 SPD:- Figure 5.1 Voltagewaveform before SPD. Figure 5.2 Voltage waveform after an ideal SPD 5.2.4 Causes of Power Line Surges:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 72/124 Version 2.0 The sporadic damped phenomena that occur in electrical systems are generally described as transients and surges or in other words Power surges and transient overvoltages are due to the sudden change in the electrical conditions of a circuit and the release of large amounts of energy stored in the inductance and capacitance elements of the system. Sources of power surges can be external or internal to the facility. 5.2.4.1External sources of transient overvoltages can be the following:- Lightning. Switching (on/off) of capacitor banks, for power coefficient Correction. Power-line disconnection and reconnection. Transformer switching on/off. Electrostatic discharges. Power utility load switching. Poor quality of power transmission and distribution grids. 5.2.4.2 Internal surges are caused by the operation of the following devices:- circuit breakers or fuses; electric motors, i.e., elevators; air conditioners; VSDs generators. 5.3 It is very important to note that the IS 3043 has specifically recommended the use of surge protection systems to protect the sensitive equipment’s against over voltages induced by lightning and switching surges. 5.4 Transient over voltages are generated due to:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 73/124 Version 2.0 a) Whenever a lightning strikes directly / in the near vicinity; b) As a consequence of different faults in the power system; and c) Switching on and off of different loads etc. d) Hence, it is very important to protect the sensitive electrical and electronic equipment’s against these transient voltage surges. 5.5 The transient voltage surges are broadly classified into two types :- Lightning Surges ( Handled by Class B or Type I SPDs); and Switching surges ( Handled by Class C or Type II SPDs) 5.5.1 The lightning surges bring very high amount of destructive energy into the system and hence, are potentially very dangerous. The Class B SPDs are designed to handle the lightning current surges. 5.5.2 The switching surges are relatively frequent than the lightning surges. Although they bring in relatively less energy into the system, however, they still are strong enough to damage the sensitive electronics. The switching surges are handled by the Class C SPDs. 5.5.3 Latest IEEE Guidelines express that lightning activity at a place can induce surges due to Galvanic Coupling for about 1.7 km radius from the point of impact. Hence, it is important to note, both the lightning and the switching surges can come from outside of our power system and hence these surges need to be isolated at the mains input point itself so it is important to put appropriate surge protection devices to all the cables i.e. Power, Data, Remote Control, RF Cables or any other devices which is likely to carry surge and which enters into a equipment room where sensitive CNS/ATM systems are installed. 5.6 Methodology for surge protection:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 74/124 Version 2.0 Surge mitigation technique suggests use of surge suppression devices for power and data lines. The sole function of a good quality surge suppressor is to protect sensitive electronic equipment from transient over voltages. It must limit transient over voltages to a value that do not surpass the AC sine wave peaks by more than 30%. 5.6.1 A surge protector (or surge suppressor) is an appliance designed to protect electrical devices from voltage spikes. A surge protector attempts to limit the voltage supplied to an electric device by either blocking or shorting to ground any unwanted voltages above a safe threshold. 5.6.2 The terms surge protection device (SPD), or the obsolescent term transient voltage surge suppressor (TVSS), are used to describe electrical devices typically installed in power distribution panels, process control systems, communications systems, and other heavy-duty industrial systems, for the purpose of protecting against electrical surges and spikes, including those caused by lightning. 5.7 Main performance parameters of a surge protector are as follows:- 5.7.1 Clamping voltage also known as the let-through voltage. This specifies what spike voltage will cause the protective components inside a surge protector to divert unwanted energy from the protected line. A lower clamping voltage indicates better protection, but can sometimes result in a shorter life expectancy for the overall protective system. 5.7.2 Joules rating: This number defines how much energy the surge protector can theoretically absorb in a single event, without failure. Counter-intuitively, a lower number may indicate longer life expectancy if the device can divert more energy elsewhere and thus will need to absorb less energy. In other words, a protective device offering a lower clamping voltage while diverting the same surge current will cause more of the surge energy to be dissipated elsewhere in the system. Better protectors Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 75/124 Version 2.0 exceed peak ratings of 1000 Joules and 40, 000 Amperes. It is often claimed that a lower Joule rating is undersized protection, since the total energy in harmful spikes can be significantly larger than this. However, if properly installed, for every joule absorbed by a protector, another 4 to 30 joules may be dissipated harmlessly into ground. A MOVbased protector (described below in Para 4.8.1) with a higher let-through voltage can receive a higher joule rating, even though it lets more surge energy through to the device to be protected. 5.7.3 Response time: Surge protectors do not operate instantaneously; a slight delay exists. The longer the response time, the longer the connected equipment will be exposed to the surge. However, surges usually take around a few microseconds to reach their peak voltage, and a surge protector with a nanosecond response time would kick in fast enough to suppress the most damaging portion of the spike. All MOVs have response times measured in nanoseconds, while test waveforms usually used to design and calibrate surge protectors are all based on modelled waveforms of surges measured in microseconds. As a result, MOV-based protectors have no trouble producing impressive response-time specifications. Slower-responding technologies (notably, GDTs) may have difficulty protecting against fast spikes. 5.7.4 Transient surges: These are characterised by different waveforms. The most frequently referenced IEEE waveform used to simulate lightning induced transient activity is the combination wave. This wave is characterised by short duration, high frequency 8/20 µs current and 1.2/50 µs voltage waveform. 5.8 Types of surge protectors:- Systems used to reduce or limit high voltage surges can include one or more of the following types of electronic components. Some surge suppression systems use multiple technologies, since each method has its strong and weak points. Some of these operate primarily by diverting unwanted surge energy away from the protected load, through a protective component connected in a parallel (or shunted) topology. Some others block Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 76/124 Version 2.0 unwanted energy by using a protective component connected in series with the power fed to the protected load, and additionally may shunt the unwanted energy like the earlier systems. 5.8.1 Metal oxide Varistors (MOV) : A metal oxide varistors consists of a bulk semiconductor material (typically sintered granular zinc oxide) that can conduct large currents (effectively short-circuits) when presented with a voltage above its rated voltage. MOVs typically limit voltages to about 3 to 4 times the normal circuit voltage by diverting surge current elsewhere than the protected load. 5.8.1.1 MOVs may be connected in parallel to increase current capability and life expectancy; provided they are matched sets (unmatched MOVs have a tolerance of approximately ±20% on voltage ratings, which is not sufficient). 5.8.1.2 MOVs have finite life expectancy and "degrade" when exposed to a few large transients, or multiple smaller transients. As a MOV degrades, its triggering voltage falls lower and lower. If the MOV is being used to protect a low-power signal line, the ultimate failure mode typically is a partial or complete short circuit of the line, terminating normal circuit operation. 5.8.1.3 If used in a power filtering application, eventually the MOV behaves as a part-time effective short circuit on an AC (or DC) power line, which will cause it to heat up, starting a process called thermal runaway. 5.8.1.4 As the MOV heats up, it may degrade further, causing a catastrophic failure that can result in a small explosion or fire, if the line current is not otherwise limited. 5.8.1.5 When used in power applications, MOVs usually are thermal fused or otherwise protected to avoid persistent short circuits and other fire hazards. In a typical power strip, the visible circuit breaker may be distinct from the internal thermal fuse, which is not normally visible to the end user. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 77/124 Version 2.0 5.8.1.6 If a surge current is so excessively large as to exceed the MOV parameters and blow the thermal fuse, then a light found on some protectors would indicate unacceptable failure. 5.8.1.7 Even adequately-sized MOV protectors will eventually degrade beyond acceptable limits, with or without a failure light indication. 5.8.1.8 Therefore, all MOV-based protectors intended for long-term use should have an indicator that the protective components have failed, and this indication must be checked on a regular basis to insure that protection is still functioning. 5.8.1.9 Because of their good price/performance ratio, MOVs are the most common protector component in low-cost basic AC power protectors. 5.8.2 Transient voltage suppression (TVS) diode: ATVS diode is a type of Zener diode, also called an avalanche diode or silicon avalanche diode (SAD), which can limit voltage spikes. 5.8.2.1 These components provide the fastest limiting action of protective components (theoretically in picoseconds), but have a relatively low energy absorbing capability. 5.8.2.2 Voltages can be clamped to less than twice the normal operation voltage. 5.8.2.3 If current impulses remain within the device ratings, life expectancy is exceptionally long. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 78/124 Version 2.0 5.8.2.4 If component ratings are exceeded, the diode may fail as a permanent short circuit; in such cases, protection may remain but normal circuit operation is terminated in the case of low-power signal lines. 5.8.2.5 Due to their relatively-limited current capacity, TVS diodes are often restricted to circuits with smaller current spikes. 5.8.2.6 TVS diodes are also used where spikes occur significantly more often than once a year, since this component will not degrade when used within its ratings. 5.8.2.7 A unique type of TVS diode (trade names Transzorb or Transil) contains reversed paired series avalanche diodes for bi-polar operation. 5.8.2.8 TVS diodes are often used in high-speed but low power circuits, such as in data communications. These devices can be paired in series with another diode to provide low capacitance as required in communication circuits. 5.8.3 Thyristor Surge Protection device (TSPD), a specialized solid-state electronic device used in crowbar circuits to protect against overvoltage conditions. 5.8.3.1 These Thyristor-family devices can be viewed as having characteristics much like a spark gap or a GDT, but can operate much faster. 5.8.3.2 They are related to TVS diodes, but can "break over" to a low clamping voltage analogous to an ionized and conducting spark gap. After triggering, the low clamping voltage allows large current surges to flow while limiting heat dissipation in the device. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 79/124 Version 2.0 5.8.4 Gas Discharge Tube (GDT): A gas discharge tube (GDT) is a sealed glassenclosed device containing a special gas mixture trapped between two electrodes, which conduct electric current after becoming ionized by a high voltage spike. 5.8.4.1 GDTs can conduct more current for their size than other components. 5.8.4.2 Like MOVs, GDTs have a finite life expectancy, and can handle a few very large transients or a greater number of smaller transients. 5.8.4.3 The typical failure mode occurs when the triggering voltage rises so high that the device becomes ineffective, although lightning surges can occasionally cause a dead short. 5.8.4.4 GDTs take a relatively long time to trigger, permitting a higher voltage spike to pass through before the GDT conducts significant current. It is not uncommon for a GDT to let through pulses of 500 V or more in duration of100 ns. 5.8.4.5 In some cases, additional protective components are necessary to prevent damage to a protected load, caused by high-speed let-through voltage which occurs before the GDT begins to operate. 5.8.4.6 GDTs create an effective short circuit when triggered, so that if any electrical energy (spike, signal, or power) is present, the GDT will short this. 5.8.4.7 Once triggered, a GDT will continue conducting (called follow-on current), until all electric current sufficiently diminishes, and the gas discharge quenches. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 80/124 Version 2.0 5.8.4.8 Unlike other shunt protector devices, a GDT once triggered will continue to conduct at a voltage less than the high voltage that initially ionized the gas; this behaviour is called negative resistance. 5.8.4.9 Additional auxiliary circuitry may be needed in DC (and some AC) applications to suppress follow-on current, to prevent it from destroying the GDT after the initiating spike has dissipated. 5.8.4.10 Some GDTs are designed to deliberately short out to a grounded terminal when overheated, thereby triggering an external fuse or circuit breaker. 5.8.4.11 Many GDTs are light-sensitive, in that exposure to light lowers their triggering voltage. Therefore, GDTs should be shielded from light exposure, or opaque versions that are insensitive to light should be used. 5.8.4.12 Due to their exceptionally low capacitance, GDTs are commonly used on high frequency lines, such as those used in telecommunications equipment. 5.8.4.13 Because of their high current handling capability, GDTs can also be used to protect power lines, but the follow-on current problem must be controlled. 5.8.5 Selenium Voltage Suppressor: An "overvoltage clamping" bulk semiconductor similar to a MOV, though it does not clamp as well. 5.8.5.1 It usually has a longer life than a MOV. It is used mostly in high-energy DC circuits, like the exciter field of an alternator. 5.8.5.2 It can dissipate power continuously, and it retains its clamping characteristics throughout the surge event, if properly sized. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 81/124 Version 2.0 5.8.6 Carbon Block Spark Gap Overvoltage Suppressor: A spark gap is one of the oldest protective electrical technologies still found in telephone circuits, having been developed in the nineteenth century. In this type of suppressor, a carbon rod electrode is held with an insulator at a specific distance from a second electrode. The gap dimension determines the voltage at which a spark will jump between the two parts and short to ground. The typical spacing for telephone applications is 0.076 mm (0.003"). 5.8.6.1 Carbon block suppressors are similar to gas arrestors (GDTs) but with the two electrodes exposed to the air, their behaviour is affected by the surrounding atmosphere, especially the humidity. 5.8.6.2 Since their operation produces an open spark, these devices should never be installed where an explosive atmosphere may develop. 5.8.7 Quarter-wave coaxial surge arrestor :Used in RF signal transmission paths, this technology features a tuned quarter-wavelength short-circuit stub that allows it to pass a bandwidth of frequencies, but presents a short to any other signals, especially down towards DC. The pass bands can be narrowband (about ±5% to ±10% bandwidth) or wideband (above ±25% to ±50% bandwidth). Quarter-wave coax surge arrestors have coaxial terminals, compatible with common coax cable connectors (especially N or 7- 16 types).They provide the most rugged available protection for RF signals above 400 MHz; at these frequencies they can perform much better than the gas discharge cells typically used in the universal / broad band coax surge arrestors. Quarter-wave arrestors are useful for telecommunications applications, such as Wi-Fi at 2.4 or 5 GHz but less useful for TV/CATV frequencies. Since a quarter-wave arrestor shorts out the line for low frequencies, it is not compatible with systems which send DC power for a LNB up the coaxial downlink. A typical Quarter-wave coaxial surge arrestor is shown in figure 5.3 below:- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 82/124 Version 2.0 Figure- 5.3 5.8.8 Series Mode (SM) Surge Suppressors: These devices are not rated in Joules because they operate differently from the earlier suppressors, and they do not depend on materials that inherently wear out during repeated surges. 5.8.8.1 SM suppressors are primarily used to control transient voltage spikes on electrical power feeds to protected devices. 5.8.8.2 They are essentially heavy-duty low-pass filters connected so that they allow 50/60 Hz line voltages through the load, while blocking and diverting higher frequencies. 5.8.8.3 This type of suppressor differs from others by using banks of inductors, capacitors and resistors that shunt voltage spikes to the neutral wire, whereas other designs shunt to the ground wire. Where ground is bonded to neutral at the electrical service entrance, the resulting surge ultimately flows into ground at that connection, but by first dumping into neutral, nearby ground contamination is avoided. 5.8.8.4 Since the inductor in series with the circuit path slows the current spike, the peak surge energy is spread out in the time domain and harmlessly diverted into the capacitor bank. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 83/124 Version 2.0 5.8.8.5 Experimental results show that most surge energies occur at under 100 Joules, so exceeding the SM design parameters is unlikely, but it provides no contingency should rare events induce energies that exceed it. 5.8.8.6 SM suppressors do present a theoretical fire risk, should the absorbed energy exceed design limits of the dielectric material of the components. 5.8.8.7 In practice, surge energy is also limited via arc-over to ground during lightning strikes, leaving a surge remnant that often does not exceed a theoretical maximum (such as 6000 V at 3000 A with a modelled shape of 8 x 20 µs waveform specified by IEEE/ANSI C62.41). 5.8.8.8 SM suppression focuses its protective philosophy on a power supply input, but offers nothing to protect against surges appearing between the input of an SM device and data lines, such as antenna, telephone or LAN connections, or multiple such devices cascaded and linked to the primary devices. 5.8.8.9 In this design philosophy, such events are already protected against the SM device before the power supply. 5.8.8.10 SM low-pass filters are generally not suitable for data communications circuits, because they would also block high-speed data signals from getting through. 5.8.8.11 In comparison to devices relying on components that operate only briefly and do not normally conduct electricity (such as MOVs or GDTs), SM devices tend to be bulkier and heavier than those simpler spike shunting components. 5.8.8.12 The initial costs of SM filters are higher, but a long service life can be expected if they are used properly. In-field installation costs can be higher, since SM Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 84/124 Version 2.0 devices are installed in series with the power feed, requiring the feed to be cut and reconnected. 5.9 Important points regarding installation of Surge Protection at mains input level and at power distribution boxes:- 5.9.1 A comprehensive surge protection system comprising of an INTEGRATED CLASS B +CLASS C TYPE SURGE PROTECTION SYSTEM is ideally suited for installation at the mains input and substation switch boards. 5.9.2 The SPD used shall comply with the performance requirements of the IEC 61643 or equivalent. 5.9.3 The Main Surge Protection System is to be installed in the mains input panel on the LT side. An indicative system is shown in Figure -5.4 below:- Figure- 5.4 5.9.4 The system shall offer comprehensive protection against all types of transient Over Voltages and shall use high capacity MOVs only. It shall be of combined class B+C type. i.e. it shall be capable of handling Lightning as well as Switching Surges. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 85/124 Version 2.0 5.9.5 Class B surge protection device (N-G) may consist of encapsulated air gap device (GDT) and may be used as galvanic separation between N-PE conductors with following characteristics:- i) Protection mode : N-PE ii) Single pole surge protection device iii) Impulse current capacity : 100 kA iv) Max current 160 kA v) Status indicator available 5.9.6 The surge protection system shall be configured such that the system offers all mode (Differential) protection. The protection shall be between each phase to neutral, each phase to earth and between neutral to earth. A typical system is indicated below:- Figure-5.5 5.9.7 The surge protection system shall comprise of multiple MOV based surge arrestors housed in an IP 65 enclosure. 5.9.8 Each Surge arrestor shall consist of at least three elements for backup protection. Each element of the surge arrestors shall comply with the performance requirements of the IEC 61643 or equivalent. 5.9.9 The Surge protection system design shall be modular in nature so that the Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 86/124 Version 2.0 individual surge arrestors can be replaced after its elements have reached the end of their life. 5.9.10 The surge arrestors shall be mounted on a DIN RAIL and housed in an IP 65 or equivalent grade enclosure for reliability and ease of replacement / maintenance. 5.9.11 The design shall be such that when a given element fuses, the balance elements in the surge arrestor continue to offer protection to the installation till it is replaced with a new one in a short period of time. 5.9.12 When any element fuses, the respective status indicator flag shall turn red indicating that the element is out of service. 5.9.13 Each individual element in the surge arrestor shall be rated as follows : - Max. Continuous operating voltage (Uc) 440 V Min. Lightning impulse current (Iimp) 15 KA ( 10/350 µs) per phase Nominal discharge current 80 KA(8/20 µs) Maximum discharge current 150 KA(8/20 µs) Peak value current 40 KA(10/350 µs) Specific energy 400 KJ/Ω Charge 20 As Protection level 1.9 KV(8/20µs);1.7 KV(10/350µs) Response time < 25 ns Residual current < 2.5 mA Follow current 0 Thermo coupler Present Fuse Present Short circuit withstand 25 KA for 50 Hz supply Switching surge current (Imax) 100 KA (8/20 µs) per phase Switching surge current (Inom) 30 KA (8/20 µs) per phase Clamping voltage 1800 V between L-E, L-N, N-E Minimum Inom exposures before fusing 20 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 87/124 Version 2.0 5.9.14 The surge arrestor elements shall be designed to withstand the specified Switching Surge Current (Inom) current for a minimum of 20 times without fusing. 5.9.15 The surge protection system shall be connected in parallel with the circuit and shall not draw the line current. The system shall be connected to the circuit with 10 / 16 Sq mm single core PVC insulated flexible copper conductor cables. The terminal connectors of the system shall be so designed to avoid any loose connections. 5.9.16 In addition to the Main surge protection Device, which provides combined Class B & C protection at the main incoming, a series surge filter may be considered to be installed at all the UPS incoming and outgoing supply which will have the following features:- I) It shall offer All Mode Protection; II) It shall offer redundant protection and staged ; III) LED status indication; and IV) Option for remote monitoring may be considered. 5.9.17 The surge filter shall filter the surges and transients occurring up to the branch panels. It shall offer all mode protection for (L-N, L-E and N-E). 5.9.18 It shall conform to ULI 1449 Edition 2 or equivalent for the metallic enclosure. 5.9.19 The MCB shall be included to ensure safety isolation under power frequency overload condition. 5.9.20 It shall be suitable for a line current of 32A or 63A, 3 phase and up to 320 V 50 Hz power supply. 5.9.21 It shall be connected in series. The surge rating shall be 40 kA, 8/20µs. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 88/124 Version 2.0 5.9.22 Each phase surge arrestor employed shall have two redundant and independent fused and thermal over load protection elements to provide back-up protection for continued equipment survival. 5.9.23 The technical features shall be as described below: Normal Voltage 320Vrms(1p), 380V(3p) Operating Voltage 180-280Vrms(1 ph); 300-480Vrms (3 ph) Operating Frequency 50 Hz Connection type Series Max. surge rating per line 50 kA to 140kA (8/20µs) Let through voltage <380V for 3 KA Cat B Protection mode L-N, L-E, N-E Earth leakage current < 1 µA Efficiency 99% Frequency response 3 dB (at 800 Hz) Response time < 5 ns Standards compliance BS6651-1999 cat.A.B.C AS1768-2003 cat.A.B.C IEEE C62.41 cat.A.B.C CP33-1999 cat.A.B.C IEC 1000-4 5 1995 UL 1449 second edition EMC Compliance BS EN 60950 : 1992; BS EN 61000 : 1999 Alarm isolation 4 Kv Status indicator LED Optional remote alarms Siren sound OK and FAIL LED Alarm(volt free contact) N/O, N/C(2A@250Vac) Alarm conductor size 2.5mm² Conductor size 35 mm² Mounting Back panel screw mount Enclosure material Galvanized steel alloy Enclosure IP rating IP 55 Operating temperature - 40 -85ºc Humidity 0-95% (R.H) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 89/124 Version 2.0 5.10 COMPUTER NETWORK PROTECTOR: - The Cat5, Cat 5e, Cat 6 and POE (Power over Ethernet) cables shall be provided with a suitable surge protector. It shall be suitable for RJ 45 connectors 5.10.1 It shall be designed to protect all widely used computer network system using Ethernet twisted pairs technology like 10/100/1000 BaseT, CDDI, ATM155 and also the Power-over-Ethernet. 5.10.2 It shall offer protection against transient over voltages due to lightning induced surges, AC power interference and ground loop energies appearing between any signal pair and / or its ground which can damage the sensitive network equipment. 5.10.3 The series protector shall be designed to protect both common and differential mode in all the 8 pins of the RJ 45 port and its ground lead. 5.10.4 It shall have the latest circuitry using Silicon Avalanche diode to ensure very fast response time and exceptional low let-through voltage which results in maximum system reliability and up-time. 5.10.5 The shunt capacitance shall be 5pf and negligible in-line resistance so that even the most demanding high speed gigabit multimedia signal can be passed without much signal degradation. 5.10.6 It shall be compact, in-line and simple plug-in design to enable it to be easily located near the protected equipment. 5.10.7 The technical features shall be as described below:- Max. working Voltage 5V Max. operating current 300mA Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 90/124 Version 2.0 Protection modes Common and transverse Lines protected All pairs Response time < 5 ns Max. surge rating 100A (8/20µs) Max. Data rate 100Mb/s (C5, PoE models), 1000Mb/s(C6 models) Let through voltage 23V (A1 5 KV 10/700µs) Shunt capacitance 5pF (single port models), 25pF(rack-mount models) In line resistance -0 Ω Standards compliance 100 Base T, 1000Base T, CAT5, CAT5e, CAT6 Connector type RJ 45 Earth connection Flying lead(single port models) Earth stud(rack-mount models) Enclosure material Anodized aluminum (single port) Galvanized steel alloy(multi-port) Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.11 Telecom line protector: All the telecommunication lines shall be protected with a suitable Surge Protector to protect the modems and other sensitive equipment’s. It shall be designed to protect all widely used telecommunication lines like PSTN, ISDN, DDN and DSL using twisted pairs. Different connectors like RJ45, RJ11 and plug/socket models shall be used to obtain optimum protection. Following are the main characteristics of Telecom line protector:- 5.11.1 The hazard of lightning induction in telephone lines can be managed by using transient protection units in parallel with each line. These multi line protection can have multi stage protection i.e. Hybrid GDT for over voltage protection and PTC for over current protection. 5.11.2 It shall offer Protection against Transient over voltages due to lightning induced surges, AC power interference and ground loop energies appearing between Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 91/124 Version 2.0 any signal pair and/or its ground that can damage the sensitive telecommunication equipment. 5.11.3 The protector shall be designed to protect both common and differential mode in all the connected pins of the RJ 45 or RJ 11 port and its ground lead. 5.11.4 They shall be multi-stage design which employ a combination of high energy gas discharge tube, ultra fast diodes and SAD which results in maximum system reliability and up-time. 5.11.5 It shall have 20KA surge handling capability and 20MHz high bandwidth, so that it can provide the safest protection in lightning intense environment to ensures a smooth data traffic. 5.11.6 It shall be compact, in-line and simple plug-in design enabling it to be easily located near to the protected equipment. 5.11.7 The important technical features of Telecom Line Protector are described as below:- Max. working Voltage (Line to line) 190v (PSTN) , 60 V (ISDN) , 68 V (DDN) 50 V (XDSL) Max. operating current 150mA Protection modes Common and transverse Lines protected 2 wires (RJ11-pin3& 4, RJ45-pin4& 5) 4 wires(RJ11-pin 3& 4, 2& 5, RJ 45-pin 4& 5, 3& 6) Response time < 5 ns Max. surge rating 20A (8/20µs) Max. Data rate 20Mb/s Let through voltage (at 5KV 10/700µs) 220V (PSTN) , 80 V (ISDN) 78V (DDN) , 60V (xDSL) Shunt capacitance < 150pF Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 92/124 Version 2.0 In line resistance 3.9 Ω Standards compliance BS6651-1999, AS1768-2003 IEC61643-21 , ITU(CCITT)1X K17 Connector type RJ 45 or RJ 11 Earth connection Flying lead (single port models) Earth stud (rack-mount models) Enclosure material Anodized aluminum(single port) Galvanized steel alloy (multi-port) Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.12 DATA PORT PROTECTOR:- The SPD for Data Line shall be based on transistor and diode circuitry which ensures a lower let through voltage to protect from the surge and transient overvoltage. Following are the main characteristics of Data Port Protector:- 5.12.1 In case of the Surge current above the Rated capacity it shall fuse and isolate the sensitive equipment. 5.12.2 It shall offer common mode & Transverse mode protection against the Transients appearing between any signal pairs. 5.12.3 The DPP RS232 port protectors shall be compact and in-line design which can be easily connected to the data of the equipments. 5.12.4 The V.35 and the RJ21X data port protectors shall be easily secured onto a standard 35mm Top Hat DIN rail. 5.12.5 It shall have fast response circuit not only to protect the equipments from repeated surges but also to allow the DPP protectors to transparently transmit the data at a speed of up to 20 Mbps. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 93/124 Version 2.0 5.12.6 DPP protector shall offer nearly zero in line resistance and a 40pF capacitance which allows the data to transmit smoothly on the lines. 5.12.7 The important technical features of Data Port Protector are described as below:- Max. operating current 300mA Protection modes Common and transverse Response time 1 ns Max. surge rating 200A (8/20µs) Max. Data rate 20Mb/s Insertion loss <1dB at 20 MHz Capacitance 40pf Standards compliance BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C IEC61643-21, ITU(CCITT)1X K17 CP33-1996 Cat A.B.C, UL497B Connector type DB9 female to male (DPP9) DB25 female to male(DPP25) M/34 female to male(DPP35) RJ21X female to male (DPP50) Earth connection DIN clip (DPP35, DPP50) Flying lead(DPP9), shell(DPP25) Enclosure material Anodized aluminum (DPP35, DPP50) Plastic (DPP9, DPP25) Operating temperature - 40 ºc to 85 ºc Humidity 0 to 95% (R.H) Altitude 0-3650m 5.13 RF COAXIAL PROTECTOR:- RF Coaxial protectors are intended to pass through a desired RF signal with minimum loss or disturbance. To minimize the impact of inserting lightning protectors within the RF circuit, seek out products with the lowest Insertion Loss and lowest VSWR at the frequencies that is intended to operate. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 94/124 Version 2.0 5.13.1Other important main characteristics of RF Coaxial Protector (Fig 5.6) are:- i) Reliable RF performance capability from DC – 3GHz ii) Multi – strike capability iii) Easily replaceable gas discharge tube iv) Bi-directional protection v) AC/DC pass vi) High quality construction vii) Full range of connector type Figure-5.6 5.13.2The coaxial RF protectors shall be a high performance gas discharge tube suppressor capable of wide-band operation from DC up to 3 GHz (N, SMA and D type connector). 5.13.3 The let-through voltage shall be as low as possible and it is capable of handling multi-strike in any lightning intensive environment. 5.13.4 CGR protectors feature easily replaceable gas tube arrester elements, which makes it simple, fast and cost effective in case replacement of the gas tube is required. 5.13.5 Both connector ports of this protector shall be equally protected. This provides protection no matter which way it is installed. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 95/124 Version 2.0 5.13.6 The important technical features of RF Coaxial Protector are described as below:- Frequency range 0-3GHz VSWR < 1.1:1 Return loss > 26dB Insertion loss < 0.2dB Impedance 50 Ω for all models Response time <5ns Peak surge rating 20 kA (8/20µs) DC sparkover voltage 90V+/- 20% (230, 350, 600, 1000V) Max. power 0 – 2000 W Standards compliance ITU(CCITT)1x K17 BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C CP33-1996 Cat A.B.C IEC61643-21/UL497B Body material Brass(Nickel plated) Contact pin Brass(silver/gold plated) Contact socket Beryllium or tin brass(silver/gold plated) Elastic contact Beryllium or tin brass(silver/gold plated) Insulator PTFE O-ring material Silastic Earth connection Via suitable screw ground lug Mounting L shape bracket Operating temperature -4-85ºc Humidity 0-95% (R.H) Altitude 0-3650m IP rating IP 65 Moisture resistance MIL-STD-202 Method 106D Salt fog MIL-STD-202 101D/B Temperature shock MIL-STD-202 107D/A-1 Vibration MIL-STD-202 Method204D/B Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 96/124 Version 2.0 5.14 Telephone Line Protector (Krone Type) The main characteristics of Telephone Line Protector which provides surge protection for telecom and other signalling equipment’s terminated on KRONE connectors are:- 5.14.1 The protector shall be available in various assorted configuration like 1 pair, 10 pair, 50 pair etc in a compact module having multi stage protection. 5.14.2 Full range of voltage to suit any particular applications and the let-through voltage shall be as low as possible. 5.14.3 The series protectors shall be easily pluggable type into the KRONE LSAPLUS disconnection blocks and shall be earthed suitably. 5.14.4 It shall offer both line to line (transverse mode) and line to earth (common mode) protection. 5.14.5 It shall have 20 KA high surge rating and 20 MHz wide bandwidth to provide the best protection and to ensure a smooth data flow in high speed data and signal lines. 5.14.6 It shall be designed in such a way that the surge exceeding the capacity of the primary gas arrester, service should be interrupted by blowing the track fuse and thereby giving a fault condition. 5.14.7 The important technical features of Telephone Line Protector are described as below:- Max. working voltage 7-280V Max. operating current 250Ma Protection modes Common and transverse Protection stages 3 stages Earth leakage current < 5 µA Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 97/124 Version 2.0 Response time <5ns Max. surge rating 20 kA (8/20µs)- KDP 10 5 KA (8/20µs) – KDP 1 Max. data rate 20 Mb/s Insertion loss < 1dB at 20 MHz Let through voltage: (At 5KV 10/700 µs) 10-320 V Capacitance 50 pf In line resistance 3.9Ω Standards compliance ITU(CCITT)1x K17 BS6651-1999 Cat.A.B.C AS1768-2003 Cat A.B.C CP33-1996 Cat A.B.C IEC61643-21 UL497B Earth connection Via earth clips on two ends – KDP 10 Via earth bar – KDP 1 Enclosure material ABS plastic Operating temperature - 40 ºc to 85 ºc Humidity 0-95% (R.H) Altitude 0-3650m 5.15 Installation notes and Important points in context of installation of Lightning, Surge Protection and Earthing Systems:- 5.15.1 A Connection made up by materials which do not comply with the chemical chain of materials choice like Copper and steel irrespective of their grade is not allowed to be connected with unless separated by appropriate means as stipulated within IEC62305-3. 5.15.2 IEC stipulates that the spark gaps used for single or multiple load be 100 kA at 8/20 µs single rated. Anything above 60 V is deadly for human life. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 98/124 Version 2.0 5.15.3 IEC 62305 regulatory norm permits only one common grounding network. This common grounding network must interconnect or cross mesh all the sub components of the LLZ system like its building, LLZ antenna array, and NF Monitor. Even the grounds of lightning protection system needs to be connected to the common grounding network. All external metal structures must be connected to the ground network. If there is any other equipment installed at the LLZ site, the same must necessarily be given relevant lightning protection not only for the sake of the equipment itself but for the sake of the whole LLZ installation. As an example wiring diagram of a standard electrical shelter installation (typical) of THALES ILS LLZ is shown below: Fig. Wiring Diagram of Electrical Installation (Typical) Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 99/124 Version 2.0 5.15.4 Implement lightning protection system compliant to IEC 62305 of Cat I. This does not permit the use of such ionizing devices like the prevectron which promise prevention of lightning and wider coverage. 5.15.5 Lightning protection by systems like “Early Streamer emission”, “Dissipation Array Systems” or “Charge Transfer Systems” are not allowed under standards of US National Fire Protection Association (NFPA), IEC, IEEE, Underwriters Laboratories (UL), US Military etc. 5.15.6 The power cable shielding must be connected to a common ground point. 5.15.7 The mains in-leading and out-leading armoured power cable must have its shield grounded with its PEN conductor to one common ground bus bar. The grounding must be done within 20 cm of the cable entry/exit point to/from the building. 5.15.8 The mechanical shield of each RF cable entering or leaving the building must be bonded to the ground at the point where it enters/leaves the building, but not more than 20 cm inside the building. Preferably it should be done outside the building. 5.15.9 The COM cable used for data communication should have its mechanical armouring and inner static shield connected to ground only at one end, say the TWR side and not at both ends. Connecting to ground at both ends is likely to induce strong equalizing ground current between different potentials of such far away buildings, which may reach values above 100 A under worst condition. The other end, both the armour as well as the shield should be grounded through a spark gap to the nearest common ground. The spark gap should be IEC 62305 compliant with low spark over voltage level (< 70 V AC) and high current rating values of 75 kA at 8/320 µs or more. 5.15.10 The IEC 62305 stipulates that there is only one common ground connecting all potentials to one, as well as the PEN, the power cable shield, the COM cable shield, any internal PE and grounds of SPDs, any RF cable shields and others like external Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 100/124 Version 2.0 groundings and lightning protection inclusive of the subsystems e.g. LLZ antenna, NFM etc. 5.15.11 RF cables entering the shelter must have in line surge arrestors. 5.15.12 The PE wire/conductor of a power cable is not a ground connection. The ground connection for static issues must use a connecting wire of cross sectional area 16 mm2 or more and use the shortest path to the near most ground. 5.15.13 All multi strand wire must use cable end sleeves and cable end lugs to enable proper installation and also to reduce chemical chain involved in corrosion. Any flat tape or round wire / cable connections must utilise termination clamps or brackets. 5.15.14 The cable routing of various voltage circuit must be separated, for e.g. the RF, the AC, the DC and the GND and static shields of all the cables must be grounded at point of entry into the building. 5.15.15 All shielded cable like RF, COM, armoured PWR line etc. should be connected to common potential ground at every 20 m along its external path. Same is to be done at every 2.5 m when internally laid. 5.15.16 Common ground network for a DVOR must be connected, DVOR building, Counterpoise steel structure, Counterpoise mesh, power cable shielding, power cable PEN wire, COM cable shield via spark gap, ground connection to SPD related to PWR, COM or RF cabling, Lightning protector rods, DVOR monitor mast/antenna, and other metallic objects of the system. 5.15.17 Copper can be bonded to galvanized steel via special bimetal media or stainless steel media of V4A grade. 5.15.18 PE: Protective earth; PEN: Combined protective earth and neutral; N: Neutral must all be connected to a common bus bar. Electrical conductors entering a Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 101/124 Version 2.0 structure should be metal cased. This metal casing should be electrically continuous within the structure; it should be earthed at the point of entry inside the structure on the user’s side of the service and bonded directly to the lightning protective system. 5.15.19 Where the electrical conductors are connected to an overhead electricity supply line, a 15m length of buried armoured cable should be inserted between the overhead line and the point of entry to the structure. 5.15.20 The overhead supply lines are liable to have large surges induced in them from lightning discharges. Hence is, therefore, needed where they join the buried cable. This will allow a large part of the lightning current to be discharged to earth at a safe distance, which is determined by the rolling sphere’s radius, from the structure. 5.15.21 Surge suppressors should be installed with minimum lead lengths to their respective panels. Under fast rise time conditions, cable inductance becomes important and high transient voltages can be developed across long leads. 5.15.22 In all instances, use high quality, high speed self diagnosing protective components. 5.15.23 Proper ground must be ensured. Earth resistance to be strived to achieved to be as low as possible preferably less than 5 Ω. 5.15.24 Do not install suppressor, if neutral to ground bond is not present. 5.15.25 If neutral to ground voltage is greater than 2 V AC, the electrical system is faulty and needs to be rectified. 5.16 Surge protection for typical DSCN System 5.16.1 A surge protector (or surge suppressor) device is used to protect linkway modem and RF components of DSCN system from lightning spikes and surges. A surge protector removes the lightning spikes induced in the RF cable through earth conduction. Moreover, Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 102/124 Version 2.0 power supply strips installed at DSCN system and RF component ends shall have built in surge protectors. A surge protection device shall also be mounted on a circuit breaker panel of UPS output. Figure below shows power strip with built in surge protector. 5.16.2 RF Connector Type of Surge Protector to be installed in DSCN System: 1. The surge protector of impedance 75Ω shall have F type female and F type male ends for connecting F type male to linkway2100 modem’s RX port and F type female to RF cable. 2. The surge protector of impedance 50Ω shall have N type female and N type male ends for connecting N type male to Linkway 2100 modem’s TX port and N type female to RF cable. 3. The surge protector shall have F type female and F type male ends for connecting F type male to linkway S2 modem’s TX and RX ports and F type female to RF cable. The impedance of surge protector shall be 75Ω for RX path and 50 Ω for TX path. 4. The surge protector of impedance 50Ω shall have N type female and N type male ends for connecting N type male to BUC’s TX port and N type female to RF cable. 5. The surge protector of impedance 75Ω shall have N type female and N type male ends for connecting N type male to LNB RX’s port and N type female to RF cable. Note: Most of LNB consist of N type port but a few LNBs are of F type. Stations may check before procurement. 5.16.3 Connection Diagram of Surge Protector (SPD) for DSCN System: Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 103/124 Version 2.0 5.16.4 Specification of typical Coaxial Cable Surge Protector used in DSCN system Proposed model is 90V DC. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 104/124 Version 2.0 Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 105/124 Version 2.0 NOTE: * Surge protector shall have rating of ‘DC Breakdown voltage’ of 90 Volt. # If 75 Ohm Surge protector is not available than 50 Ohm may be used with same voltage rating as above and LMR 400- 50 Ohm coaxial cable should be used instead of LMR 400-75 Ohm for Rx path. 5.16.5 Connection of Surge Protector Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 106/124 Version 2.0 5.17 Coaxial Connector Seal 5.17.1 Sealing Concepts for Coaxial Connectors: The electrical connecting points in coaxial connectors must be protected against ambient influences. Dust, water and moisture are a constant hazard especially in outdoor applications. Moisture particularly, which penetrates a coaxial system, changes the RF transmission enormously and leads to impedances or poor return loss values. Seals must be fitted at all connecting points to protect the sensitive and expensive electronics. Fig: Sealing Tape 5.17.2 Coax Seal Moisture Proof Sealing Tape 1/2" x 60". Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 107/124 Version 2.0 Coax-Seal is a special material that will quickly and effectively seal all types of coaxial fittings of any shape from moisture, water and corrosion. Coax-Seal stays flexible for years thus insuring moisture proof connections. It ensures good SWR and long coax life. CoaxSeal also allows you to disconnect and reconnect fittings with the same material by simply re-forming the plastic. Coax-Seal is the only material that will adhere to vinyl and poly vinyl connector’s outer covers. Coax-Seal is non-toxic, non-corrosive, non-conducting and stays flexible at any temperature. 5.17.3 Specifications of Self-Fusing Silicon tape/Silicon Rubber Tape: 1. Self-Bonding Silicone 2. Color: Black/oxide-red/Gray 3. Thickness: 30 mil 4. Width: 1.5 inches 5. Length: 15 feet 6. Operating Temperature Range: -30C to +70C 7. Tensile Strength: 700 PSI Minimum 8. Ultimate Elongation: 300% Minimum 9. Tear Resistance: 85 psi 10. Configuration: Rectangular shape Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 108/124 Version 2.0 Fig: Self-fusing Silicone tape ---------------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 109/124 Version 2.0 Chapter - 6 Measurement of Earth Resistance 6.1 Measurement of Earth Resistivity:- 6.1.1 Need for the measurement of Resistivity:- The resistivity of the soil varies within extremely wide limits, between 1 and 10, 000 Ω-meters. The resistivity of the soil is found to be non-uniform at many station sites. To design the most economical and technically sound grounding system for large installations, it is necessary to obtain accurate data on soil resistivity and on its variation. Resistivity measurements at the site help in designing a good earthing system. The resistivity of the earth varies over a wide range depending on its moisture content. It is therefore, advisable to conduct earth resistivity tests during the dry season in order to get conservative results. 6.1.2 Test Locations:- In the evaluation of the earth resistivity of, at least eight test directions should be chosen from the centre to cover the whole site. This number shall be increased for very large station sites and for sites where, the test results obtained at various locations show a significant difference, indicating variations in soil formation. In case of transmission lines, the measurements shall be taken along the direction of the line throughout the length approximately once in every 4 kilometers. 6.2 Principle of Tests:- 6.2.1 Wenner’s four electrode method is recommended for these types of field investigations. In this method, four electrodes are driven into the earth along a straight line at equal intervals. A current I is passed through the two outer electrodes and the earth as shown in figure below and the voltage difference V observed between the two inner electrodes. The current I flowing into the earth produces an electric field proportional to its density and to the resistivity of the soil. The voltage V measured Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 110/124 Version 2.0 between the inner electrodes is, therefore, proportional to the field. Consequently, the resistivity will be proportional to the ratio of the voltage to current. If the depth of burial of the electrodes in the ground is negligible compared to the spacing between the electrodes, then:- ρ = 2π SV / I Earth testers normally used for these tests comprise the current source and meter in a single instrument and directly read the resistance. The most frequently used earth tester is the four –terminal Megger shown in Fig 1. When using such a Megger, the resistivity may be evaluated from the modified equation as given below. ρ = 2π x SR Where ρ = resistivity in ohm – meters S = distance between successive electrode in meters R = Megger reading in ohms. C1, C2 Current Electrodes P1, P2 Potential Electrodes Fig. 6.1 Measurement of Earth Resistivity ---------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 111/124 Version 2.0 Chapter -7 Supply, Installation, Testing and Commissioning [SITC] of Lightning, Surge Protection and Earthing System of CNS Facilities as part of Turnkey Project. 7.1When Lightning, Surge Protection and Earthing System of CNS Facilities are being procured under SITC as a part of turnkey project, General Technical specifications of the Tender Document in such cases should clearly specify following:- The vendor/supplier/system integrator shall be responsible for complete Supply, Installation, Testing and Commissioning of the Lightning, Surge Protection and Earthing System of the facility. The vendor/supplier/system integrator shall design and provide a comprehensive Lightning, Surge Protection and Earthing System which shall meet the following National and International Standards:- IS-2309 Code of protection for Lightning Protection IS -3043 Code of practice for earthing IS -5216 Safety procedures & practice in electrical work IEC -62305 Protection against Lightning IEC -61643 Low Voltage Surge Protective Devices IEC -60364 Low Voltage electric Installation: ANSI/UL 467 Grounding & Bonding Equipment 7.2 The lightning & Surge Protection System provided shall be a comprehensive system i.e. it should include:- 7.2.1Power Supply Surge Protection System at the input of Equipment room where the facility is proposed to be installed and each distribution board which will supply power to the equipment and its accessories. 7.2.2Surge Protection system should be provided to all incoming and outgoing cables connected to system such as Data lines [Telephone, OFC, RC cables etc] and RF Cables etc. Standard bonding of cable shields/trays to ground at building entry/exit points must be ensured. 7.2.3Air Terminals/Lightning Rods should be positioned to give full coverage of structure [Building, Antenna, Mast etc.] against the lightning. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 112/124 Version 2.0 7.2.4 Earthing system shall meet the following requirements: 7.2.4.1 Provide safety to equipment from power line faults, lightning and surges. 7.2.4.2 Provide a common reference ground plane for electronic equipment which will minimize electronic system noise and electromagnetic interference (EMI). 7.2.4.3 The grounding system design shall be based on single grounding network with multiple earths. 7.2.5 Appropriate references should be made to the guidelines provided in the manual in this regard. 7.2.6 If only a part of Lightning, Surge Protection and Earthing System e.g. only surge protection system is to be supplied by vendor then also appropriate references should be made to standards in this regard in the tender document. 7.3 Any other specific requirement for Lightning, Surge protection and earthing system specific to the equipment being procured should also be clearly specified in the Tender Document. 7.4 Lightning, Surge Protection and Earthing System of CNS facility shall form a part of Factory Acceptance Test (FAT) and Site Acceptance Test (SAT). 7.5 The complete layout of the Lightning, Surge Protection and Earthing System of CNS facility shall be submitted by the vendor/supplier/system integrator before commissioning. ---------------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 113/124 Version 2.0 Chapter -8 Maintenance Procedures of Lightning, Surge Protection and Earthing Systems 8.1Responsibility of Maintenance Maintenance of Earthing, Lightning and Surge Protection System for the CNS installations installed in Terminal Building and/or Technical Block and located inside operational area and around airport (Radar, LLZ, GP, DVOR, OM/MM and NDB etc. ) shall be looked after by the CNS personnel. 8.2 Testing:- 8.2.1 On the completion of the installation, or any modification to it, the following measurements should be made and the results recorded in a lightning protective system logbook: i) The resistance to earth of the whole installation and of each earth termination. ii)The electrical continuity of all conductors, bonds and joints. 8.2.2 If the resistance to earth of a lightning protective system exceeds 5Ω, the value should be reduced. If the resistance is less than 5Ω, but significantly higher than the previous reading, the cause should be investigated and any necessary remedial action should be taken. 8.2.3 Tests should be repeated at fixed intervals, preferably not exceeding 06 months. 8.2.4 It is emphasized that before isolating a lighting protection earth, it should be tested to ensure that it is not “live”, using a sensitive voltage device. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 114/124 Version 2.0 8.3 System Inspection:- 8.3.1 All lightning protective systems should be visually inspected by a competent person during installation, after completion and after alteration or extension, in order to verify that they are in accordance with the recommendations in this code. 8.3.2 Visual inspections should be repeated at fixed intervals, preferably not exceeding 03 months. 8.3.3 In addition, the mechanical condition of all conductors, bonds, joints, and earth electrodes (including reference electrodes) should be checked and the observations noted. 8.3.4 If, for any reason, such as other site works, it is temporarily not possible to inspect certain parts of the installation, this also should be noted. 8.4 Total System Maintenance 8.4.1 Of particular importance is the regular detailed examination of the complete LPS for any evidence of corrosion. If this check is not carried out then vital components within the LPS, which may have suffered from corrosion and which could exhibit a high resistance could be missed. This will have a detrimental effect on the whole system making it an unattractive high impedance path for the lightning current to follow. 8.4.2 The earth resistance for all the electrodes must be measured periodically to ensure their usability. 8.4.3 The resistance of the air terminals to the earth electrode should also be measured periodically. 8.4.4 Maintenance Checks For Lightning Protection System Following checks should be carried out at regular interval – once every 06 months: Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 115/124 Version 2.0 8.4.4.1 Inspection of Air Terminal Physical inspection of air terminal and functionality checks with air terminal test meter. 8.4.4.2 Inspection of Down-conductors Check for corrosion Continuity testing by continuity tester, across all types of conductors in lightning protection and grounding system. The resistance should be strived to be as less as possible preferably less than 5.0 ohm. The down conductors are routed, located and electrically bonded as required. 8.4.5 Periodic Check for Earthing System: Earth resistance will be checked at the interval of 6 months with the standard process of measurement (Three point method) and recorded. If the measured value is beyond specified standards, corrective action must be taken. Earth termination systems are interconnected. Where a conductor is totally hidden, its electrical continuity should be tested. In case specified standards of earth resistance are not met, ground conductivity may be improved by Refilling of earth pit with electrolytic compound for electrolytic grounding system where provided. Recharging of earth pits in case conventional grounding system is installed. Physical inspection of connection between ground rod and down conductor near grounding system for corrosion, bad contacts followed by corrective action. 8.4.6 Inspection of Surge Protection devices: All surge protection devices should be checked at an interval of 3 months for their functionality. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 116/124 Version 2.0 Indications provided with surge protection system should be monitored and recorded on daily basis. Faulty devices should be replaced. 8.4.7 Earthing System Inspection Chambers Inspection Chambers of each earthing system should be maintained properly. Grass and other wild growth should be regularly cleared around inspection chamber. Whenever grading or other civil works takes around these chambers, they should be protected properly and should not be allowed to be lost during such works. 8.5 Special Total System Inspection: In the event of occurrence of major lightning strike around the Terminal building and other CNS facility as observed or monitored on the strike record counter, all the aforesaid inspection should be carried out and if need be, the corrective measures to be taken immediately so that LPS is maintained in its optimal effectiveness. 8.6 Inspection Regarding Modifications / Repairs of the Protected Structures While carrying out the periodic maintenance particular attention should be paid, besides earthing and corrosion, to alteration or extensions to the structure that may affect the LPS. Examples of such alterations or extensions are:- a) Change in the use of building; b) Installation of fuel oil storage tank near to building; c) Erection of radio aerials; and d) Installation or alteration to electrical, telecommunications or computing Facilities within or closely connected to the building. 8.7 Records The following records should be kept on site, or by the person responsible for the upkeep of the installation:- a) Scale drawings showing the nature, dimensions and position of all components and Parts of the LPS. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 117/124 Version 2.0 b) The nature of the soil and any special earthing arrangements. c) Date and particulars of salting, if used. d) Test conditions, date and results. e) Alterations, additions or repairs to the system. f) The name and contact details of the person/s responsible for the installation or its upkeep. 8.8 Maintenance Schedules A coordinated programs of inspection and maintenance of the lightning and surge protection systems have been designed in the form of preventive maintenance schedules as given below to ensure its serviceability. 1. Weekly Preventive Maintenance 2. Monthly Preventive Maintenance 3. Inspection after Lightning 4. Pre Monsoon/Pre Winter Maintenance. 8.8.1 Weekly Preventive Maintenance Schedule Visual Inspection (Corrosion, loose connection, dry solder) Surge Protective Devices Status Remarks Air Terminal Down Conductors Connectors of Earth Pit Air terminal & Down conductor Down conductor & Earth Electrode Self diagnostic type of Surge protectors. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 118/124 Version 2.0 8.8.2 Monthly Preventive Maintenance Schedule Surge Protective Devices Status (Resistance of GDT element should be very high) Earth Resistance Value observed Earth Resistance Value of site at the time of Installation Tightness of Connectors of Visual Inspection as given in table at 8.8.1 Air Remarks terminal & Down Conductor Down Conductor & Earth Electrode 8.8.3 Inspection after Lightning Status of surge protector(Resistance of GDT element) Visual Inspection as as given in table 8.8.1 Earth Air Resistance Remarks Terminal & its Connection Down Conductor & its Connection Earth Pit Rx path Tx path Power strip Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 119/124 Version 2.0 8.8.4 Pre Monsoon/Pre Winter Maintenance Earth Resistance Loop Resistance of Air terminal & Down conductor Tightness of Connectors of Greasing of Connectors of Visual inspection As given in table 8.8.1 Equipotential Bonding status Value at Installation Value observed Value at Installation Value observed Air terminal & Down conductor Down conductor & Earth electrode Air terminal & Down conductor Down conductor & Earth electrode Air terminals Down conductor ------------------------------------------------ Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 120/124 Version 2.0 Chapter -9 DEFINITIONS and ACRONYMS 9.1 DEFINITIONS In this Manual, the following definitions shall apply.- 9.1.1 Lightning Flash: Electrical discharge of atmospheric origin between cloud and earth comprising one or more impulse of many kilo amps 9.1.2 Lightning Strokes: The single distinguishable current impulse of a flash. 9.1.3 Lightning Protective System: The whole system of conductors used to protect a structure from the effects of lightning. 9.1.4 Air Termination (Air Termination Network):That part of a lightning protective system which is intended to intercept lightning discharges. 9.1.5 Down Conductor: Conductor that connects an air termination with an earth termination. 9.1.6 Bond: A conductor intended to provide electrical connection between the lightning protective system and other metalwork and between various portions of the latter. 9.1.7 Joint: A mechanical and/or electrical junction between two or more portions of a lightning protective system. 9.1.8 Testing Joint: Joints designed and situated so as to enable resistance or continuity measurements to be made. 9.1.9 Earth Termination (Earth Termination Network) :That part of a lightning protective system which is intended to discharge lightning currents into the general mass of the earth. All points below the lowest testing point in a down conductor are included in this term. 9.1.10 Earth Electrode: That part of the earth termination making direct electrical contact with earth. Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 121/124 Version 2.0 9.1.11 Ring Conductor: Earth termination or electrode fixed to a structure above or below the earth or within or under foundations. A ring conductor may be used alone as an earth termination network or in conjunction with metal rods as an interconnection conductor. 9.1.12 Indicating Plate: A plate detailing the number and position of earth electrodes. 9.1.13 Reference Earth Electrode:An earth electrode capable of being completely isolated from an earth termination network for use in periodic testing. 9.1.14 Log Book:A record of tests and inspections of a lightning conductor installation. 9.2 Acronyms A : Ampere ASR : Airport Surveillance Radar ARSR : Air route Surveillance Radar ANSI : American National Standard Institute ATM system : Air Traffic Management System BS : British standards BIS : Bureau of Indian Standards cm : centimeter CNS : Communication Navigation Surveillance CNS-OM : CNS –Operation & Maintenance Deg. : Degree dia : Diameter DME : Distance Measuring Equipment ES : Earthing System EES : Earth Electrode System IS : Indian Standards (Bureau of India Standards) IEC : International Electro technical Commission IEEE : Institute of Electrical and Electronics Engineers LA : Lightning Arrestor Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 122/124 Version 2.0 LLZ : Localizer LPS : Lightning Protection System Ft : Feet GP : Glide Path kA : Kilo Ampere kmph : Kilometer per hour kV : Kilo volt M(m) : Meter mm : millimeter ms : mill second MIL –STD : Military Standard EEB :Equi-potential Earth Bus bar MEEB :Main Equi-potential Earth Bus bar NDB : Non Direction Beacon NF : Near Field NFPA : National Fire Protection Association MV : Mega Volt RF : Radio Frequency SMR : Surface Movement Radar UL : Underwriters Lab. V : Volt VLSI : Very Large Scale Integrated Circuit ---------------------------- Airports Authority of India CNS Manual Vol. V Ver. 2.0 Lightning, Surge Protection and Earthing System for CNS Installations ------------------------------------------------------------------------------------------------------------------------------------------------------------------ April 2014 Page 123/124 Version 2.0 ******End of CNS Vol. V Ver. 2.0 *****">